-
Leon Zhang Sales Manager
-
Email: sale@relayprotect.com
-
Phone/WhatsApp: +86 13655813266
87T Relay AST-441H for Transformer Differential Protection
AST-441H 87T relay for two-winding and three-winding transformer differential protection: biased differential, harmonic restraint, IEC 61850. MOQ 1 unit.
Description
87T relay AST-441H is a numerical transformer differential protection relay for two-winding and three-winding power transformers. It compares the currents entering and leaving the protected zone and trips the transformer breakers when the difference points to an internal fault. Biased differential, second-harmonic inrush restraint, CT ratio correction and vector group compensation are built in, and the functions follow IEC 60255-187-1:2021 with ANSI/IEEE C37.2-2022 device numbers.
The relay is specified for substation, industrial and power plant transformers rated 110 kV and below. Channel count, protocol and mounting follow the project, so one build covers a 10 MVA distribution unit and a step-up transformer through different configuration files.
One model covers both winding counts.

87T is the ANSI/IEEE C37.2-2022 device number for transformer differential protection. PDIF is the IEC 61850 logical node for the same function, the functional requirements sit in IEC 60255-187-1:2021, and product safety follows IEC 60255-27:2023. The full list sits in the Technical References table.
Specifications and ordering data last reviewed October 2026.
| Ordering fact | AST-441H |
|---|---|
| Models | AST-441H, one differential platform for two-winding and three-winding transformers |
| Rated | 1 A or 5 A CT secondary, AC/DC 220 V auxiliary supply, 100 V AC voltage input |
| Lead time | 4 to 6 weeks from order confirmation, expedited build on request |
| MOQ | 1 pc |
At a Glance
- AST-441H covers two-winding and three-winding transformer differential duty in one build.
- Biased differential with slope 0.30 to 0.70 and second-harmonic restraint 0.10 to 0.70.
- CT inputs accept 1 A or 5 A secondaries, with software ratio and vector group compensation.
- Auxiliary supply is AC/DC 220 V, rated AC voltage input is 100 V at 50 Hz.
- Station integration runs over IEC 61850, IEC 60870-5-103, Modbus RTU or Ethernet.
- Trip contacts carry 50 W breaking capacity with a make current up to 5 A.
- Mounting is 19-inch chassis or drawout case, for panel or DIN rail.
- Commercial terms: MOQ 1 unit, 4 to 6 week lead time, 12-month warranty.
The sections below cover what the relay measures, how it is ordered and where it does not fit.
AST-441H 87T Relay Overview
The AST-441H is built around one differential element set that serves both winding counts. Two-winding projects use the high voltage and low voltage current inputs. Three-winding projects add the medium voltage side. The relay applies amplitude, phase and zero-sequence compensation in software, so the CTs can be wired star on both sides.
Measured values, event records and fault records stay on the device for commissioning and post-fault analysis. Settings live in one menu tree, and the same file can be copied between relays guarding identical transformers.
Transformer protection rarely stops at 87T. Backup overcurrent, non-electrical protection and measurement usually share the same panel; the scheme view is in the transformer protection relay article.
Key Features of the 87T Transformer Differential Protection Relay
1. ANSI 87T Differential Protection
High-speed differential protection for internal transformer faults within the protected zone.
2. Percentage-Biased Differential Protection
Bias restraint keeps the relay stable through external faults and CT errors.
3. CT Ratio and Phase Compensation
Transformer-side currents are compensated for CT configuration and transformer vector group.
4. Harmonic Restraint
Second-harmonic restraint holds the relay back during energization and magnetizing inrush.
5. Fault and Event Recording
Protection operations, events and fault records support commissioning and post-fault analysis.
6. Flexible CT Input
1 A and 5 A rated CT secondaries, selectable per project.
7. Communication Interfaces
Project-dependent RS-485, Ethernet and IEC 60870-5-103 ports, with IEC 61850 and Modbus options.
8. Protection and Control Integration
Integrates with transformer protection, measurement, control and substation automation systems.
Transformer Protection Functions and ANSI Codes
The function list below is the AST-441H set. Device numbers follow ANSI/IEEE C37.2-2022, the differential function maps to PDIF in IEC 61850, and inrush restraint maps to PHAR.
| Protection Function | ANSI Code | IEC 61850 Node | Purpose |
|---|---|---|---|
| Transformer Differential Protection (biased) | 87T | PDIF | Main protection for internal transformer faults |
| High-Speed Differential Protection (unrestrained) | 87T | PDIF | Fast operation for severe internal faults |
| CT Open-Circuit Detection | n/a | n/a | Detects abnormal CT secondary conditions |
| Differential Current Alarm | n/a | n/a | Warns of abnormal differential current |
| Harmonic Restraint | n/a | PHAR | Prevents unwanted operation during inrush |
General Technical Data
| No. | Parameter Category | Core Technical Specification |
|---|---|---|
| 1 | Power Supply & Rated Electrical Parameters | 1. Rated control voltage: AC/DC 220 V 2. Power supply ripple coefficient: ≤ 5% 3. Voltage tolerance: -20% to +15% 4. Rated AC current In: 1 A/5 A (specify when ordering) 5. Rated AC voltage: 100 V 6. Rated frequency: 50 Hz (customizable per project requirements) |
| 2 | Power Consumption | 1. DC power circuit: ≤ 25 VA (normal operation), ≤ 30 VA (device activated) 2. AC voltage circuit: ≤ 1 VA/phase (at 100 V rated voltage) 3. AC current circuit: ≤ 0.5 VA/phase (1 A In), ≤ 1 VA/phase (5 A In) |
| 3 | Output Contact Performance | 1. DC circuit: 50 W breaking capacity (voltage ≤ 250 V, current ≤ 0.5 A, time constant 5 ± 0.75 ms); allowable make current ≤ 5 A 2. AC circuit: 50 W breaking capacity (voltage ≤ 250 V); maximum allowable make current 5 A |
| 4 | Insulation Performance | Insulation resistance, dielectric withstand and impulse voltage tests follow IEC 60255-27:2023, which covers insulation coordination and product safety for measuring relays and protection equipment. |
Rated frequency is 50 Hz as standard, and 60 Hz builds follow project requirements. The values above are type-test ratings, not settings.
Global Supply and Delivery Terms
Ship from Shanghai or Ningbo | 4 to 6 weeks for standard relays, 6 to 8 weeks for panels | FOB / CIF / DDP available.
What Is an 87T Relay?
An 87T relay is a transformer differential protection relay that compares the currents entering and leaving the protected transformer zone to detect internal electrical faults.
- 87 = differential protection
- T = transformer
- 87T = transformer differential protection, defined in IEC 60255-187-1:2021
The device number comes from ANSI/IEEE C37.2-2022. In IEC 61850 the same function is the PDIF logical node, which is what the relay exposes on the station bus.
How Does an 87T Relay Work?

| Condition | Differential current | Relay response |
|---|---|---|
| Normal load or external fault | I₁ ≈ I₂, low | No trip; restraint holds |
| Internal fault | I₁ ≠ I₂, high | 87T operates and the transformer breaker trips |
During energization the magnetizing inrush carries a strong second-harmonic component. The relay measures that component and blocks the differential element while it lasts, which is why a correctly set relay rides through energization without tripping. The harmonic threshold is a setting, not a fixed value.
Through faults outside the zone push the restraint current up. The biased characteristic raises the operate value with it, so CT errors and saturation do not turn into a trip. The calculation behind those values is worked step by step in the 87T setting guide.
87T Relay Settings
The AST-441H keeps every differential setting in one menu tree. The table below is the setting menu as it appears on the device: display name, range, step and remark. It is the envelope the relay accepts, not a recommended project setting.
Pickup, slope and harmonic values for a given transformer are calculated in the 87T setting calculation guide, and the differential protection setting calculation article works a full example end to end.
| No. | Display Name | Range | Step | Remark |
|---|---|---|---|---|
| 1 | High-speed Differential Setting | |||
| 1.1 | High-speed Differential Protection | 1/0 | n/a | Enable(1) / Disable(0) |
| 1.2 | High-speed Differential Setting Value | 0.40-99.99A | 0.01A | |
| 2 | Differential Protection Setting | |||
| 2.1 | Differential Protection Enable | 1/0 | n/a | Enable(1) / Disable(0) |
| 2.2 | CT Broken Circuit Blocking Differential | 1/0 | n/a | CT break blocking function: Enable(1) / Disable(0) |
| 2.3 | Differential Current Setting | 0.50-99.99A | 0.01A | |
| 2.4 | Restraint Current Setting | 0.50-99.99A | 0.01A | |
| 2.5 | Differential Bias Current Setting | 0.50-99.99A | 0.01A | |
| 2.6 | CT Broken Circuit Threshold | 0.50-99.99A | 0.01A | |
| 2.7 | Harmonic Restraint Coefficient | 0.10-0.70 | 0.01 | Second harmonic restraint ratio |
| 2.8 | Slope / Ratio Restraint Coefficient | 0.30-0.70 | 0.01 | |
| 2.9 | Balance Coefficient | 0.100-1.999 | 0.001 | |
| 3 | Overcurrent Fan Control | |||
| 3.1 | Overcurrent Fan Start | 1/0 | n/a | Enable(1) / Disable(0) |
| 3.2 | Ventilation Time Delay | 0.00-999.99s | 0.01s | |
| 3.3 | Fan Start Current Setting | 0.5-99.99A | 0.01A | |
| 4 | General Setting | |||
| 4.1 | Motor Differential Mode Selection | 1/0 | n/a | |
| 4.2 | HV Side Y/△-11 Connection | 1/0 | n/a | |
| 4.3 | HV Side Y/△-01 Connection | 1/0 | n/a | |
| 4.4 | Secondary Wiring Mode | 1/0 | n/a | Delta/Y(1) / Y/Y(0) |
| 4.5 | Control Circuit Break Alarm | 1/0 | n/a | Alarm enable(1) / disable(0) |
| 4.6 | Current Angle Display | 1/0 | n/a | |
| 4.7 | Secondary Current Rated | 1/0 | n/a | 1A input(1) / 5A input(0) |
| 4.8 | Inter-tripping C6C7 | 1/0 | n/a | High-speed & differential trip C06C07(1) |
| 4.9 | Rated Secondary Current | 0.50-99.99A | 0.01A | HV side CT secondary rated current |
87T Transformer Differential Protection Zone

The protected zone covers the windings between the CTs on each side. Busbar and line duties stay with other relays, because IEC 60255-187-1:2021 covers motor, generator and transformer differential only, and leaves busbar and line differential schemes outside its scope.
87T vs 50/51 Transformer Protection
| Feature | 87T | 50/51 |
|---|---|---|
| Protection principle | Differential current | Overcurrent |
| Main protection area | Transformer internal zone | Backup / overcurrent |
| ANSI code | 87T | 50/51 |
| CT requirement | CTs on transformer sides | Current measurement CT |
| Internal winding faults | Highly sensitive | Depends on fault current |
| External fault stability | Bias/restraint | Time-current coordination |
| Typical role | Main transformer protection | Backup protection |
A transformer scheme normally carries both. 87T clears internal faults fast, and 50/51 picks up whatever the differential element cannot see, such as a fault fed from the low voltage side with a weak source behind it.
How to Test an 87T Relay?

Before commissioning the transformer differential protection, technicians shall check the relay wiring, verify the CT ratio and CT polarity, and confirm the correctness of transformer vector group compensation; subsequently, perform a full secondary injection test, including differential pickup test, bias and slope characteristic test, harmonic restraint test, and trip output test, and finally record and verify all test results so protection performance is checked against design requirements.
The infographic lists the same ten steps in order. Two checks catch most wrong wiring: a single-side injection that moves the differential current in the expected direction, and a trip output test that proves the trip coil and the breaker trip circuit, including any surge suppressor fitted across the coil.
A stuck breaker shows up here as a trip command with no change in breaker status. Record it, do not re-energize, and clear the mechanism first.
Transformer Differential Protection Relay Applications
Power Substations
Transformer main protection for substation applications, reporting to the station automation system. The full relay range sits in the substation protection relays category.
Industrial Power Systems
Protection for transformers supplying industrial plants and large electrical loads.
Power Plants
Transformer protection for generator step-up and auxiliary transformers where applicable.
Distribution Transformers
Suitable relay configurations for medium-voltage transformer protection.
EPC Substation Projects
Suitable for protection and control panel integration, commissioning and project-specific relay configuration.
How to Select a Transformer Differential Protection Relay
| Selection Factor | What to Check |
|---|---|
| Transformer Rating | MVA and voltage levels |
| Transformer Vector Group | YNd11, Dyn11, Yy, etc. |
| CT Ratio | HV/LV CT ratios |
| CT Secondary | 1 A or 5 A |
| Protection Functions | 87T, backup protection, alarms |
| Communication | Required substation protocol |
| Fault Recording | Number of channels and record capacity |
| Installation | Panel or rack mounting |
| Project Standard | IEC / utility / EPC specification |
Selection starts with the transformer nameplate: MVA rating, voltage ratio and vector group. CT ratios on both sides come next, because a mismatch above roughly 4:1 needs interposing CTs. Protocol, mounting and record depth follow the station design.
Ordering Information: What to Specify
One ordering sheet covers the build. Send the rows below with the enquiry, and the returned quotation carries the model, the price band and the lead time together.
| Item | What to specify |
|---|---|
| Model | AST-441H |
| Winding count | Two-winding or three-winding |
| CT secondary | 1 A or 5 A |
| Auxiliary supply | AC/DC 220 V (other voltages on request) |
| Communication | IEC 61850, IEC 60870-5-103, Modbus RTU/TCP or Ethernet |
| Mounting | 19-inch chassis, drawout case, panel or DIN rail |
Price band: the AST-441H is quoted per configuration rather than listed, because the protocol option and the record depth move the build. Enquiries with the full sheet come back with a firm price inside one working day.
When an AST-441H Is Not the Right Choice
87T is main protection for a transformer zone. It is the wrong tool in four situations.
- Backup duty only. If the requirement is backup overcurrent, a 50/51 relay costs less and does the job.
- Busbar or line differential. IEC 60255-187-1:2021 covers motor, generator and transformer differential; busbar and line differential schemes are separate functions.
- No CTs on both sides. The relay compares two current sets, so a small distribution transformer with a single CT set cannot feed a differential zone.
- No one to own the settings. A relay left on default values drifts into nuisance trips or slow operation. Commissioning and periodic verification need a named owner.
Three failure modes show up in service. A wrong second-harmonic setting trips the relay on every energization. Deep CT saturation during a through fault can lift the differential current above the bias characteristic. A stuck breaker leaves the fault connected after a correct trip.
Why Choose Our 87T Transformer Differential Protection Relay?
Project-Based Configuration
Relay parameters and functions can be configured according to transformer ratings and project protection requirements.
Technical Documentation
Provide technical specifications, wiring diagrams, configuration information and supporting documentation for project review.
Factory Testing / Pre-Shipment Verification
Provide functional verification and configuration checks before shipment according to the agreed project requirements.
EPC Support
Support technical communication during relay selection, panel integration and commissioning.
Replacement and Alternative Applications
Suitable for projects requiring an alternative transformer differential protection relay, subject to technical compatibility and project approval.
Request a Quote for 87T Transformer Differential Protection Relay
Send your transformer rating, voltage ratio, vector group, CT ratios, required protection functions and communication protocol. Our technical team can review the application and recommend a suitable relay configuration.
A complete ordering sheet, as listed in the ordering information table, returns a configuration, a datasheet and a quotation together.
How do I place an order?
Send your specification through the contact form, by email to sale@relayprotect.com or on WhatsApp. We check the rating, the protocol and the wiring against your application, confirm the model, and return a quotation. No account or registration is needed.
What is the minimum order quantity?
The minimum order quantity is one unit. A single unit can be ordered for evaluation or for a pilot installation, and project quantities are quoted separately.
What is the lead time?
Standard models ship in 7 to 15 working days after the order is confirmed and payment is received. Custom ratings, protocols or mounting arrangements are confirmed in writing before the order is placed, so the delivery date is known in advance.
Which payment methods and trade terms do you accept?
Payment by T/T, L/C, Western Union or PayPal. Trade terms are EXW, FOB, CIF and DDU. Every relay carries a 12-month warranty.
FAQ
1. What is a transformer differential protection relay?
A primary protection device that detects internal transformer faults (e.g., turn-to-turn and phase-to-phase faults) by comparing currents on both sides, and trips to isolate the transformer upon fault detection.
2. What is ANSI 87T protection?
ANSI 87T is the standard function code for transformer differential protection. 87 denotes differential protection, and T stands for transformer. The functional requirements sit in IEC 60255-187-1:2021.
3. What transformer faults does an 87T relay protect against?
Internal faults including:
- Turn-to-turn faults
- Phase-to-phase short circuits
- Ground faults
- Winding open circuits/breaks
- Core faults (e.g., overheating from multiple ground points).
4. Does the relay support 1A and 5A CT inputs?
Yes. Both 1A and 5A CT secondary inputs are supported and configurable via relay settings.
5. How does the relay compensate for transformer vector group?
It applies software-based amplitude and phase correction to match different vector groups (e.g., Ynd11, Dyn1). Users only need to enter the vector group and connection type; the relay calculates the differential current automatically.
6. How does 87T protection prevent transformer inrush tripping?
It uses harmonic restraint (mainly second-harmonic braking). During inrush, the high second-harmonic content raises the operating threshold or blocks the protection, preventing false trips.
7. What communication interfaces are available?
Common options include:
- RS485 (Modbus RTU)
- Fiber optic Ethernet (IEC 61850, Modbus TCP)
- Fiber optic serial ports
- Optional: Profibus, DNP 3.0 (select models).
8. What information is required to select a transformer differential protection relay?
Key parameters needed:
- Rated capacity (MVA/kVA)
- Voltage ratio (e.g., 110kV/10kV)
- Vector group (e.g., Ynd11)
- CT ratios and connection types (both sides)
- Required protection functions
- Communication protocol
- Power supply and installation environment.
9. Can the relay be integrated into a transformer protection and control panel?
Yes. It is available in 19-inch chassis or drawout modules, supporting panel or DIN-rail mounting, and can be integrated with other protection and control devices in a cubicle.
10. How can I request the technical datasheet and quotation?
Contact us via:
- Sales email (with project requirements and transformer parameters)
- Technical support hotline
- Online inquiry form on our website.
Our team will recommend the right model and provide a quotation and datasheet accordingly.
11. What is the price band for the AST-441H?
The AST-441H is quoted per configuration, so there is no list price. Send the transformer rating, winding count, CT ratios and protocol, and the reply carries the model, the price band and the lead time together.
12. What is the MOQ and lead time?
MOQ is 1 unit for samples. Standard delivery is 4 to 6 weeks from order confirmation, and expedited builds are available for urgent projects.
13. What warranty and support come with the relay?
Each relay carries a 12-month warranty. Spare parts, firmware updates and commissioning support are included, and setting guidance is free of charge.
14. What are the payment and delivery terms?
Prices are quoted EXW, FOB, CIF or DDU. Payment is accepted by T/T, L/C, Western Union or PayPal.
15. Can the AST-441H replace a differential relay from another brand?
Often yes, subject to CT ratio range, auxiliary supply and protocol compatibility. Send the existing relay model and its setting file, and the team confirms the fit before an order.
16. Do you run factory tests before shipment?
Every relay undergoes functional verification and a configuration check before dispatch, against the agreed project requirements. The test report ships with the unit.
Related Products and Systems
- Three-winding transformer differential protection relay: for transformers with a third, medium voltage winding.
- Transformer backup protection relay: the overcurrent and backup duty that shares the panel with 87T.
- Substation protection relays: the full relay range for station and bay duty.
Background reading: 87T setting calculation, differential relay protection (87T, 87B, 87G and 87L compared) and star-delta transformer differential protection.
Conclusion
An 87T relay earns its place on every transformer where a fast, selective main protection matters. The AST-441H covers two-winding and three-winding duty with biased differential, second-harmonic restraint and software vector group compensation, and it reports to the station bus over IEC 61850 or IEC 60870-5-103. Send the ordering sheet, and the datasheet, price band and lead time come back together.
Technical References
The standards below are the ones this relay is built around. Editions are listed so the quotation and the site specification can be checked against the same documents.
| Standard | Edition | What it governs on this relay | Source |
|---|---|---|---|
| IEC 60255-187-1:2021 | 2021 (Ed 1.0, Cor. 1:2023) | Functional requirements for restrained and unrestrained differential protection of motors, generators and transformers (87T, PDIF, PHAR) | IEC Webstore |
| ANSI/IEEE C37.2-2022 | 2022 | Device function numbers: 87T transformer differential protection | IEEE SA |
| IEC 60255-1:2022 | 2022 | Common requirements for measuring relays and protection equipment | IEC Webstore |
| IEC 60255-27:2023 | 2023 (Ed 3.0) | Product safety: insulation coordination, dielectric and impulse withstand | IEC Webstore |
| IEC 61850 | Edition 2.1 (core documents consolidated from 2020) | Station bus communication, MMS reporting and GOOSE, PDIF logical node | IEC Webstore |
| IEC 60870-5-103:1998 | 1998 | Companion standard for the informative interface of protection equipment | IEC Webstore |
Editions move. Check the year before the specification goes out.
Need pricing, a datasheet or a wiring drawing?
Tell us your transformer rating, voltage ratio, vector group and CT ratios, and we will send a quotation with the matching model. Free technical guidance, parameter setting and commissioning support are included.
MOQ 1 unit for samples | Standard delivery 4 to 6 weeks from order confirmation | 12-month warranty | EXW, FOB, CIF, DDU | Payment by T/T, L/C, Western Union or PayPal. New to ordering? See how to order for process, MOQ and lead time.











xiao zhang –
Transformer differential relay (87T) adopts percentage restraint algorithm, strong anti-CT-saturation capability and CT break lockout. Instant trip for internal winding faults, flexible parameter setting and multi-communication options for all types of distribution & power transformers.