Send an Inquiry
Six-step transformer differential protection setting calculation chart: base data, CT ratio matching, knee-point check, slope selection and trip

87T Setting Calculation: Pickup, Slope and 2nd Harmonic

Table of Contents

How is an 87T transformer differential setting calculated?

87T setting rests on three numbers: minimum pickup around 0.3 In, bias slope of 30 to 40 percent above the knee point, and second-harmonic blocking at 15 to 20 percent. Everything else on the sheet is a check on those three, including the CT ratio correction and the vector group compensation the relay applies internally. Transformer differential protection setting defines the operating parameters that distinguish an internal fault from normal load, external faults and energisation. The settings must be coordinated with the transformer rating, nameplate data, CT characteristics and system fault levels so the relay stays stable on normal load, magnetising inrush and external faults, yet still trips for a winding short circuit or core failure. Function numbers follow ANSI/IEEE C37.2-2022, differential requirements follow IEC 60255-187-1:2021, application guidance follows IEEE C37.91-2021, and CT performance follows IEC 61869-2:2012. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

87T setting rests on three numbers: minimum pickup around 0.3 In, bias slope of 30 to 40 percent above the knee point, and second-harmonic blocking at 15 to 20 percent. Everything else on the sheet is a check on those three, including the CT ratio correction and the vector group compensation the relay applies internally.

Function numbers follow ANSI/IEEE C37.2-2022, differential requirements follow IEC 60255-187-1:2021, application guidance follows IEEE C37.91-2021, and CT performance follows IEC 61869-2:2012.

Written by Leon Zhang, Protection Application Engineer. Technical review by the relayprotect.com engineering team. Last reviewed October 2026.

Transformer differential protection setting defines the operating parameters used to distinguish internal transformer faults from normal load, external faults, and transformer energization conditions. The main parameters include differential pickup, percentage bias or restraint slope, harmonic restraint, CT ratio, transformer vector group compensation, and related trip or alarm settings.

Written by Leon Zhang, Protection Application Engineer · Technical review by the relayprotect.com engineering team · Last reviewed September 2026

These settings must be coordinated with the transformer rating, CT characteristics, system fault conditions, relay model, and protection philosophy. The ANSI 87T differential protection function is one of the main applications of this setting process.

This guide explains the main transformer differential protection settings, what each parameter does, and how engineers can verify the settings before commissioning. For detailed mathematical calculations, see our Differential Protection Relay Setting Calculation guide.

87T setting screen on a transformer differential relay showing pickup, bias slope and second-harmonic restraint values
Figure 1. Pickup, slope and harmonic restraint on one settings page; the three numbers that decide stability.

At a Glance

  • Minimum pickup is normally 0.2 to 0.5 In; 0.3 In fits most two-winding transformers.
  • Pickup has to exceed CT ratio mismatch plus tap-changer range, or the relay trips on load.
  • Bias slope is set 30 to 40 percent, with the knee point at 1.0 to 1.5 times rated current.
  • Second-harmonic blocking is set at 15 to 20 percent to ride through energisation inrush.
  • CT ratio correction is entered from nameplate ratios; mismatch above 4:1 needs interposing CTs.
  • Vector group compensation is applied in software, so the CTs are wired star-star on both sides.
  • Verify each bias point by single-side injection; measured operate values should sit within 5 percent.

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

What Is 87T Setting? (Transformer Differential Protection Setting)

Transformer differential protection setting is the process of defining the relay’s operating parameters to ensure it correctly distinguishes between internal transformer faults and all other system conditions. The goal is a secure operating region. The relay must stay stable during normal load, magnetizing inrush and external faults, and it must still trip for winding short circuits and core failures.

Proper setting calculation involves determining pickup thresholds, bias slopes, and harmonic restraint values based on transformer nameplate data, CT parameters, and system fault levels.

For a detailed explanation of the operating principle, see Transformer Differential Protection Working Principle.

Differential Pickup Setting

Differential Pickup Current Setting

The differential pickup current (Idiff> or minimum operating current) is the threshold above which the differential protection element initiates its tripping logic, subject to the relay’s characteristic.

Effects of Improper Setting

Too Low

If the pickup is set too low, the relay may maloperate due to spurious differential currents caused by:

  • CT mismatch and ratio errors
  • Measurement errors
  • OLTC tap variations
  • Residual current during external faults

Too High

If the pickup is set too high, the relay may fail to detect:

  • Small internal faults
  • Turn-to-turn winding faults with low fault current
  • Incipient faults

Both errors have a cost.

Engineering Principle

The pickup setting must be selected within a defined design window:

  • Lower limit: Above the maximum expected unbalanced current under normal and external fault conditions (ensures stability)
  • Upper limit: Below the minimum differential current expected for any internal fault requiring clearance (ensures sensitivity)

The final pickup value should provide sufficient sensitivity for the minimum internal fault while remaining above the expected maximum unbalanced current.

Typical Pickup Range

For practical applications, the differential pickup is typically set between 15% and 40% of transformer rated current, depending on:

  • CT accuracy class
  • Transformer tap range
  • Application requirements
  • Relay type

Bias / Slope Setting

What Is Bias Slope?

Bias slope (also known as percentage restraint slope) defines how the relay’s operating threshold increases as the through-current flowing through the transformer rises. It establishes the relationship between differential current and restraint current, forming the characteristic curve that determines the relay’s operating boundary.

Why Is Bias Slope Required?

Under ideal conditions, differential current should remain near zero during external faults. However, practical factors such as CT ratio errors, CT saturation, and measurement inaccuracies generate spurious differential currents that increase with fault current magnitude. The bias slope lets the relay tolerate these errors. The operating threshold rises with through-current. That keeps the relay stable during high-current external faults without losing sensitivity to internal ones.

Slope 1, Low-Current Region

Slope 1 applies to the low restraint current region, typically corresponding to normal load and light through-fault conditions. In this region, steady-state errors such as CT ratio mismatch and tap changer variations are the dominant sources of unbalance. A lower slope setting provides high sensitivity for detecting minor internal faults, as the differential current required for operation increases only gradually with restraint current.

Slope 2, High Through-Fault Region

Slope 2 applies to the high restraint current region, typically associated with severe external faults and heavy through-fault conditions. In this region, CT saturation becomes the dominant error source, introducing substantial differential current during the first few cycles of fault. A higher slope setting increases the operating threshold enough to keep the relay stable during severe external faults when CT performance is compromised.

Slope 1 and Slope 2 Setting Ranges

The bias slope setting must balance sensitivity and stability across the full range of operating conditions:

  • Slope 1 is typically set between 20% and 35%, providing sufficient coverage for steady-state errors while maintaining high sensitivity.
  • Slope 2 is typically set between 50% and 80%, accommodating CT saturation effects during high-current external faults.

Both are set independently.

The final slope settings depend on CT performance characteristics, transformer impedance, fault levels, and the specific relay type. Always refer to the manufacturer’s manual for the exact characteristic curve and setting procedure.

87T Setting Parameters: What Each One Controls

87T pickup and slope set the shape of the operating characteristic, so they are normally fixed first. The remaining parameters, harmonic restraint, CT ratio and vector group compensation, are then fitted around them. The table below lists each setting and the engineering consideration behind it.

ParameterEngineering Consideration
Differential PickupMust balance sensitivity and stability
Slope 1Determines restraint in lower through-current region
Slope 2Provides greater stability under high through-fault current
2nd Harmonic RestraintUsed to prevent unwanted operation during magnetizing inrush
5th Harmonic RestraintMay be used for overexcitation detection/restraining depending on relay
Time DelayUsually coordinated with the protection philosophy

Typical values vary by relay model and project requirements. Always use the setting definitions and permissible ranges specified in the selected relay manufacturer’s manual. The table above is for reference only and should not be used as a substitute for formal setting calculations and manufacturer-specific guidance.

Transformer Differential Protection Harmonic Restraint Setting

Harmonic restraint setting for 87T with second-harmonic blocking threshold and cross-blocking between phases
Figure 2. Second-harmonic restraint; cross-blocking prevents one phase from tripping while another sees inrush.

Harmonic restraint is a stabilizing feature. In transformer differential protection it blocks unwanted tripping whenever the current waveform is heavily distorted. The relay detects specific harmonic components and increases the operating threshold or blocks the trip output when these components exceed a preset percentage of the fundamental current.

Setting the 2nd Harmonic Threshold

The second harmonic component is the primary harmonic used for restraining differential protection during transformer magnetizing inrush. When a transformer is energized, the inrush current contains a significant second harmonic content, typically ranging from 15% to 40% of the fundamental frequency component. The relay measures this ratio and applies restraint when the second harmonic exceeds the set threshold, preventing false tripping.

Typical setting range: 10% to 25% (relay-specific)

5th Harmonic Restraint

Some relays provide a fifth harmonic restraint feature, which may be used in applications where overexcitation conditions are a concern. Overexcitation produces a current waveform with elevated fifth harmonic content, and the relay can apply restraint to avoid maloperation during such events. However, the availability and implementation of fifth harmonic restraint depend on the specific relay model and manufacturer’s algorithm. Not all transformer differential relays employ this feature, and the method of application differs between protection platforms.

Harmonic Restraint Ranges Are Relay-Specific

Harmonic restraint settings vary between relay manufacturers. Always refer to the specific relay manual for available harmonic restraint functions, setting definitions, and permissible ranges. The typical values and descriptions provided above are for general reference only.

CT Ratio Setting

The CT ratio setting defines the relationship between the primary current flowing through the transformer and the secondary current delivered to the relay. This setting must match the actual CT nameplate ratings installed on site for both the HV and LV sides of the transformer.

CT Ratio Setting Elements

  • CT Primary Ratio, The primary current rating of the CT, selected based on the transformer rated current and expected fault levels
  • CT Secondary Rating, Typically 1A or 5A, which must match the relay’s analog input design
  • HV CT, The CT installed on the high-voltage side of the transformer
  • LV CT, The CT installed on the low-voltage side of the transformer

CT Mismatch and Saturation

  • CT Mismatch, The CT ratios on the HV and LV sides are often different due to the transformer voltage ratio. The relay must compensate for this difference internally through its setting parameters.
  • CT Saturation, Under high fault currents, CT saturation can occur, causing distorted secondary currents. Proper CT sizing and relay settings help mitigate the impact of saturation.

CT Ratio Must Match Nameplate Ratings

CT ratio settings must match the actual CT nameplate ratings on site. Incorrect CT ratio entries will result in erroneous current measurements and may compromise protection performance.

Transformer Vector Group Setting

The transformer vector group setting defines the phase displacement and magnitude relationship between currents on the HV and LV sides. Correct configuration of this setting lets the relay calculate differential current correctly under normal load and through-fault conditions.

Phase Displacement

Transformers with different vector groups introduce a phase shift between primary and secondary currents. Common vector groups include:

  • YNd11 – 30° phase displacement
  • Dyn11, 30° phase displacement
  • Yy0, 0° phase displacement
  • Yd1, 30° phase displacement

The relay must compensate for this phase shift so that currents from both sides line up before differential current is calculated.

Amplitude Compensation

In addition to phase displacement, the relay must also compensate for differences in current magnitude between the HV and LV sides. This compensation is typically based on the transformer ratio and CT ratios, allowing the relay to compare currents on a common reference basis.

Internal vs External Compensation

For a YNd11 transformer, the relay must correctly account for the transformer phase displacement and current magnitude relationship. Whether compensation is performed internally by the numerical relay or through external CT connections depends on the relay design.

Some relays perform full compensation through software settings, where the user simply enters the vector group and CT parameters. Other relays may require specific CT connection configurations to achieve proper compensation. The implementation differs across manufacturers and relay models.

Confirm the Compensation Method in the Relay Manual

Always consult the specific relay manual to confirm:

  • Whether vector group compensation is handled internally or externally
  • The correct setting parameters for the transformer vector group
  • Any special CT connection requirements for the relay

Incorrect vector group settings will result in phase mismatch, persistent differential current, and potential relay maloperation.

What Is Zero-Sequence Current?

Zero-sequence current flows when a ground fault occurs in a system that has a grounded neutral. The magnitude and path of this current depend on the transformer winding configuration and the system grounding arrangement.

Transformer Winding Connection Impact

  • In a star-connected winding with a grounded neutral, zero-sequence current can flow through the neutral path and appears as phase current on that side.
  • In a delta-connected winding, zero-sequence current is trapped within the delta and does not appear in the line currents.

Take a transformer with one star-grounded winding and one delta winding. A ground fault on the star side produces zero-sequence current in the star side phase currents. The delta side sees none of it. If the relay calculates differential current without compensation, this imbalance may be seen as a false differential current.

Relay Compensation

Numerical relays can apply zero-sequence compensation to remove the zero-sequence component from the measured currents before differential calculation. This ensures that only the positive- and negative-sequence components are compared, avoiding maloperation during ground faults.

Zero-Sequence Compensation Is Not Universal

Function availability depends on relay model and transformer connection. Not all relays provide zero-sequence compensation, and the method of implementation varies between manufacturers. Always confirm the available functions and correct compensation settings in the specific relay manual for your application.

Transformer Inrush Restraint Setting

Why Transformer Inrush Causes Differential Current

Energizing a transformer applies the full system voltage to a cold core. The resulting magnetizing inrush is rich in harmonics. It can reach several times the transformer rated current. Because inrush current flows only on the energized side of the transformer, the relay sees a large differential current that resembles an internal fault.

Inrush is not a fault. Without special measures, the differential protection would trip incorrectly during transformer energization.

2nd Harmonic Restraint During Energization

The most common method used to prevent inrush tripping is second harmonic restraint. During inrush, the current waveform is highly distorted and contains a significant second harmonic component, typically ranging from 15% to 40% of the fundamental. The relay measures the ratio of the second harmonic to the fundamental frequency component. When this ratio exceeds the set threshold, the relay restrains operation for that phase.

Cross-Blocking / Phase Blocking

Some relays provide cross-blocking, where the detection of inrush on one phase can be used to restrain the differential protection on all three phases. This can be beneficial during inrush conditions where one phase exhibits a lower second harmonic content than the others. Function availability depends on the specific relay model.

How to Verify Inrush Restraint

Verification of inrush restraint settings typically involves:

  • Simulating inrush conditions using a secondary injection test set with harmonic injection capability
  • Checking that the relay correctly identifies inrush and applies restraint
  • Confirming that the relay does not trip when inrush currents are simulated

For detailed test procedures, see our transformer differential protection testing guide.

87T Setting Reference Table

The 87T setting parameters are collected here for reference during commissioning.

Setting ParameterPurposeTypical Consideration
Differential PickupMinimum operating thresholdSensitivity vs stability
Bias Slope 1Low-current restraintCT mismatch / normal errors
Bias Slope 2High-current restraintExternal fault stability
2nd HarmonicInrush restraintTransformer energization
5th HarmonicOverexcitation-related restraint/alarmRelay dependent
CT RatioCurrent scalingMatch actual CT
Vector GroupPhase compensationMatch transformer nameplate
Zero-Sequence CompensationGround-fault compensationApplication dependent
Trip DelayOperation timingProtection coordination

87T Setting Calculator

Transformer differential setting calculator (Excel). Enter the transformer rating, the two CT ratios and the impedance on the first sheet, and the workbook returns pickup, slope 1, slope 2, the bias knee, the harmonic thresholds and the unrestrained high set, each one checked against the terminal fault level and the CT accuracy limit. The bias characteristic sheet plots the curve that comes out of those numbers. Download the 87T setting calculator (xlsx, 14 KB)

The same workbook works for a two-winding transformer with a 1 A or a 5 A relay; change the secondary current on the Inputs sheet. For the motor version of the same calculation, see the motor protection relay setting calculator.

Transformer Differential Protection Setting Example

The table below shows what a transformer differential calculation returns for a typical two-winding unit, before the numbers are entered into the relay. Actual values depend on the transformer rating, CT parameters, fault conditions, relay characteristics and project requirements.

ParameterExample Setting
Differential PickupProject-specific
Slope 1Project-specific
Slope 2Project-specific
2nd Harmonic RestraintProject-specific
CT Ratio400/1A / 1200/1A
Vector GroupYNd11

All settings shown above are project-specific and must be calculated based on transformer nameplate data, CT ratios, fault studies, and relay manufacturer requirements. The values provided are for illustrative purposes only and should not be used as final settings.

See the complete calculation process in our Differential Protection Relay Setting Calculation guide.

Common 87T Setting Problems

The following table identifies common operational issues that may arise during transformer differential protection and their potential root causes related to incorrect settings.

ProblemPossible Setting Cause
False trip during energizationIncorrect harmonic restraint
Differential current during loadWrong CT ratio / vector group
External fault maloperationInsufficient bias / slope
Internal fault not detectedPickup too high
Ground fault sensitivity reducedIncorrect zero-sequence compensation

These issues may also result from non-setting-related factors such as CT wiring errors, hardware faults, or external system conditions. A systematic investigation should be conducted to identify the root cause before modifying any relay settings.

How to Verify 87T Settings

Verification StepWhat to Check
Parameter CheckConfirm CT ratio, vector group, pickup, slope, and harmonic restraint values match calculation results
CT Ratio and Polarity CheckConfirm CT ratios match nameplate ratings; verify CT polarity connections are correct
Pickup TestVerify relay operates at the set pickup threshold
Bias / Slope TestVerify relay operates correctly on the bias characteristic
Harmonic Restraint TestVerify relay remains stable during simulated inrush conditions
Trip Logic VerificationVerify trip command and alarms operate correctly

Run these before first energisation.

Functions of Transformer Differential Protection Relay

The transformer differential protection relay is a numerical relay designed to provide high-speed main protection for power transformers. It operates on the bias differential principle, ensuring stability during external faults and through-fault conditions while maintaining sensitive detection of internal winding faults. The relay supports flexible CT ratio and phase compensation, with harmonic restraint to prevent false tripping during transformer energization.

Key 87T relay functions include transformer differential protection, percentage-biased differential protection, high-set differential protection, harmonic restraint, CT ratio compensation, vector group compensation, and fast trip output for internal transformer faults.

Advanced event and fault recording functions enable detailed post-event analysis, while multiple communication interfaces allow integration into modern substation automation systems.

87T Relay FeaturesPurpose
Differential ProtectionDetect internal transformer faults
Percentage Bias / RestraintMaintain stability during external faults
High-Set DifferentialProvide fast operation for severe internal faults
2nd Harmonic RestraintPrevent false tripping during transformer inrush
5th Harmonic RestraintProvide restraint or alarm for overexcitation where supported
CT Ratio CompensationCorrect current magnitude differences
Vector Group CompensationCorrect phase displacement between transformer windings
Trip LogicRapidly isolate the transformer during internal faults

FAQ

Q1. What is transformer differential protection setting?

Transformer differential protection setting is the process of defining the relay’s operating parameters to ensure correct operation for internal faults and stability for external faults, inrush, and overexcitation. The setting defines the actual values entered into the relay.

Q2. What Are the Main 87T Settings?

The main transformer differential protection settings include differential pickup, bias slope, harmonic restraint, CT ratio, vector group compensation, zero-sequence compensation where applicable, and trip-related parameters. The exact settings depend on the transformer, CT characteristics, relay model, and project requirements.

Q3. How is differential pickup selected?

Differential pickup is selected to be above the maximum expected unbalanced current under normal and external fault conditions, while remaining below the minimum differential current expected for internal faults. This ensures both stability and sensitivity.

Q4. What is the purpose of bias slope in transformer differential protection?

Bias slope raises the operating threshold as through-current increases, allowing the relay to remain stable during external faults when CT errors and saturation may produce spurious differential currents. Slope 1 covers the low-current region, while Slope 2 addresses high through-fault conditions.

Q5. How should 2nd harmonic restraint be set?

The 2nd harmonic restraint is set to a percentage of the fundamental current, typically within the range specified by the relay manufacturer. The setting must be high enough to prevent blocking during internal faults with harmonic content, yet low enough to secure restraint during inrush.

Q6. How Does Transformer Vector Group Affect Differential Protection Settings?

The transformer vector group determines the phase displacement between winding currents. The differential protection relay must compensate for this phase displacement before calculating differential current. Incorrect vector group configuration can produce persistent differential current and cause protection maloperation.

Q7. How does CT ratio affect 87T settings?

CT ratio determines the secondary current magnitude seen by the relay. An incorrect CT ratio entry leads to incorrect compensated currents, affecting all derived values including differential and restraint currents.

Q8. What is the difference between differential protection setting and setting calculation?

Setting calculation is the analytical process of determining the appropriate values based on transformer data, CT parameters, and fault studies. The setting is the final step where those calculated values are entered into the relay. Calculation defines the values; setting applies them.

Q9. How should 87T settings be verified?

Verification includes parameter checks, CT ratio and polarity checks, secondary injection tests for pickup and slope, harmonic restraint tests, and trip logic verification.

Q10. Can 87T Settings Be Customized for a Project?

Yes. Transformer differential protection settings should be determined according to the transformer nameplate data, CT characteristics, system fault levels, transformer vector group, relay characteristics, and project protection requirements. The final values should be verified through calculation and relay testing before commissioning.

Q11. What are the main 87T relay functions?

The main 87T relay functions include transformer differential protection, percentage-biased differential protection, high-set differential protection, harmonic restraint, and CT ratio and vector group compensation. Fast tripping follows for internal transformer faults. These functions allow the relay to detect internal transformer faults while remaining stable during external faults and transformer energization.

When These 87T Settings Do Not Apply

The numbers above fit a two-winding oil-immersed transformer with an off-circuit tap changer. Four configurations need a different sheet, and copying the standard values into them is how a relay ends up tripping on load. On an 11 kV feeder with 4 kA of fault current, a 40 percent slope still leaves about 480 A of sensitivity at the knee point, and a drifting CT ratio is the usual cause of a nuisance trip on a unit that passed its type test.

  • Three-winding transformers with an on-load tap changer: the tap range adds mismatch on one side only, and the slope has to be raised or the pickup recalculated against the worst tap position.
  • Generator step-up units: 87T has to coordinate with 87G, and the generator’s contribution to a transformer fault changes the required operating time rather than the pickup.
  • Arc furnace and rectifier transformers: the load current is rich in harmonics that are not second harmonic, so second-harmonic blocking is unreliable and waveform or fifth-harmonic restraint is used instead.
  • Dry-type transformers below 5 MVA: inrush decays quickly and the CTs are often 5P10, so a 0.3 In pickup with 40 percent slope is too insensitive for the fault current available.
  • Where the trip coil circuit is not supervised, a 87T element that operates correctly still leaves the breaker free to refuse the trip, and the contact rating of the output has to be checked against the coil resistance.

Standards and Edition Reference

Edition years are the issues in force. Older setting sheets often cite IEEE C37.91-2000, which has been superseded twice since; a sheet carrying a burnt or welded trip contact is the other thing an audit finds. Insulation is proved at 5 kV for 1 min before any injection begins. The CT secondary is earthed at one point only, on 4 mm2 cable.

StandardWhat it coversEdition
IEC 60255-187-1:2021Differential protection function: requirements and test methods2021
IEEE C37.91-2021Guide for protective relay applications to power transformers2021
ANSI/IEEE C37.2-2022Device function numbers and acronyms2022
IEC 61869-2:2012Current transformers: additional requirements for protection2012
IEC 60076-1:2011Power transformers: general requirements2011
IEC 60255-1:2022Protection relays: common requirements and test conditions2022

Table 7. Standards cited in this article and the edition each reference follows.

Conclusion: Verifying the Settings Before First Energisation

87T setting is finished when the measured operate values match the sheet at every bias point, not when the numbers are typed in. Transformer differential protection settings must be coordinated with the transformer nameplate data, CT characteristics, vector group, relay model and system protection requirements. The key 87T parameters include differential pickup, bias slope, harmonic restraint, CT ratio and phase compensation.

The final settings should be verified through protection calculations, relay testing and commissioning procedures before the transformer is placed into service.

For the worked calculation example, see the setting calculation guide. To select the relay itself, see the 87T relay.

A 5 A CT into a 1 A relay: the error that survives commissioning

On one project the CTs at site were 5 A secondary and the transformer differential relay that arrived was the 1 A input variant. Nothing in the setting calculation catches this, because the calculation is right – it is the hardware that does not match. A 5 A secondary current driven into a 1 A input reads five times high, so every setting expressed in multiples of rated current is five times off, and at rated load the input already carries about 4.4 x In on a typical 200/5 CT, which is at the continuous thermal limit before any fault occurs. The relay is not faulty. It is the wrong variant, and no setting value fixes a rated current that does not match the CT. Country by country: project record.

Field record

Transformer differential settings in our record span 10 kV to 110 kV: Pakrut and Hamadoni in Tajikistan, Sakaka and Al-Jalamid in Saudi Arabia, a 34.5 kV substation in Mexico City, the 66 kV substation in Qatar, and the 110 kV substations in Myanmar and Russia. The vector group and the CT ratio pair drive the calculation; the country does not. See the project record for the full list.

References

SourceWhat it coversTypeEdition
ANSI/IEEE C37.2Device function numbers (87T and related functions)StandardConfirm current edition
IEC 60255 seriesMeasuring relays and protection equipment, performance and testingStandardConfirm current edition
IEEE C37.91Guide for protective relay applications to power transformersStandardConfirm current edition
Relay manufacturer manualsPermissible setting ranges, characteristic curves and calculation examplesManufacturer documentPer relay model

For a quotation with drawings and a test certificate, send the feeder schedule.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.