Send an Inquiry
ANSI Code Protection Relay

ANSI Protection Relay Codes: Device Number Chart

What are ANSI protection relay codes and why do they matter?

ANSI protection relay codes are numeric function identifiers defined by ANSI/IEEE C37.2-2022: ANSI 50 for instantaneous overcurrent, 51 for time-delayed overcurrent, 87 for differential, and 27 and 59 for voltage. One number names one protection function, so a single-line diagram reads the same in every country. The 87 function shows why suffixes matter: the number says differential protection, while T, G, B or L identifies the transformer, generator, busbar or line zone. The numbering survives because it describes what a device does, not how a maker builds it, so two relays can carry 51 yet differ on curves or reset time. Functions sort into nine working groups, from current and voltage to differential, distance and motor thermal. IEC keeps a parallel set of performance requirements in IEC 60255-1:2022; the two systems are not interchangeable. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

ANSI protection relay codes are the numeric function identifiers defined by ANSI/IEEE C37.2-2022: ANSI 50 for instantaneous overcurrent, ANSI 51 for time-delayed overcurrent, ANSI 87 for differential, ANSI 27 and ANSI 59 for voltage. One number names one protection function, so a single-line diagram drawn in one country reads the same way in every other. The 87 relay function is one example: the number says differential protection is installed, and the suffix T, G, B or L says which zone it guards.

At a glance:

  • Governing document: ANSI/IEEE C37.2-2022, published 14 December 2022 and replacing C37.2-2008
  • What a code does: identifies the protection function rather than the maker’s product name
  • Common pairs: 50/51 for phase faults, 50N/51N for earth faults, 67/67N for directional cases
  • Suffix letters: N for neutral or residual, G for ground, T for transformer, G for generator, B for busbar, L for line
  • IEC equivalents: IEC 60255-151:2009 covers what ANSI 50 and ANSI 51 do; IEC 60255-187-1:2021 covers ANSI 87
  • Typical feeder IED: ANSI 50, ANSI 51, ANSI 50N, ANSI 51N, ANSI 67 and ANSI 50BF
  • Where you meet them: schematic symbols, wiring labels, setting files and factory acceptance test sheets
  • Limits: a code tells you which function exists, never how well anyone implemented it

The numbering survives because it describes what a device does rather than how somebody builds it. Two relays from different makers can both carry ANSI 51 and still differ on curves, reset time and harmonic restraint, but nobody has to guess which element clears which fault.

That is why the ANSI device numbers outlive the hardware. When a relay is swapped out after twenty years, the replacement still matches the drawings, the panel labels and the commissioning sheet.

Every entry in the relay ANSI code list below traces back to ANSI/IEEE C37.2-2022. IEC keeps a parallel set of performance requirements under IEC 60255-1:2022; the two systems are not interchangeable, and a scheme normally cites one family or the other.

Overview of ANSI Protection Relay Codes

ANSI protective relay device numbers, standardized under the IEEE C37.2 standard, are a universal functional coding system for protective relays and intelligent electronic devices (IEDs) in power systems.

Protection relay front panel with the function list used for ANSI protection relay codes (illustrative)

Vendor function names drift apart. What one maker calls a second earth-fault stage, another labels Io>> whatever it likes. ANSI protection relay codes settle that argument with one number per function, recognized in every market.

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

Modern digital relays and IEDs are integrated devices. One enclosure can carry dozens of protection functions that used to need a panel of discrete electromechanical units, which is why one line of markup can describe what sits inside it.

You meet these codes on single-line diagrams, in protection relay setting files, on factory acceptance test sheets and on switchboard wiring labels. Reading them is part of the job for anyone drawing schemes, setting devices or testing panels.

Four results follow from having one numbering system:

  • Unify global protection function definition, eliminating manufacturer technical barriers
  • Simplify engineering drawing design and technical document compilation
  • Improve the compatibility and interchangeability of ABB, Siemens, SEL, Schneider and other mainstream relay devices
  • Standardize project selection, configuration, setting calculation and fault analysis processes

Classification & Full List of Common ANSI Protection Functions

Single-line diagram marked with ANSI device numbers 50, 51 and 51N on a feeder protection scheme (illustrative)

Protection functions sort into nine working groups by application: current, voltage, frequency, differential, distance, power and direction, motor thermal, logic control and special cases. Each ANSI code chart below covers one group, and together they span the protection normally fitted to lines, transformers, generators and motors.

Overcurrent & Earth Fault Protection

ANSI 50 and ANSI 51 are the first pair anyone meets in an ANSI code chart. Between them they clear phase-to-phase and earth short-circuits on distribution feeders, industrial systems and medium-voltage lines: one trips with no intentional delay, the other waits long enough for the device downstream to clear first.

ANSI CodeFull NameFunctional Description & Application
50Instantaneous Overcurrent ProtectionTrips immediately when fault current exceeds the threshold; fast-acting primary protection for short-circuit faults
51Time Overcurrent ProtectionInverse-time or definite-time overcurrent tripping; acts as backup protection for lines and equipment
50N / 50GInstantaneous Earth Fault ProtectionInstant tripping for zero-sequence grounding faults, applicable to neutral grounded systems
51N / 51GTime-Delayed Earth Fault ProtectionTime-limited zero-sequence grounding protection, cooperating with upstream and downstream protection stages
67Directional Overcurrent ProtectionIdentifies fault direction to avoid mal-operation of overcurrent protection in loop networks
67NDirectional Earth Fault ProtectionDirectional judgment for grounding faults, suitable for complex grid and multi-power supply systems

Voltage Protection

This group watches the supply rather than the load. ANSI 27 catches an undervoltage that would stall motors or drop contactors, ANSI 59 catches insulation stress from prolonged overvoltage, and ANSI 47 picks up phase sequence errors and negative-sequence unbalance.

ANSI CodeFull NameFunctional Description & Application
27Undervoltage ProtectionTrips or locks equipment when system voltage drops abnormally to prevent motor stalling and grid collapse
59Overvoltage ProtectionProtects equipment insulation from damage caused by abnormal overvoltage
59NZero-Sequence Overvoltage ProtectionMonitors unbalanced zero-sequence voltage, applicable to ungrounded neutral system grounding fault detection
47Negative Sequence / Phase Sequence ProtectionIdentifies phase sequence error and three-phase voltage unbalance to protect rotating equipment

Frequency Protection

ANSI 81 functions decide islanding and grid-connection. Under-frequency, over-frequency and rate-of-change-of-frequency elements separate a distributed generator from a dead grid quickly enough to keep the rest of the plant running.

ANSI CodeFull NameFunctional Description & Application
81UUnder Frequency ProtectionTrips when system frequency is lower than the rated value, preventing system frequency collapse
81OOver Frequency ProtectionProtects against frequency over-limit caused by generator no-load or light-load over-speed
81RRate of Change of Frequency (ROCOF) ProtectionJudges grid islanding state rapidly, core protection for distributed power grid-connection

Differential Protection

ANSI 87 compares the current going into a zone with the current leaving it. It is the sensitive primary protection for the equipment nobody wants to lose, and the suffix says which one it guards: 87T transformer, 87G generator stator, 87B busbar, 87L line.

ANSI CodeFull NameFunctional Description & Application
87General Differential ProtectionRealizes fault judgment by comparing current difference at both ends of protected equipment
87TTransformer Differential ProtectionPrimary protection for main transformers, removing internal winding short-circuit faults
87GGenerator Differential ProtectionProtects generator stator winding internal short-circuit faults
87BBusbar Differential ProtectionRapid tripping for substation busbar short-circuit faults
87LLine Differential ProtectionPrimary protection for long-distance high-voltage transmission lines

Distance Protection

ANSI 21 measures impedance rather than current magnitude, which lets one function estimate how far away the fault is. One function does two jobs at once: an undelayed trip over the first portion of the line, plus a timed reach that backs up the remote end.

ANSI CodeFull NameFunctional Description & Application
21Distance / Impedance ProtectionJudges fault location by measuring line impedance; serves as primary and backup protection for 110kV and above high-voltage transmission lines, with segmental setting characteristics

Power & Direction Protection

These functions watch direction and state rather than current size. ANSI 32 trips a generator that has started motoring, ANSI 40 catches loss of excitation, ANSI 37 detects under-power, and ANSI 55 handles power factor control on the grid tie-line.

ANSI CodeFull NameFunctional Description & Application
32Reverse Power ProtectionPrevents reverse power transmission of generators to avoid unit damage and grid accidents
40Loss of Excitation ProtectionSpecial protection for generator excitation loss fault, avoiding generator out-of-step operation
37Under Power ProtectionMonitors active power under-limit state of grid-connected equipment
55Power Factor ProtectionControls system power factor to prevent reactive power over-limit and grid loss increase

Thermal & Motor Protection

Rotating equipment needs its own set. ANSI 49 models accumulated heat, ANSI 46 detects current unbalance, ANSI 48 catches a failed or prolonged start, and ANSI 51LR protects against a locked rotor while starting.

ANSI CodeFull NameFunctional Description & Application
49Thermal Overload ProtectionSimulates equipment heat accumulation to protect motors and transformers from long-term overload damage
46Negative Sequence Current / Phase Unbalance ProtectionProtects equipment from heating damage caused by three-phase current unbalance
48Stall / Failed Start ProtectionRapid tripping when motor starts abnormally or stalls under load
51LRMotor Locked Rotor ProtectionExtended function of mainstream relays, dedicated to motor locked rotor fault protection

Control & Auxiliary Logic Functions

These numbers cover outputs and interlocks instead of measurement. ANSI 86 latches a trip so nothing re-closes into the fault, ANSI 94 drives the breaker trip coil, ANSI 74 raises an alarm without tripping, and ANSI 69 enforces the operating interlock.

ANSI CodeFull NameFunctional Description & Application
86Lockout RelayLocks trip state after fault action to prevent repeated closing on fault
94Trip RelayOutputs trip command to drive circuit breaker opening
74Alarm RelayOutputs alarm signal for abnormal operating conditions without tripping
69Control Interlock SwitchRealizes equipment operation interlock and permission control
85Carrier Communication ProtectionRealizes inter-station protection signal transmission and cooperative action

Special Protection Functions

What remains are conditions no fault-current element would recognise. ANSI 25 checks synchronism before closing, ANSI 78 catches out-of-step swings, ANSI 64 monitors stator insulation to earth, and ANSI 50BF trips the neighbouring breakers when the local one refuses to open.

ANSI CodeFull NameFunctional Description & Application
25Synchrocheck ProtectionVerifies voltage, frequency and phase angle consistency before generator/line grid-connection to ensure safe closing
78Out-of-Step ProtectionIdentifies system out-of-step oscillation faults to prevent large-scale grid disconnection
64Ground Insulation ProtectionStator grounding and system insulation monitoring protection for generators
50BFBreaker Failure ProtectionTrips adjacent breakers when the local breaker fails to open, removing fault isolation dead zone

Reading an ANSI Code: Number, Suffix and Prefix Rules

Every entry in the nine tables above is read in two parts: a root number that names the function, followed by nothing at all or by one or two letters saying where and how it applies. The root on its own is rarely enough. ANSI 87 means some kind of differential, but ANSI 87T is transformer differential and ANSI 87G is generator differential, and those involve different CT arrangements, different restraint settings and different commissioning tests. The same pattern runs through the whole list: 50 and 51 for phase overcurrent, 50N and 51N for the residual or neutral path, 50G where a maker separates measured ground current from calculated residual. The root number does most of the work; the letters do the rest.

Two conventions cause most misreads.

First, N and G are not synonyms, however loosely the industry treats them. N marks the neutral or residual path drawn on the scheme, G marks a connection to earth, and the same element gets printed 50N by one maker and 50G by another. Only the setting file tells you which current that element actually measures, and that distinction decides whether a high-impedance earth fault is detected at all. Second, suffixes stack, and the order carries meaning: 87TG is not 87GT, and 50BF shares nothing with 50B or 50N despite looking alike on a crowded drawing. Where a vendor’s documentation and your own habit disagree, the device function list shipped with that model governs, because ANSI/IEEE C37.2 defines the numbers but not every combination anyone implements.

Prefixes work the other way round. They sit in front of the number to record location rather than behaviour, so 21-1 names zone 1 of the distance relay and 87U-ST places a function inside a unit rather than a panel. The ANSI device numbers themselves never change; the prefix is local paperwork that keeps parallel installation records straight.

One practical habit follows. Before altering any setting on an inherited scheme, list every number in the IED function list against the drawings and reconcile the two. Codes present in one place and missing from the other are where errors hide, and they cost far less to find on paper than during a factory acceptance test.

Engineering Matching Configuration of Typical IED Devices

Unlike discrete single-function relays, a digital IED carries several protection elements in one enclosure, which is why the same hardware can be commissioned as a feeder relay or something quite different. A typical EPC feeder IED is configured along these lines, covering most fault scenarios met on distribution circuits:

  • Basic overcurrent protection: 50 / 51 (phase overcurrent) + 50N / 51N (ground overcurrent)
  • Directional protection: 67 / 67N (adapting to multi-power supply grid)
  • High-voltage line core protection: 21 (distance protection)
  • Grid stability protection: 81U / 81O / 81R (frequency protection)
  • Logic safety protection: 86 (trip locking)
  • Fault backup protection: 50BF (breaker failure protection)

Core Engineering Application Value of ANSI Coding System

On international EPC work the same numbers turn up in every document package, and that consistency has measurable value. Four things follow from it:

First, cross-border readability. Numbers defined in ANSI/IEEE C37.2-2022 carry no vendor trademark, so a package drawn in one office can be reviewed, tendered and commissioned in another without a glossary.

Second, compact drawings. Three characters replace a sentence. Single-line diagrams, schematics and parameter lists all shrink, which shortens the review cycle and leaves less room for transcription mistakes.

Third, faster maintenance. A technician who knows the numbers can read an unfamiliar relay, identify which element operated and verify its setting without waiting for the vendor manual.

Fourth, digital mapping. Codes map cleanly onto logical nodes defined in the IEC 61850-8-1:2011+AMD1:2020 station bus, which is why the labels survive the move from copper wiring to GOOSE messaging.

Complete ANSI Device Number List: 1 to 99

The tables above cover the numbers that turn up on most protection drawings. This one is the full C37.2 list in order, for the drawings that carry something you have not met before. Numbers 95 to 99 are reserved for functions that no standard number fits.

ANSI 1 to 20

No.Function
1Master Element
2Time-Delay Starting or Closing Relay
3Checking or Interlocking Relay
4Master Contactor
5Stopping Device
6Starting Circuit Breaker
7Rate of Change Relay
8Control Power Disconnecting Device
9Reversing Device
10Unit Sequence Switch
11Multifunction Device
12Overspeed Device
13Synchronous-Speed Device
14Underspeed Device
15Speed or Frequency Matching Device
16Data Communications Device
17Shunting or Discharge Switch
18Accelerating or Decelerating Device
19Starting-to-Running Transition Contactor
20Electrically Operated Valve

ANSI 21 to 40

No.Function
21Distance Relay
22Equalizer Circuit Breaker
23Temperature Control Device
24Volts per Hertz Relay
25Synchronizing or Synchronism-Check Device
26Apparatus Thermal Device
27Undervoltage Relay
28Flame Detector
29Isolating Contactor
30Annunciator Relay
31Separate Excitation Device
32Directional Power Relay
33Position Switch
34Master Sequence Device
35Brush-Operating or Slip-Ring Short-Circuiting Device
36Polarity or Polarizing Voltage Device
37Undercurrent or Underpower Relay
38Bearing Protective Device
39Mechanical Condition Monitor
40Field Relay (Loss of Excitation)

ANSI 41 to 60

No.Function
41Field Circuit Breaker
42Running Circuit Breaker
43Manual Transfer or Selector Device
44Unit Sequence Starting Relay
45Atmospheric Condition Monitor
46Reverse-Phase or Phase-Balance Current Relay
47Phase-Sequence or Phase-Balance Voltage Relay
48Incomplete Sequence Relay
49Machine or Transformer Thermal Relay
50Instantaneous Overcurrent Relay
51AC Time Overcurrent Relay
52AC Circuit Breaker
53Exciter or DC Generator Relay
54Turning Gear Engaging Device
55Power Factor Relay
56Field Application Relay
57Short-Circuiting or Grounding Device
58Rectification Failure Relay
59Overvoltage Relay
60Voltage or Current Balance Relay

ANSI 61 to 80

No.Function
61Density Switch or Sensor
62Time-Delay Stopping or Opening Relay
63Pressure Switch
64Ground Detector Relay
65Governor
66Notching or Jogging Device
67AC Directional Overcurrent Relay
68Blocking Relay
69Permissive Control Device
70Rheostat
71Level Switch
72DC Circuit Breaker
73Load-Resistor Contactor
74Alarm Relay
75Position Changing Mechanism
76DC Overcurrent Relay
77Telemetering Device
78Phase-Angle Measuring or Out-of-Step Relay
79AC Reclosing Relay
80Flow Switch

ANSI 81 to 99

No.Function
81Frequency Relay
82DC Reclosing Relay
83Automatic Selective Control or Transfer Relay
84Operating Mechanism
85Pilot Communications, Carrier or Pilot-Wire Relay
86Lockout Relay
87Differential Protective Relay
88Auxiliary Motor or Motor Generator
89Line Switch
90Regulating Device
91Voltage Directional Relay
92Voltage and Power Directional Relay
93Field-Changing Contactor
94Tripping or Trip-Free Relay
95Reserved for specific applications
96Reserved for specific applications
97Reserved for specific applications
98Reserved for specific applications
99Reserved for specific applications

Suffix Letters and What They Change

The suffix is not decoration. 87T and 87G share a principle and share nothing else: different CT ratios, different restraint, different commissioning test. Reading the suffix before the number is usually faster.

SuffixApplies the function to
BBusbar. 87B bus differential.
BFBreaker failure. 50BF breaker failure protection.
FField circuit, or feeder. 64F field ground protection.
GGround, or generator. 87G generator differential; 50G ground instantaneous overcurrent.
LLine. 87L line differential.
MMotor. 87M motor differential.
NNeutral. 51N neutral time overcurrent; 59N neutral overvoltage.
PPhase. 50P phase instantaneous overcurrent.
RRotor, as in 64R rotor earth fault. Reclosing when it stands alone, as in 79.
SStator, or secondary. 64S stator earth fault.
TTransformer. 87T transformer differential.

Two rules keep a drawing readable. The suffix never changes the meaning of the number, and a combined code such as 50/51 names two functions that share one current input but not one curve.

Summary

ANSI protection code is the working vocabulary of power system protection. Devices built around these numbers cover current, voltage, frequency, differential, distance and special functions in one enclosure, and being able to read a relay ANSI code list now belongs to anyone drawing schemes, selecting equipment or calculating settings.

The numbers themselves live in ANSI/IEEE C37.2-2022, which assigns every device function number and fixes the suffix and prefix rules, so no manufacturer gets to invent its own meaning. ANSI 32 means reverse power and ANSI 87 means differential wherever the label appears. Two working examples: the way protective relay functions are grouped by number, and how a generator protection relay combines them into one device.

FAQ

Q1: What are ANSI protection relay codes?

A1: They are the numeric identifiers defined in ANSI/IEEE C37.2 that label each protection function inside a relay or IED. Instead of writing out “inverse definite minimum time overcurrent earth fault”, you write ANSI 51N, and every party to the project knows which element you mean.

Q2: Why are ANSI protection relay codes used in international EPC projects?

A2: It eliminates confusing brand-specific function names. Engineers can read schematics, set protection values and debug devices without extra translation.

Q3: Which standard defines ANSI protection relay codes?

A3: ANSI/IEEE C37.2-2022 assigns every device function number and sets out the suffix and prefix rules. It was published on 14 December 2022 and replaced C37.2-2008, which IEEE has withdrawn.

Q4: Can one relay carry several ANSI protection functions?

A4: Yes. Modern digital IEDs integrate dozens of ANSI codes, replacing multiple old single-function electromechanical relays.

Q5: Which fault types do ANSI protection relay codes cover?

A5: It supports overcurrent, undervoltage, frequency, differential, distance, motor stall, ground fault and islanding protection for generators, transformers and feeders.

Q6: Who needs to read ANSI protection relay codes?

A6: EPC designers, relay commissioning technicians, substation O&M staff and overseas power equipment distributors.

Q7: Can ANSI function combinations be customized?

A7: Yes. Functions are enabled in configuration rather than by hardware, so the same unit can be commissioned as a feeder relay built around ANSI 50, 51 and 67, or loaded with a different setting file and used for transformer protection with ANSI 87T.

Q8: Is there a complete ANSI code table?

A8: The nine tables above cover the numbers used in day-to-day work, from ANSI 50 through ANSI 87 and ANSI 50BF. Full device number tables, setting guides and schematic samples ship with the relay documentation.

Q9: Which industries rely on ANSI device numbers most?

A9: Industrial power plants, distribution grids, mining power systems, solar/wind power stations and overseas medium-voltage EPC projects.

Q10: How do I get the device function list for a relay?

A10: Ask for the device function list rather than the brochure. It names the ANSI numbers actually implemented in the model you are considering, which tells you far more about what it can protect.

Conclusion

An ANSI protection relay code compresses a whole protection philosophy into two or three characters. Learn the core group (ANSI 50, 51, 27, 59, 81, 87), learn what the suffix letters do, and you can read any manufacturer’s relay from its ANSI code chart alone, without opening the manual.

That leaves one working habit worth keeping: put a printed relay ANSI code list in the panel folder and check it against the setting file before writing the first value. Most commissioning arguments come from a misread number, not from a bad calculation.

Sources

Revision years below were checked against the publisher catalogues of IEEE SA and the IEC Webstore. Where an IEC functional standard exists for the equivalent ANSI function, it is listed alongside so the two coding families can be read side by side.

SourceWhat it coversTypeEdition
ANSI/IEEE C37.295 device function numbers, 22 acronyms, suffix and prefix rulesIEEE Standard2022
IEC 60255-1Common requirements for measuring relays and protection equipmentIEC Standard2022
IEC 60255-151Over/under current protection, the IEC counterpart to ANSI 50 and 51IEC Standard2009
IEC 60255-127Over/under voltage protection, the counterpart to ANSI 27 and 59IEC Standard2010
IEC 60255-181Frequency and ROCOF protection, the counterpart to ANSI 81U, 81O and 81RIEC Standard2019
IEC 60255-149Thermal protection, the counterpart to ANSI 49IEC Standard2013
IEC 60255-187-1Differential protection for motors, generators and transformers, the counterpart to ANSI 87, 87T and 87GIEC Standard2021
IEC 60255-121Distance protection, the counterpart to ANSI 21IEC Standard2014
IEC 61850-8-1Station bus mapping for protection devices, including GOOSE messagingIEC Standard2011+AMD1:2020

Field record

Substation and transformer work in our project record sits at 10-110 kV: Pakrut and Hamadoni substations in Tajikistan, Sakaka and Al-Jalamid in Saudi Arabia, and mine and industrial substations across Myanmar at 35-110 kV. The industrial side is where the ANSI codes get exercised hardest – cement plants in Myanmar and Ghana, steel plants in Vietnam and Thailand, copper-cobalt mining in DR Congo. All 93 projects are listed by country in the project record.

The nine tables above name functions; the pages below go into what each one does on real equipment. If the numbering itself is new to you, start with the definition and types of protective relays, then follow whichever branch matches the object you are protecting. Each one works through settings, wiring and typical faults for a single device family.

Related: What Are Protective Relays? Types, Functions and Working Principle

Questions on the settings in this guide go to the engineering team, normally answered the same working day.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.