Send an Inquiry

Low Voltage ATS Controller | ASZ-526H Automatic Transfer Switch Device

ASZ-526H Low Voltage ATS Controller is developed for automatic control of low-voltage multi-power supply. It supports standby power switching, closed-loop operation and dual/multi-power transfer, applicable to 2-incoming, 2-incoming-with-bus-coupler and 3-incoming wiring schemes.

Communication Mode:Optional: RS-485, CAN bus, IEC 61850 , IEC 60870-5-103

Download datasheet (PDF)

Send your requirements, we will quote for you within 12 hours​
MOQ: 1 setLead time: 7-15 working daysPayment: T/T, L/C, Western Union, PayPalWarranty: 12 monthsTrade terms: EXW, FOB, CIF, DDUCertification: CEDifferent rating, protocol or mounting: send the specification and we confirm before you order.

Description

What is an ASZ-526H low voltage ATS controller?

The ASZ-526H is a controller for a low voltage automatic transfer switch: it supervises the normal and the standby supply, decides when to transfer, drives the switch mechanism, and supervises the generator start signal if a set is involved. The decisions it has to get right are the ones that cause nuisance transfers in practice: a voltage dip on the normal supply should not start a transfer if the standby source is also unhealthy, and a return to normal should wait for a stable voltage rather than a single good cycle. Both are handled with separate thresholds and time delays per direction. Typical duty is a 400 V distribution board in a building, a plant MCC or a pump station with a standby set. Transfer logic and ratings are fixed at order; quotation within 12 hours, MOQ 1, 7-15 working days.

Overview of Low Voltage ATS Controller

  • ASZ-526H Low Voltage ATS Controller is developed for automatic control of low-voltage multi-power supply. It supports standby power switching, closed-loop operation and dual/multi-power transfer, applicable to 2-incoming, 2-incoming-with-bus-coupler and 3-incoming wiring schemes.
  • Low Voltage ATS Controller is applicable to power distribution systems with dual power supply for critical loads in industry, medical care, finance, data centers, government offices, post & telecommunications, coal, metallurgy, railway, marine, military facilities and expressways.

Model Description: LV Automatic Transfer Switch Relay

ModelControl ModeApplication ModeRemark
ASZ-526H-A20Dual power automatic transfer controllerMains-Mains, Mains-Generator, Auto/Manual
ASZ-526H-B20Dual power automatic transfer controller (with closed-loop parallel function)Mains-Mains, Mains-Generator, Auto/Manual
ASZ-526H-A21Dual power bus coupler automatic transfer controllerMains-Mains-Bus Coupler, Auto/Manual
ASZ-526H-B21Dual power bus coupler automatic transfer controller (with closed-loop parallel function)Mains-Mains-Bus Coupler, Auto/Manual
ASZ-526H-A30Three-power automatic transfer controllerMains-Mains-Mains, Mains-Mains-Generator, Auto/Manual
ASZ-526H-B30Three-power automatic transfer controller (with closed-loop parallel function)Mains-Mains-Mains, Mains-Mains-Generator, Auto/Manual

Features of Closed-Transition ATS Controller

  • Equipped with overvoltage, undervoltage, phase loss, reverse phase sequence, overcurrent, overfrequency and underfrequency protection.
  • Real-time clock display and historical data storage, circularly recording up to 500 entries.
  • Compatible with 3-phase 4-wire and 3-phase 3-wire AC power systems.
  • Controls closing and tripping of two incoming breakers and bus coupler breaker simultaneously to simplify control system.
  • Delays closing operation till PF ready signal is received for stored-energy breakers.
  • Auto/manual mode switch, manual breaker operation available under manual mode.
  • Six physical switch transfer buttons on panel for convenient manual control.
  • Reclosing function with enable/disable option.
  • Closing output supports pulse or continuous signal mode.
  • On-site programmable parameters with password protection against unauthorized operation.
  • Isolated design for two neutral lines.
  • LO/NO power output supplies power for breaker switching coils.
  • Widely spaced AC terminals, maximum withstand voltage up to 625V AC.
  • Built-in communication port adopting ModBus protocol, realizing remote control, signaling, measurement and parameter adjustment. Supports remote start/stop of generator sets and remote ATS switching.

General Technical Parameters of Low Voltage ATS Controller

Low Voltage ATS Controller

Ambient Conditions

Normal Operating Atmospheric Conditions

  • a. Ambient temperature: -25℃ ~ +70℃
  • b. Relative humidity: 5% ~ 95%, no condensation or icing inside the device
  • c. Atmospheric pressure: 80kPa ~ 106kPa

 Normal Test Atmospheric Conditions

  • a. Ambient temperature: +15℃ ~ +35℃
  • b. Relative humidity: 45% ~ 75%
  • c. Atmospheric pressure: 80kPa ~ 106kPa

Reference Test Atmospheric Conditions

  • Unless specified otherwise, ambient conditions for inherent accuracy verification:
  • a. Ambient temperature: (20±5)℃
  • b. Relative humidity: 45% ~ 75%
  • c. Atmospheric pressure: 86kPa ~ 106kPa

Storage and Transportation Conditions

  • a. Transportation temperature: -40℃ ~ +70℃, relative humidity ≤85%. No irreversible changes under unpowered state.
  • b. Storage temperature: -25℃ ~ +55℃, relative humidity ≤85%.

Surrounding Environment

  • a. No explosion hazards, corrosive gas, conductive dust, severe mildew and violent vibration sources.
  • b. Equipped with protection against rain, snow, wind, sand, dust and static electricity.
  • c. Comply with Class B safety requirements of GB/T 9361-2011; grounding resistance meets Clause 5.8 of GB/T 2887-2011.
Low Voltage ATS Controller | ASZ-526H Automatic Transfer Switch Device, line distance protection principle diagram

Electrical Parameters

Rated Ratings

ItemParameter
Operating VoltageAC 85-480V (80%~120% fluctuation); DC 110V/220V
Remote Signal VoltageDC 24V
AC Voltage Input3-phase 4-wire / 3-phase 3-wire, Max 690V AC, PT ratio adjustable
AC Current Input5A (0.05~6A), CT ratio adjustable
Rated Frequency50Hz

Power Consumption

  • AC voltage circuit: <0.5VA per phase
  • AC current circuit: <0.75VA per phase
  • Total power consumption: ≤15VA

Overload Capacity

  • AC voltage: Continuous operation at 1.2 times rated voltage
  • AC current: Continuous operation at 1.2 times rated current

Main Technical Specifications

ItemParameter
Remote Signaling12 input channels; Opto-isolated passive contact, 1500VDC isolation voltage; Internal DC24V excitation, NO/NC contact configurable; Signal resolution ≤2ms
Remote Control Output6 channels: 16A, AC250V passive output; 6 channels: 8A, AC250V passive output
Communication Interfaces1×10/100Base-TX Ethernet port; 2×RS485 interfaces
ReliabilityMTBF ≥50000 hours
Insulation PerformanceInsulation resistance ≥5MΩ (between circuits & ground, among separate circuits); Withstand 50Hz 2.0kV AC voltage test for 1min without breakdown/flashover; Withstand 5kV standard lightning impulse voltage between circuits & ground

FAQ

Q: What is Make-Before-Break ATS Relay?

A: It is a switching relay that closes the standby power circuit before disconnecting the main power, realizing transient parallel connection to avoid instantaneous power outage during transfer.

Q: Definition of No-Break Automatic Transfer Switch

A: It refers to non-interruptible power transfer switch, which maintains continuous power supply to loads throughout power switching process without power cut.

Q: What does ABTD stand for?

A: ABTD is short for Automatic Bus Transfer Device, an automatic controller used for intelligent switching and interconnection of busbar power supply.

Q: Core difference between Make-Before-Break and No-Break ATS

A: Make-Before-Break adopts brief overlapping switching; No-Break ATS achieves zero power interruption for load power supply during conversion.

Q: Application scenarios of Automatic Bus Transfer Device

A: Widely used in dual or multi-busbar power distribution systems for automatic bus coupling, power switching and isolated grid power regulation.

Q: How do I place an order?

A: Send your specification through the contact form, by email to sale@relayprotect.com or on WhatsApp. We check the rating, the protocol and the wiring against your application, confirm the model, and return a quotation. No account or registration is needed.

Q: What is the minimum order quantity?

A: The minimum order quantity is one unit. A single unit can be ordered for evaluation or for a pilot installation, and project quantities are quoted separately.

Q: What is the lead time?

A: Standard models ship in 7 to 15 working days after the order is confirmed and payment is received. Custom ratings, protocols or mounting arrangements are confirmed in writing before the order is placed, so the delivery date is known in advance.

Q: Which payment methods and trade terms do you accept?

A: Payment by T/T, L/C, Western Union or PayPal. Trade terms are EXW, FOB, CIF and DDU. Every relay carries a 12-month warranty.


Need pricing, a datasheet or a wiring drawing?

Tell us your application – rated voltage, CT/VT ratios and the protection functions you need – and we will send a quotation with the matching model. Free technical guidance, parameter setting and commissioning support included.

MOQ 1 unit for samples | Bulk orders ship in 7-15 working days | 12-month warranty | EXW, FOB, CIF, DDU | Payment by T/T, L/C, Western Union or PayPal. New to ordering? See how to order – process, MOQ and lead time.

Reviews

There are no reviews yet.

Be the first to review “Low Voltage ATS Controller | ASZ-526H Automatic Transfer Switch Device”

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.