Send an Inquiry
Distribution Room Secondary Equipment

Distribution Room Secondary Equipment: Types, Functions and Applications

Table of Contents

What is secondary equipment in a distribution room?

Distribution room secondary equipment is the low-voltage devices that measure, protect, control and report on the primary switchgear: protection relays, meters, automation terminals, gateways, fault recorders and the DC supply keeping them alive. A transformer, breaker and busbar move energy at 6 to 35 kV; the relay, meter and RTU work at 48, 110 or 220 V DC and never carry load current. That split is the whole definition, and why the secondary layer can be replaced and re-tested without taking primary plant out of service. ANSI/IEEE C37.2-2022 assigns the device numbers on every single-line diagram: 50/51, 50N/51N, 87, 67 and 79. IEC 60255-1:2022 states what measuring relays must meet; IEC 61869-2:2012 and IEC 61869-3:2011 fix the CT and VT outputs feeding them. Secondary equipment is bought against signal and communication requirements, bench-tested and swapped without an outage; primary equipment is bought against fault ratings. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

Distribution room secondary equipment is the set of low-voltage devices that measure, protect, control and report on the primary switchgear: protection relays, meters, automation terminals, protocol gateways, fault recorders and the DC supply that keeps them alive. Seven categories cover every device on a modern room’s equipment list, and each answers a different question.

Seven categories. One equipment list.

Primary equipment carries the power, and distribution room secondary equipment watches it. A transformer, a circuit breaker and a busbar move energy at 6 kV to 35 kV. The relay, the meter and the RTU work at 48 V, 110 V or 220 V DC and never carry load current. That split is the whole definition, and it is also why the secondary layer can be replaced, re-tested and upgraded without taking primary plant out of service.

Three documents set the boundaries. ANSI/IEEE C37.2-2022 assigns the device numbers used on every single-line diagram: 50/51, 50N/51N, 87, 67, 79. IEC 60255-1:2022 states what measuring relays and protection equipment have to meet. IEC 61869-2:2012 and IEC 61869-3:2011 fix the CT and VT outputs that feed them.

Distribution room secondary equipment laid out on a relay and metering panel (illustrative)

Distribution Room Secondary Equipment: At a Glance

Seven categories, and the device that gives each one away:

  • Protection relays hold the ANSI functions: 50/51 overcurrent, 50N/51N earth fault, 87 differential, 67 directional and 79 reclosing.
  • Measurement and metering covers multifunction power meters, revenue energy meters and power quality analysers.
  • Distribution automation terminals split by location: RTU at the substation, DTU at the ring main unit, FTU on the pole switch, TTU at the transformer.
  • Control and monitoring brings control panels, PLC logic, HMI screens, remote I/O and alarm annunciators.
  • Communication is the Ethernet switches, protocol gateways, fibre runs and RS485 trunks that move the data.
  • Fault recording captures waveforms, disturbance records and time-stamped sequences of events.
  • DC and auxiliary power means the DC panel, battery charger, station battery, UPS and DC monitoring that keep the rest alive.
  • A minimum viable room still needs five things: one feeder relay, one multifunction meter, one automation terminal, one DC supply and one gateway.

The protocol layer behind category five is covered in Modbus and IEC 61850 substation communication protocols. Picking the relay itself is a separate decision, set out in medium voltage protection relay selection. A panel that combines measurement and control in one cubicle is described under common measurement and control panel.

Secondary Equipment Definition: What Counts in a Distribution Room

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

The secondary equipment definition engineers actually work from is a functional one: any device in the room that does not carry load current but measures, protects, controls or reports on the equipment that does. A protection relay, a meter, a terminal unit and a DC panel all qualify. A surge arrester and a cable termination do not, because they sit in the power path.

That boundary matters for procurement as much as for design. Secondary equipment is bought against signal and communication requirements, tested on a bench, and replaced without an outage on the primary circuit. Primary equipment is bought against fault ratings and cannot be swapped without switching the network.

The table below pairs each primary item with the secondary device that watches it.

Primary EquipmentSecondary Equipment
TransformerProtection Relay
Circuit BreakerMeasurement Device
BusbarRTU / FTU / DTU
CableSCADA
SwitchgearCommunication Gateway
CT / VTControl & Monitoring System
Primary and secondary equipment pairing: transformer to protection relay, breaker to meter, busbar to RTU

Types of Secondary Equipment in Distribution Rooms

Secondary equipment in a distribution room refers to all low-voltage devices that monitor, control, protect, and communicate with the primary power system. While primary equipment such as transformers, circuit breakers, and busbars handle the actual power flow, secondary equipment processes signals, executes protection logic, records operational data, and enables remote control .

Below are the seven main secondary equipment types you will find in a modern distribution room, ordered by the question each one answers about the network.

1. Protection Relays

Protection relays are the most critical secondary devices in any distribution room. They continuously monitor electrical parameters (current, voltage, frequency, and phase angle) and issue trip or alarm commands when abnormal conditions are detected .

The distribution room protection devices in this group are named after their ANSI device numbers, which is why one hardware platform often ships under several names. Common types of protection relays:50/51 + 7987T + 50/5149 + 46 + 4887G + 40

Relay TypeANSI CodeApplication
Overcurrent Protection Relay50/51Detects excessive current from short circuits or overloads
Earth Fault Protection Relay50N/51NDetects phase-to-ground leakage currents
Feeder Protection RelayProtects distribution feeders with multiple functions
Transformer Protection RelayDifferential and backup protection for power transformers
Motor Protection RelayProtects motors from overload, stall, and unbalance
Differential Protection Relay87Compares currents entering and leaving a protected zone
Directional Protection Relay67/67NDetects fault direction in looped networks
Generator Protection RelayProtects generators from internal and external faults

Modern numerical relays combine multiple protection functions in a single device, replacing racks of discrete electromechanical relays . This makes them ideal for space-constrained distribution rooms.

2. Measurement and Metering Equipment

Measurement devices provide real-time data on system performance and energy consumption. Billing, load management and power quality assessment all run off this data.

Key devices include:

  • Multifunction Power Meter: Measures current, voltage, power, frequency, and power factor
  • Energy Meter: Records active and reactive energy consumption
  • Power Quality Analyzer: Monitors harmonics, sags, swells, and transients
  • Voltage Measurement: PT-based or direct voltage sensing
  • Current Measurement: CT-based current sensing
  • Frequency Measurement: Monitors system frequency stability
  • Power Factor Measurement: Critical for reactive power management

These devices provide the data needed for load profiling, demand forecasting, and energy efficiency improvements.

3. Distribution Automation Terminals

Distribution automation terminals are the brains of a modern distribution network. They enable unattended operation, remote control, and rapid fault handling .

Terminal TypeFull NamePrimary Function
FTUFeeder Terminal UnitMounted on pole-mounted switches (10kV breakers, load switches). Collects electrical parameters, monitors line status, and executes remote open/close commands
DTUDistribution Terminal UnitInstalled in ring main units, switching stations, and compact substations. Collects switch position signals, voltage, current, and power data. Performs fault identification, isolation, and non-fault zone restoration
TTUTransformer Terminal UnitInstalled at distribution transformers. Monitors transformer operating conditions: voltage, current, power, energy. Records historical data for load analysis and fault detection
RTURemote Terminal UnitBasic automation unit for monitoring and controlling transformers, breakers, reclosers, sectionalizers, and capacitor banks. Communicates with the master station to provide operational data and execute control commands

In the distribution automation hierarchy: Master Station → Substation → FTU/DTU/TTU work together to enable fault detection, isolation, and service restoration .

4. Control and Monitoring Equipment

Control equipment allows operators to manage the distribution system locally or remotely. These devices provide the human-machine interface and logic processing for system operations.

Key components:

  • Control Panels: House switches, indicators, and control circuits
  • PLC (Programmable Logic Controller): Executes automation logic for switching and interlocking
  • HMI (Human-Machine Interface): Touchscreen or display panels for local operation
  • Remote I/O: Distributed input/output modules for signal acquisition
  • Alarm Panels: Visual and audible alarms for abnormal conditions
  • Interlocking Devices: Prevent unsafe operations (e.g., closing a breaker while a ground switch is closed)

These devices work together to ensure safe, reliable, and operator-friendly control of the distribution system .

5. Communication Equipment

Communication equipment enables data exchange between protection relays, automation terminals, SCADA systems, and control centers. Modern distribution rooms depend on communication networks that stay up through a fault: redundant paths, supervised links, and a defined fallback when one link drops.

Key devices and protocols:

Device / ProtocolPurpose
Industrial Ethernet SwitchBackbone for substation communication networks
Communication GatewayProtocol conversion between different systems
Fiber Optic CommunicationHigh-speed, interference-free data transmission
RS485Serial communication for legacy devices
Modbus RTU/TCPWidely used for SCADA integration
IEC 61850International standard for substation communication. It supports GOOSE messaging for high-speed peer-to-peer protection signals
IEC 60870-5-103/104Telecontrol protocols for utility communication

Communication protocols are selected according to the substation automation architecture and project requirements. IEC 61850 is increasingly preferred for its interoperability and high-speed capabilities .

6. Fault Recording Equipment

Fault recording devices capture detailed data when a fault occurs. This data is what makes post-fault analysis possible: it shows the root cause and tells you whether the settings were right. A dedicated digital fault recorder panel is the usual way to get waveform and sequence-of-events records in one place.

Key devices:

  • Fault Recorder: Captures waveforms during system disturbances
  • Disturbance Recorder: Records voltage and current variations
  • Event Recorder: Logs sequence of events (trip signals, breaker operations)
  • SOE (Sequence of Events): Time-stamped record of all digital state changes

These devices help engineers analyze fault behavior, verify relay operation, and optimize protection coordination.

7. DC and Auxiliary Power Equipment

DC and auxiliary power equipment provide the reliable power supply that all secondary devices depend on. This category is often overlooked, yet it decides whether the room protects anything at all during an AC supply loss.

Key components:

  • DC Panel: Distributes DC power to protection and control circuits
  • Battery Charger: Converts AC to DC and maintains battery charge
  • Station Battery: Provides backup DC power during AC failure
  • UPS (Uninterruptible Power Supply): Ensures continuous AC power for critical loads (PCs, servers, communication gear)
  • DC Monitoring: Monitors battery voltage, current, and health status

In a typical secondary equipment room, you will find protection panels, fault recorders, metering panels, power quality monitors, DC panels, and UPS units all housed together .

Summary Table

CategoryKey DevicesPrimary Purpose
Protection RelaysOvercurrent, Earth Fault, Feeder, Transformer, Motor, Differential, DirectionalDetect faults and issue trip commands
Measurement & MeteringPower Meter, Energy Meter, Power Quality AnalyzerMonitor system parameters and energy consumption
Distribution AutomationFTU, DTU, TTU, RTUEnable remote monitoring, control, and fault handling
Control & MonitoringControl Panels, PLC, HMI, Remote I/O, Alarm PanelsProvide local and remote system control
CommunicationEthernet Switches, Gateways, Fiber Optic, Modbus, IEC 61850Enable data exchange and SCADA integration
Fault RecordingFault Recorder, Disturbance Recorder, Event Recorder, SOECapture data for post-fault analysis
DC & Auxiliary PowerDC Panel, Battery Charger, Station Battery, UPS, DC MonitoringEnsure reliable power supply to all secondary devices

How Does Secondary Equipment Work in a Distribution Room?

Distribution room secondary equipment does not operate in isolation. It functions as an integrated chain that transforms raw electrical signals into actionable intelligence, enabling both local protection and remote control. Break the chain at any link and the parts downstream go blind.

Below is the typical data and control flow from the primary power system to the control center.

The Workflow

Signal and control chain from CT/VT inputs through relays and RTUs to the SCADA master station

Step-by-Step Breakdown

Step 1: Signal Acquisition

Devices involved: CT (Current Transformer), VT (Voltage Transformer)

Governed by IEC 61869-2:2012 for current transformers and IEC 61869-3:2011 for voltage transformers, the CTs and VTs step down high primary current and voltage to safe, standardized secondary values (e.g., 5A / 1A for current, 100V / 110V for voltage). These analog signals represent the real-time electrical condition of the feeder.

These signals are the foundation for everything that follows: protection, measurement, and control all depend on accurate CT/VT inputs.

Step 2: Protection and Measurement

Devices involved: Protection Relays / IEDs, Multifunction Meters, Power Quality Analyzers

The analog signals are fed into protection relays and measurement devices:

  • Relays / IEDs digitize the signals, calculate RMS values, and continuously compare them against preset thresholds (e.g., overcurrent pickup, earth fault sensitivity).
  • Meters display real-time values (current, voltage, power, frequency, power factor) for local reading and remote transmission.

If a fault is detected, the relay is ready to act. If the system is healthy, measurement devices log data for monitoring and analysis.

Step 3: Local Control

Devices involved: Protection Relays, PLCs, Control Panels, HMI

When the relay’s protection algorithm identifies a fault condition, it issues a trip command to the associated circuit breaker. This is the critical action that isolates the fault and protects the system.

Control actions include:

  • Trip: Open the circuit breaker to isolate the fault
  • Close: Re-energize the feeder after fault clearance (manual or auto-reclose)
  • Alarm: Notify operators of abnormal conditions without tripping
  • Interlock: Prevent unsafe operations (e.g., closing a breaker with a ground switch still engaged)

Local control devices ensure the distribution system reacts immediately to faults, even when communication to the control center is lost.

Step 4: Data Communication

Devices involved: RTU, Communication Gateway, Industrial Ethernet Switch, Fiber Optic

Once the local protection and measurement devices have processed the data, it needs to be transmitted to the control center. This is where the communication infrastructure comes in.

  • RTU (Remote Terminal Unit) or DTU (Distribution Terminal Unit) collects data from multiple IEDs and protection relays.
  • Communication gateways convert protocols between different devices (e.g., Modbus to IEC 61850).
  • Ethernet switches and fiber optic provide high-speed, reliable data transmission, often with redundancy for critical applications.

Common communication protocols used at this stage:

  • Modbus RTU/TCP: simple, widely supported, the default for legacy integration.
  • IEC 61850-8-1:2011+AMD1:2020: substation automation with GOOSE for fast peer-to-peer signals.
  • IEC 60870-5-103:1997 and IEC 60870-5-104:2006+AMD1:2016: utility-standard telecontrol protocols.
  • DNP3: common in North American utilities.

The communication layer is what transforms a traditional distribution room into a smart, connected substation.

Step 5: Remote Monitoring and Control

Devices involved: SCADA System, Control Center

At the top of the chain, the SCADA (Supervisory Control and Data Acquisition) system receives all data from the distribution room:

  • Real-time analog values (current, voltage, power, etc.)
  • Status indicators (breaker open/closed, relay healthy/alarm)
  • Event records (trip signals, fault logs, SOE)
  • Waveform data (from disturbance recorders)

SCADA displays this information to operators on a human-machine interface (HMI), typically a graphical screen showing the single-line diagram of the distribution network.

Operators can:

  • Monitor system status in real time
  • Respond to alarms and faults
  • Issue remote control commands (open/close breakers)
  • Analyze historical data and event records
  • Optimize system performance and load management

SCADA integration enables unattended operation: distribution rooms that run automatically with minimal human intervention.

Summary: From Signal to Action

StepFunctionKey DeviceAction
1Signal AcquisitionCT / VTSteps down high voltage/current to safe levels
2ProcessingRelay / IED / MeterCalculates values and compares against settings
3Local ControlRelay / PLCIssues trip, close, or alarm commands
4CommunicationRTU / Gateway / SwitchTransmits data to control center
5Remote MonitoringSCADA / Control CenterOperators monitor and control the system

Why This Flow Matters

Engineers, system integrators and plant operators need this sequence because it shows:

  • How protection is executed locally: even without communication, relays will trip for faults
  • How data flows to the control center: enabling remote visibility and control
  • How the system achieves coordination: each step depends on the previous one; a failure at any point affects the entire chain

In modern distribution rooms, secondary equipment is not just a collection of devices; it is a system-of-systems designed for safety, reliability, and intelligence.

Primary Equipment vs Secondary Equipment

The distinction is drawn on three tests: what the device carries, what voltage it works at, and whether it can be removed without switching the network out. Secondary equipment fails all three primary tests, which is exactly why it is the layer that gets instrumented.

FeaturePrimary EquipmentSecondary Equipment
Main PurposePower transmission/distributionProtection, control and monitoring
Typical EquipmentTransformer, CB, BusbarRelay, Meter, RTU, SCADA
Carries Main PowerYesGenerally no
Fault DetectionIndirectYes
ControlMechanical/electricalLogic/software based
CommunicationUsually limitedCommon
AutomationLimitedCore function

Primary equipment handles the electrical power path, while secondary equipment monitors, protects, controls and communicates with the primary system.

Functions of Distribution Room Secondary Equipment

Distribution room secondary equipment serves six core functions that work together to ensure safe, reliable, and intelligent power distribution. Protection and measurement come first; control, monitoring, communication and automation build on what those two produce.

1. Protection

Detect electrical faults and initiate tripping.

Protection relays continuously monitor current, voltage, frequency, and phase angle. When a fault occurs, such as overcurrent, short circuit, earth fault, or overvoltage, the relay issues a trip command to the circuit breaker, isolating the faulty section before damage can spread.

Key devices: Protection Relays (Overcurrent, Earth Fault, Differential, Directional), Breaker Failure Relays

Protection is the primary function of secondary equipment: it prevents equipment damage, ensures personnel safety, and maintains system stability.

2. Measurement

Measure voltage, current, power, energy, and power quality.

Measurement devices provide real-time data on system performance. This data is used for:

  • Load monitoring and demand forecasting
  • Energy billing and consumption analysis
  • Power quality assessment (harmonics, sags, swells)
  • System efficiency optimization

Key devices: Multifunction Power Meters, Energy Meters, Power Quality Analyzers, CTs/VTs

Accurate measurement is the foundation for informed decision-making, both for operators and for automated control systems.

3. Control

Control circuit breakers, switches, and other equipment.

Control devices enable operators to open and close breakers and switches either locally at the panel or remotely from a control center. Control functions include:

  • Manual open/close commands
  • Automatic switching based on protection logic
  • Interlocking to prevent unsafe operations
  • Auto-reclosing after transient faults

Key devices: Control Panels, PLCs, HMI, Remote I/O, Relay Output Contacts

Control is how the system acts, transforming protection decisions into physical switching actions.

4. Monitoring

Monitor operating status and alarms.

Monitoring devices continuously track the state of the distribution system:

  • Breaker position (open/closed)
  • Relay health and self-diagnostic status
  • Alarm conditions (overload warning, earth fault alarm)
  • System voltage and current trends

Monitoring provides operators with visibility into system status, enabling rapid response to abnormal conditions.

Key devices: Alarm Panels, HMI, SCADA Front-End, Status Indicators

You cannot manage what you cannot see, and monitoring provides the situational awareness needed for effective system management.

5. Communication

Transmit data to SCADA and control centers.

Communication devices and protocols enable the exchange of data between local secondary equipment and remote control centers. This includes:

  • Real-time analog values (current, voltage, power)
  • Status indicators (breaker position, relay flags)
  • Event records (trips, alarms, SOE)
  • Remote control commands (open/close)

Key devices: RTU, DTU, Communication Gateway, Ethernet Switch, Fiber Optic

Common protocols: Modbus RTU/TCP, IEC 61850, IEC 60870-5-103/104, DNP3

Communication transforms a traditional distribution room into a smart, connected asset, enabling automation and remote management.

6. Automation

Support fault detection, isolation, restoration, and remote operation.

Automation is the integration layer that ties all other functions together. It enables the distribution system to act without human intervention in certain scenarios:

  • Fault Detection: Identify fault type and location
  • Fault Isolation: Open the correct breaker to isolate only the faulty zone
  • Service Restoration: Re-energize healthy sections after fault clearance
  • Remote Operation: Execute commands from the control center
  • Unattended Operation: Run the distribution room with minimal on-site personnel

Key devices: Distribution Automation Terminals (FTU, DTU, TTU, RTU), SCADA Systems, PLCs

Automation is what enables the smart grid, improving reliability, reducing outage times, and lowering operational costs.

Summary Table: Six Core Functions

FunctionPurposeKey DevicesOutcome
ProtectionDetect faults and initiate trippingProtection Relays, 50BFEquipment safety, personnel protection
MeasurementMonitor voltage, current, power, energyMeters, PQ Analyzers, CT/VTLoad management, billing, efficiency
ControlOpen/close breakers and switchesControl Panels, PLC, HMI, Remote I/OPhysical switching actions
MonitoringTrack operating status and alarmsAlarm Panels, HMI, Status IndicatorsSituational awareness
CommunicationTransmit data to SCADA and control centersRTU, Gateway, Switches, FiberRemote visibility and control
AutomationEnable fault detection, isolation, restoration, remote operationFTU, DTU, TTU, RTU, SCADASmart grid, unattended operation

Secondary Equipment for Smart Distribution Rooms

Modern distribution room secondary equipment is evolving from isolated, manually operated setups into fully integrated digital systems, combining protection relays, intelligent electronic devices (IEDs), RTUs, communication gateways, power quality monitors, and SCADA into a unified network.

This shift is not just about technology; it is about reliability, efficiency, and intelligence.

Traditional vs. Smart Distribution Room

AspectTraditionalSmart
MonitoringManual inspectionReal-time remote monitoring
ProtectionStandalone relayDigital relay with communication
ControlLocal manualRemote and automated
CommunicationLimited or noneHigh-speed industrial network
Fault HandlingField crew dispatchedInstant detection and isolation
DataPaper logsAutomated logging and analytics

Workflow Comparison

Traditional Distribution Room:

Traditional distribution room with local manual control and panel indication (illustrative)

Smart Distribution Room:

Smart distribution room with networked IEDs, gateway and remote SCADA monitoring (illustrative)

Key Technologies Enabling Smart Distribution

1. Intelligent Electronic Devices (IEDs)

Microprocessor-based devices that combine protection, control, measurement, and communication in a single unit. IEDs provide self-diagnostics, event recording, and network connectivity.

2. Digital Protection

Digital relays offer multiple protection functions in one device, programmable logic, self-diagnostics, waveform capture, and remote setting adjustments, capabilities that traditional electromechanical relays cannot provide.

3. Automation Terminals by Location

DeviceFunction
RTUData acquisition and remote control at substations
DTUCommunication and data transmission at ring main units
FTUFeeder monitoring and automation on pole-mounted switches
TTUTransformer condition monitoring

4. Communication Network

Communication infrastructure built on fibre optic, industrial Ethernet and gateways, with redundancy wherever a single link failure would blind the room. Protocols include IEC 61850 (with GOOSE for fast peer-to-peer signals), Modbus RTU/TCP, IEC 60870-5-103/104, and DNP3.

5. SCADA and Remote Monitoring

SCADA provides:

  • Real-time visualization with live data
  • Alarm management and event logging
  • Historical data trending and analysis
  • Remote open/close control
  • Automated reporting

6. Power Quality Monitoring

Dedicated monitoring for harmonics, voltage sags/swells, flicker, and power factor, helping identify issues before they cause equipment damage or production interruptions.

The Business Value

BenefitImpact
Reduced downtimeFaster fault detection and restoration
Lower operational costsUnattended operation, fewer site visits
Improved safetyRemote control reduces personnel exposure
Better asset managementData-driven maintenance decisions
Enhanced reliabilityProactive issue identification
Future-readySupports renewables and EV charging integration

Conclusion

The transition to smart distribution rooms transforms the system from:

Traditional versus smart distribution room architecture compared side by side (illustrative)

By integrating IEDs, digital protection, automation terminals, communication networks, SCADA, and power quality monitoring, smart distribution rooms deliver:

  • More reliability: Faster fault response
  • More efficiency: Lower operational costs
  • More intelligence: Data-driven decisions
  • More sustainability: Renewable energy ready

Smart distribution rooms are not a future concept; they are today’s standard for utilities, industrial plants, and commercial facilities seeking better reliability, efficiency, and control.

How to Select Secondary Equipment for a Distribution Room?

Selecting distribution room secondary equipment starts from the object being protected, not from the device catalogue. One row of the table below per requirement gives you the equipment list; the six steps that follow it turn that list into a specification you can send to three suppliers and compare line by line.

RequirementRecommended Equipment
Feeder ProtectionFeeder Protection Relay
Transformer ProtectionTransformer Protection Relay
Motor ProtectionMotor Protection Relay
Energy MeasurementMultifunction Meter
Power QualityPower Quality Analyzer
Remote MonitoringRTU / DTU
Feeder AutomationFTU
Fault RecordingFault Recorder
CommunicationGateway / Industrial Switch
Central MonitoringSCADA
Backup DC PowerDC Panel / UPS

Distribution Room Secondary Equipment List, Device by Device

This is the distribution room secondary equipment list for a typical 10 kV or 20 kV room. Read it as a procurement checklist: every row has to be answered before the panel layout can be frozen.

CategoryDeviceWhat it doesWhere it sits
ProtectionFeeder protection relay50/51 overcurrent, 50N/51N earth fault, 79 auto-recloseFeeder cubicle, switchgear mounted
ProtectionEarth fault relayDetects phase-to-ground current on high-impedance earthed systemsFeeder cubicle or residual CT circuit
ProtectionDifferential relay87T or 87B zone comparisonTransformer or busbar cubicle
ProtectionDirectional relay67 or 67N fault direction on looped and parallel feedersIncomer and tie cubicles
MeasurementMultifunction power meterCurrent, voltage, power, frequency, power factorMetering panel or cubicle door
MeasurementEnergy meterActive and reactive energy for billing, to IEC 62053-22:2020 accuracy classesRevenue metering panel, sealed
MeasurementPower quality analyserHarmonics, sags, swells and transientsMetering panel or temporary survey
AutomationDTU / RTUCollects status and measurements, executes remote commandsRMU cubicle or room marshalling panel
AutomationFTU / TTUFeeder and transformer terminal functions on the networkPole switch, distribution transformer
ControlPLC and HMIInterlocking logic and local operator interfaceControl panel in the secondary room
CommunicationGateway and Ethernet switchProtocol conversion and network backbone, IEC 61850-8-1 or Modbus TCPCommunication panel
RecordingFault recorderWaveform capture and sequence of eventsRecording panel
AuxiliaryDC panel, charger, battery, UPSHolds up protection, control and communication during AC lossBattery room or secondary room

Two rows cause most of the rework on site: the DC supply and the gateway. Undersize the battery and every relay in the room loses its trip supply together; under-specify the gateway and the SCADA point list cannot be delivered.

Standards Behind Distribution Room Secondary Equipment

Six documents decide what goes into the room and how it is tested. Quote the edition, not just the number, because vendors still ship firmware built against older revisions.

  • ANSI/IEEE C37.2-2022 defines the device numbers: 50/51, 50N/51N, 87, 67, 79.
  • IEC 60255-1:2022 sets the general requirements for measuring relays and protection equipment.
  • IEC 61869-2:2012 covers current transformers and IEC 61869-3:2011 inductive voltage transformers.
  • IEC 61850-8-1:2011+AMD1:2020 maps the station bus onto MMS and Ethernet, including GOOSE.
  • IEC 60870-5-103:1997 is the serial information interface for protection equipment; IEC 60870-5-104:2006+AMD1:2016 carries telecontrol over TCP.
  • IEC 62053-22:2020 fixes accuracy classes 0.1S, 0.2S and 0.5S for revenue energy meters.
  • IEC 61000-6-5:2015 sets the immunity levels equipment has to survive in a substation environment.

Power quality monitoring on the measurement side is usually specified against IEC 61000-4-30 for the measurement method, which is a separate question from the meter accuracy class above.

Secondary Equipment in Distribution Room FAQ

1. What is secondary equipment in a distribution room?

Distribution room secondary equipment refers to all low-voltage devices in the room that monitor, control, protect, and communicate with the primary power system. Unlike primary equipment (transformers, circuit breakers, busbars) that handle the actual power flow, secondary equipment processes electrical signals, executes protection logic, records operational data, and enables remote control.

Common examples: Protection relays, multi-function meters, RTUs, communication gateways, and SCADA systems.

2. What are the main types of distribution room secondary equipment?

Secondary equipment falls into seven main categories:

CategoryExamples
Protection RelaysOvercurrent, Earth Fault, Feeder, Transformer, Motor, Differential, Directional relays
Measurement & MeteringMulti-function power meters, energy meters, power quality analyzers
Distribution AutomationRTU, DTU, FTU, TTU
Control & MonitoringControl panels, PLC, HMI, remote I/O, alarm panels
CommunicationEthernet switches, communication gateways, fiber optic, RS485
Fault RecordingFault recorders, disturbance recorders, event recorders, SOE
DC & Auxiliary PowerDC panels, battery chargers, station batteries, UPS, DC monitoring

3. What is the difference between primary and secondary electrical equipment?

AspectPrimary EquipmentSecondary Equipment
FunctionHandles main power flowMonitors, controls, and protects primary equipment
Voltage LevelHigh voltage (6–35 kV and above)Low voltage (typically 48V, 110V, 220V DC)
ExamplesTransformers, circuit breakers, busbars, CTs/VTsProtection relays, meters, RTUs, SCADA
RoleCarries and switches high powerProcesses signals and executes logic

Key point: Primary equipment carries the power; secondary equipment protects and controls it.

4. What does a protection relay do in a distribution room?

A protection relay continuously monitors current, voltage, frequency, and phase angle, and issues a trip or alarm command when an abnormal condition is detected.

Key functions:

  • Fault detection (overcurrent, short circuit, earth fault, overvoltage, etc.)
  • Trip command: open circuit breaker to isolate the fault
  • Alarm output: notify operators of abnormal conditions
  • Event recording: save fault data for post-analysis
  • Coordination: ensure selective tripping with downstream devices

Protection relays are the most critical secondary devices, the first line of defense against electrical faults.

5. What are the roles of RTU, FTU, and DTU in distribution automation?

DeviceFull NamePrimary FunctionTypical Installation
RTURemote Terminal UnitData acquisition and remote control; communicates with SCADASubstations, distribution facilities
DTUDistribution Terminal UnitCollects switch status, voltage, current; fault detection and isolationRing main units, compact substations
FTUFeeder Terminal UnitMonitors feeder parameters; executes remote open/close commandsPole-mounted switches, 10kV breakers
TTUTransformer Terminal UnitMonitors transformer conditions (voltage, current, load, temperature)Distribution transformers

In the distribution automation hierarchy: SCADA → Substation → RTU/DTU/FTU work together for fault detection, isolation, and service restoration.

6. How does secondary equipment communicate with SCADA?

Communication flow:

Communication path from distribution room secondary equipment to the SCADA master station

Common communication protocols:

ProtocolApplication
Modbus RTU/TCPSimple, widely supported, legacy integration
IEC 61850Advanced substation automation; supports GOOSE for high-speed signals
IEC 60870-5-103/104Utility telecontrol standard
DNP3Common in North American utilities

Data transmitted: Real-time analog values (current, voltage, power), status indicators (breaker position), event records (trips, alarms, SOE), waveform data, remote control commands.

Pin the edition, not just the protocol name. IEC 61850 station-bus mapping is IEC 61850-8-1:2011+AMD1:2020; telecontrol over TCP is IEC 60870-5-104:2006+AMD1:2016; the serial protection interface is IEC 60870-5-103:1997. A gateway specified against one edition will not always talk to a master station built against another.

Communication transforms a traditional distribution room into a smart, connected asset: enabling remote visibility, control, and automation.

7. What equipment is required for a smart distribution room?

ComponentPurpose
IEDs and digital protection relaysIntelligent fault detection and trip execution
RTU, DTU and FTURemote data acquisition and control
Multi-function MetersReal-time measurement of current, voltage, power, energy
Power Quality AnalyzerMonitor harmonics, sags, swells, and transients
Communication GatewayProtocol conversion and network integration
Industrial Ethernet SwitchHigh-speed, reliable network backbone
SCADA SystemCentralized monitoring, control, and data management
Fault recorderCapture data for post-fault analysis
DC panel and UPSReliable power supply for all secondary devices

All devices must be network-connected with real-time data exchange capability, typically using IEC 61850 or Modbus over Ethernet.

8. How do I select secondary equipment for a distribution room?

Step 1: Define System Parameters

  • Voltage level (6kV, 11kV, 22kV, 33kV, etc.)
  • System grounding (solid, impedance, ungrounded)
  • Fault current levels
  • Load profile and criticality

Step 2: Identify Protection Functions Required

  • Overcurrent (50/51): always required
  • Earth Fault (50N/51N): required for most systems
  • Directional (67/67N): required for looped or parallel feeders
  • Other functions as needed (46, 59/27, 50BF, 87, etc.)

Step 3: Determine Automation and Communication Requirements

  • Remote monitoring: Yes/No
  • SCADA integration: Yes/No
  • Protocol required (Modbus, IEC 61850, DNP3, etc.)
  • Unattended operation: Yes/No
  • Auto-reclosing: Yes/No

Step 4: Confirm Physical Constraints

  • Panel space availability
  • Mounting type (panel mount, switchgear mount)
  • Ambient temperature and humidity
  • Protection rating (IP rating)

Step 5: Device Selection

Device TypeSelection Criteria
Protection RelayRequired functions, communication protocol, form factor
MeteringAccuracy class, measurement parameters, communication
RTU/DTUI/O count, communication ports, protocol support
CommunicationNetwork topology, protocol, redundancy requirements
DC PowerBattery capacity, charger rating, monitoring features

Step 6: Verify Coordination

  • Ensure relay settings coordinate with upstream and downstream protection
  • Confirm communication compatibility between all devices
  • Validate with protection coordination software (e.g., ETAP, SKM)
Distribution terminal unit front panel with I/O and communication ports (illustrative)
DTU installed in a ring main unit cubicle (illustrative)
SCADA screen showing a distribution room single-line diagram with live status (illustrative)

Nine pages that carry the detail behind the seven categories of distribution room secondary equipment listed above. Two of them cover switchgear and relay selection, three cover settings and calculation, and the rest cover the protocol and panel layers that decide whether the equipment list actually talks to SCADA.

Technical References

Nine sources behind the device numbers, accuracy classes, transformer ratings and protocol editions quoted above. Every one is publication-dated, because vendors still ship firmware built against older revisions; check the edition against the issue in force before you write a specification. Where a standard has an amendment, the amendment date matters as much as the base year.

SourceWhat it coversTypeEdition
ANSI/IEEE C37.2Device function numbers used on single-line diagramsStandard2022
IEC 60255-1General requirements for measuring relays and protection equipmentInternational standard2022
IEC 61869-2Current transformers: accuracy classes and ratingInternational standard2012
IEC 61869-3Inductive voltage transformersInternational standard2011
IEC 61850-8-1Station-bus mapping to MMS and Ethernet, including GOOSEInternational standard2011+AMD1:2020
IEC 60870-5-103Serial information interface for protection equipmentInternational standard1997
IEC 60870-5-104Telecontrol over TCP for utility networksInternational standard2006+AMD1:2016
IEC 62053-22Accuracy classes 0.1S, 0.2S and 0.5S for AC active energy metersInternational standard2020
IEC 61000-6-5Immunity for equipment in substation and power station environmentsInternational standard2015

Tell us the voltage class and the duty, and the reply comes back with a model and a lead time.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.