87T Three winding transformer protection

The AST-442H transformer differential protection device is mainly applied to three winding transformer protection , realizing differential protection for high, medium and low voltage sides. It fits voltage levels up to 133 kV and adopts panel mounting installation style.

ANSI:87/87T/50

Communication Mode

Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103), IEC 61850

In-house Factory & Technical Team, OEM ODM Custom Electrical Equipment

Description

Overview of Three winding transformer protection

Transformer protection methods

  • Differential protection ANSI 87
  • 2nd & 3rd harmonic restraint
  • Differential instantaneous trip protection ANSI 87
  • Differential current overload alarm
  • TA disconnection detection ANSI 50
  • Non-electrical protection signal acquisition
  • B-code & NTP time synchronization

Wiring Diagram

Setting Table

No. Setting Name Unit Range Remark
1 Secondary Rated Current(Ie) A 0.05~30 Calculated based on HV side rated current of transformer
2 Differential Protection Setting Ie 0.1~2
3 Differential Instantaneous Trip Setting Ie 0.1~20
4 Percentage Restraint Coefficient 0.3~1
5 2nd Harmonic Restraint Coefficient 0.1~0.3
6 3rd Harmonic Restraint Coefficient 0.1~0.3
7 MV Side Balance Coefficient 0~10
8 LV Side Balance Coefficient 0~10
9 Differential Current Overlimit Setting Ie 0.1~1 Generally 50% of differential protection setting
10 Differential Current Overlimit Delay s 0.1~20.00

Switch Status

No. Control Word Option Remark
1 yyy □ Disable □ Enable
2 ydd1 □ Disable □ Enable
3 ydy1 □ Disable □ Enable
4 yyd1 □ Disable □ Enable
5 ydd11 □ Disable □ Enable
6 ydy11 □ Disable □ Enable
7 yyd11 □ Disable □ Enable
8 dyy11 □ Disable □ Enable
9 dyy1 □ Disable □ Enable
10 Differential Instantaneous Trip □ Disable □ Enable
11 2nd Harmonic Restraint □ Disable □ Enable
12 3rd Harmonic Restraint □ Disable □ Enable
13 Phase A Differential Protection □ Disable □ Enable
14 Phase B Differential Protection □ Disable □ Enable
15 Phase C Differential Protection □ Disable □ Enable
16 Differential Current Overlimit Alarm □ Disable □ Enable
17 CT Disconnection Signal Output □ Disable □ Enable
18 Differential Blocking by CT Disconnection □ Disable □ Enable

Outline and Installation Dimensions

   

FAQ

Q:What is the protection scope of transformer differential protection?

A:The scope of differential protection in transformer covers internal windings, insulating bushings and connecting wires on all sides.

Q:How to Select Differential Protection Current Transformers?

A:When selecting current transformers (CTs) for differential protection, choose Type P or TPY CTs of the same model to ensure that the turns ratio matches, the accurate limit factor (ALF) is sufficiently high (at least 20 times), and the actual load is less than the rated load, in order to prevent false tripping due to saturation caused by faults outside the protection zone.

Q:Core Issues and Solutions of Differential Protection of Star Delta Transformers Caused by Two-side Current Phase Deviation?

A:The core issue with Y/d transformer differential protection is that there is a 30° phase difference between the currents on the two sides; directly incorporating this would result in a significant unbalanced current. Solution: Connect the secondary windings of the CTs on the star side in a delta configuration, and the secondary windings of the CTs on the delta side in a star configuration. This compensates for the phase difference through the wiring, thereby canceling out the differential current.

Q:What functions are generally enabled for medium voltage transformer protection?

A:Generally speaking, medium voltage covers 6 kV to 35 kV. Main transformers shall be equipped with differential protection, backup protection and non-electrical protection. Distribution transformers require three-stage current protection, overload protection and zero-sequence current protection. Specific requirements vary with actual operating conditions.

Q:What is the calculation method for transformer differential protection?

A:

Transformer differential protection calculation:

The core of transformer differential protection calculations is the elimination of unbalanced currents. Take, for example, a 10/0.4 kV transformer with a Y/d-11 connection:

Calculate secondary rated current of each side:

HV side CT ratio: 400/5

LV side CT ratio: 2000/5

Balance coefficient and phase compensation:
The microprocessor-based protection multiplies HV side current by balance coefficient
and implements Y-Δ phase shift to eliminate normal differential current.
Setting parameters:Minimum operating current: 0.4 times rated current;Percentage restraint coefficient: 0.5;2nd harmonic restraint coefficient: 0.15 (to block inrush current);Differential instantaneous trip setting: 6 times rated current

Reviews

There are no reviews yet.

Be the first to review “87T Three winding transformer protection”

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.