ATN-400 Automation Solution for Photovoltaic Power Systems

ATN-400 Automation Solution for Photovoltaic Power Systems

The AutomationSolution for Photovoltaic Power Systems serves as the core technical framework to ensure the safe, stable, and efficient grid-connected operation of power plants.

This solution for grid-connected photovoltaic power systems must adhere to the fundamental principles of power system protection—Reliability, Selectivity, Sensitivity, and Speed—and requires specialized design tailored to the unique operating characteristics of photovoltaic power systems.

Automation Solution for Photovoltaic Power Systems & Protection Relay Configuration List

No.Protected ObjectEquipment NameMain FunctionConfiguration Requirement
1Outgoing LineLine Protection RelayThree-zone distance protection, four-zone ground distance, zero-sequence directional overcurrent, pilot differential (fiber channel), autoreclosing, two-end fault locationFiber optic differential protection for 110kV and above; directional overcurrent and distance protection for 35kV
2BusbarBusbar Protection RelayBusbar differential protection, breaker failure protectionIndependent busbar protection for 110kV and above; 35kV busbar protection can be integrated into bay protection
3Main TransformerMain Transformer Protection RelayDifferential protection (with inrush identification and CT disconnection blocking), composite voltage blocking overcurrent, zero-sequence overcurrent, gap protection, overload alarmDual configuration; selection based on capacity
4Main TransformerNon-Electrical Protection RelayNon-electrical protection for oil temperature, gas, pressure, etc.Independent device or integrated into main transformer protection
5Feeder / Collector LineFeeder Protection RelayThree-stage overcurrent protection, zero-sequence overcurrent, inverse time overcurrent, small current grounding fault line selection, autoreclosingConfigured for 35kV/10kV collector lines; small current grounding fault line selection function required
6Collector BusbarCollector Busbar Protection RelayBusbar differential protectionConfigurable as needed; bus fault isolation can be achieved via feeder protection
7Unit TransformerUnit Transformer Protection RelayOvercurrent protection, overload protection, zero-sequence overcurrent, non-electrical protectionIntegrated protection and control device installed at HV side of pad-mounted transformer
8InverterInverter ProtectionAnti-islanding protection, over/under voltage protection, over/under frequency protection, reverse polarity protectionIntegrated inside inverter
9SVG (Reactive Power Compensation)SVG Protection RelayOvercurrent protection, overload protection, overvoltage protection, ground fault protectionConfigured for 35kV/10kV SVG branch
10Grounding TransformerGrounding Transformer Protection RelayOvercurrent protection, zero-sequence overcurrent protection, overload protectionConfigured as needed
11Station Service TransformerStation Service Transformer Protection RelayOvercurrent protection, overload protection, zero-sequence overcurrent protectionIntegrated protection and control device
12Point of Common Coupling (PCC)Anti-Islanding Protection RelayPassive islanding detection (voltage/frequency anomaly), active islanding detection, reverse power protection, frequency sudden change tripping, automatic reclosing when voltage returnsIndependent anti-islanding protection relay required; operating time ≤2s; reverse power protection required (for non-reverse power grid connection mode)
13Common EquipmentFault RecorderRecords fault waveform data (COMTRADE format), collects station-wide fault informationConfigured for 110kV and above step-up substations
14Common EquipmentSmall Current Grounding Fault Line Selection DeviceSelects faulty line for single-phase ground faultConfigured for 35kV/10kV neutral ungrounded or resonant grounded systems
15Common EquipmentAutomatic Transfer Switch (ATS)Automatic backup power switchingConfigured for station service power system
16Common EquipmentPower Quality Monitoring DeviceHarmonic monitoring (THD, inter-harmonics), voltage fluctuation and flicker monitoring (Pst), three-phase unbalance monitoringConfigured per grid requirements

Safety Automatic Devices Configuration List

No.Equipment NameMain FunctionConfiguration Requirement
1Stability Control DeviceUnder-frequency load shedding, under-voltage load shedding, over-frequency generator trippingConfigured per grid dispatch requirements
2Frequency and Voltage Emergency Control DeviceAutomatically trips partial generation units or loads during abnormal frequency/voltage conditionsConfigured per grid requirements
3AGC SystemReceives dispatch commands, automatically adjusts active power output of PV stationRequired for grid-connected PV stations
4AVC SystemAutomatically adjusts reactive power compensation devices to maintain voltage stability at PCCRequired for grid-connected PV stations
5Fault Ride Through (FRT) Monitoring DeviceMonitors and records LVRT/HVRT process waveformsConfigured per grid requirements

We are engaged in the power relay protection industry, with years of in-depth experience in the photovoltaic sector. The Automation Solution for Photovoltaic Power Systems we provide delivers professional, tailored PV automation services for clients.

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.