Table of Contents

What does a pump station automation and PLC control system include?

Pump station automation is the control layer that starts, sequences and protects pumps without an operator standing at the panel. A PLC or LCU cabinet runs the sequencing logic, protection relays watch the motors and cables, and a SCADA link carries status, alarms and commands between the site and the control room. Three documents set the boundaries for that hardware: IEC 61131-3:2025 defines the PLC programming languages, IEC 61439-2:2020 covers the assembly the controller and protection devices sit in, and IEC 60255-1:2022 sets general relay requirements. Motor protection practice follows IEEE C37.96-2012 and device numbers ANSI/IEEE C37.2-2022. Ten functions appear in almost every specification: the first three decide which pump runs, the middle four hold the process steady, and the last three keep the operator informed. PLC duty is mostly sequencing – which pump starts first, how run hours are equalised, and what blocks a start when a level transmitter fails. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

Pump station automation is the control layer that starts, sequences and protects pumps without an operator standing at the panel. A PLC or LCU cabinet runs the sequencing logic, protection relays watch the motors and cables, and a SCADA link carries status, alarms and commands between the site and the control room.

Pump station automation cabinet with PLC, HMI and protection relays (illustrative)

At a Glance: What Pump Station Automation Covers

  • Controller: a PLC or local control unit holds the sequencing logic, so the station keeps running when the SCADA link drops.
  • Process inputs: level, pressure and flow transmitters decide when a pump starts and which one leads.
  • Sequencing: lead/lag and duty/standby rotation spread run hours evenly across pumps.
  • Protection: overload (49), short circuit (50/51), earth fault (51N), phase loss and phase sequence (47), plus dry-run and winding temperature.
  • Drives: VFDs trim motor speed to hold pressure instead of throttling a valve.
  • Telemetry: Modbus TCP, IEC 60870-5-104 or DNP3 carry measurements to the SCADA master.
  • Operator layer: HMI on site, SCADA screens in the control room, alarm notification by SMS or email.
  • Records: event logs and trends are what turn a trip into a diagnosis instead of a guess.

Three documents set the boundaries for that hardware. IEC 61131-3:2025 defines the PLC programming languages, IEC 61439-2:2020 covers the assembly the controller and protection devices are built into, and IEC 60255-1:2022 sets the general requirements for the relays themselves. Motor protection practice follows IEEE C37.96-2012, and the device numbers come from ANSI/IEEE C37.2-2022.

The sections below go through what the controller does, which protection functions belong on a pump feeder, how the SCADA link is built, and what to specify for the cabinet.

What Is Pump Station Automation?

Pump station automation refers to the use of intelligent control and monitoring technologies to automatically operate, protect, and manage pumping equipment.

A typical system includes:

  • PLC (Programmable Logic Controller)
  • Motor protection relays
  • Human Machine Interface (HMI)
  • SCADA system
  • Variable Frequency Drives (VFDs)
  • Level, pressure, and flow sensors
  • Industrial communication networks

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

Pump station automation components: PLC, protection relays, HMI, VFD and sensors (illustrative)

These components work together to monitor operating conditions, control pump operation, detect abnormal situations, and provide remote access to operators.

Instead of relying on manual inspections and local controls, automated pump stations continuously optimize performance while providing instant fault notifications.

Pump Station Automation Functions

Ten functions show up in almost every pump station specification. The first three decide which pump runs, the middle four hold the process steady, and the last three keep the operator informed.

FunctionPurpose
Automatic Pump Start/StopAutomatic operation
Lead/Lag ControlPump sequencing
Duty/Standby ControlImprove reliability
Level ControlMaintain water level
Pressure ControlMaintain discharge pressure
Flow ControlRegulate water flow
VFD ControlAdjust pump speed
Alarm ManagementDetect abnormal conditions
Remote MonitoringCentralized supervision
Remote ControlStart/stop pumps remotely

Problems without automation in sewage pumping stations

Unexpected Pump Trips

One of the most common complaints from operators is unexplained pump shutdowns.

Frequent trips may be caused by:

Each unplanned trip can interrupt operations and increase maintenance costs.

Motor Overheating and Failure

Pump motors are often subjected to harsh operating conditions.

Common causes include:

  • Mechanical blockage
  • Excessive starting cycles
  • Phase imbalance
  • Poor ventilation
  • Overloading

Without proper protection, motor failures can result in expensive repairs and prolonged downtime.

Lack of Remote Monitoring

Many older pump stations still depend on local monitoring.

This creates several problems:

  • Delayed fault detection
  • Increased labor costs
  • Longer response times
  • Limited operational visibility

Operators may not discover a problem until significant damage has already occurred.

High Energy Consumption

Energy costs often represent one of the largest operating expenses in a pumping system.

Inefficient pump operation can lead to:

  • Excessive electricity consumption
  • Increased equipment wear
  • Reduced system efficiency

Automation helps optimize pump scheduling and energy usage.

PLC-Based Pump Station Control Systems & Plant Automation

PLC control for pump station duty is mostly sequencing: which pump starts first, how run hours get equalised, and what blocks a start when a level transmitter fails. The table below lists what a pump station PLC is normally asked to carry.

Key PLC Functions

Core PLC FunctionFunction DescriptionTrigger/Monitoring Conditions & Core Capabilities
Automatic Pump Start and StopPLC automatically starts or stops pumps according to preset conditions without manual intervention1. Tank levels2. Pipeline pressure3. Flow requirements4. Time schedules
Multi-Pump ControlRealizes coordinated control of multiple pumps in large pump stations, balancing equipment wear1. Alternate pump operation 2. Balance runtime hours of each pump 3. Prevent excessive wear on individual pumps
Alarm ManagementThe system continuously monitors critical operating conditions of the pump station and pushes alarm notifications immediately when abnormalities occur1. High water level warning 2. Low pressure alarm 3. Motor fault alarm 4. Communication failure alarm 5. Instant alarm push to operators when abnormality occurs
Data Logging and ReportingModern PLC systems automatically record core operation data of the pump station, form traceable full-cycle operation records, and support maintenance and system optimization1. Pump running hours 2. Energy consumption data 3. Real-time/cumulative flow rates 4. Alarm history 5. Data supports maintenance planning improvement and system operation optimization

Why Protection Relays Are Essential in Pump Stations

Pumping station automation relies on PLCs for control functions and protection relays to safeguard valuable electrical equipment.

PLC and motor protection relays wired in a pump station control panel (illustrative)

Without proper protection, faults can rapidly damage motors, cables, transformers, and switchgear.

Critical Protection Functions

Protection TypeDescription & Protected Conditions
Overcurrent ProtectionDetects excessive current from short circuits, mechanical jamming and motor overloads. The relay cuts off the fault to avoid severe damage.
Ground Fault ProtectionIdentifies leakage currents caused by ground faults which lead to safety risks and equipment damage, and triggers rapid disconnection.
Phase Loss ProtectionDetects phase loss, phase sequence errors and phase imbalance. Single-phasing will cause severe damage to three-phase motors.
Thermal Overload ProtectionContinuously monitors motor load to prevent overheating, as high temperature will reduce service life of equipment.
Under-Voltage and Over-Voltage ProtectionGuards against power quality disturbances that impair pump operation, maintains system stability and protects key equipment.

What Is a Pump Station SCADA System?

A pump station SCADA system is a supervisory control and monitoring system used to monitor and control pumps, motors, valves and process instrumentation. It collects data from PLCs, RTUs and field devices and provides operators with real-time status, alarms, trends and remote control functions.

SCADA screen showing pump status, level trend and remote monitoring alarms (illustrative)

What Operators Can Monitor?

Through a SCADA dashboard, operators can view:

  • Pump status
  • Flow rates
  • Tank levels
  • Pipeline pressures
  • Electrical parameters
  • Alarm conditions
  • Energy consumption

All information is available in real time.

Faster Fault Response

Instead of waiting for field reports, operators receive immediate notifications when:

  • Pumps trip
  • Water levels exceed limits
  • Communication links fail
  • Protection relays operate

That cuts response times.

Centralized Management

A single control center can supervise dozens or even hundreds of pump stations.

This improves operational efficiency while reducing staffing requirements.

Experience & Recommendations for Pumping Station Automation

Product Selection Tips

Small general pumping stations: Compact PLC + integrated motor protection relay, to meet basic automation and safety protection requirements.

Conventional multi-pump pumping stations: Modular PLC + separate motor protection & ground fault protection, equipped with Modbus communication.

Large-scale, unattended and intelligent pumping stations: High-end PLC system + digital intelligent protection relays + IEC 60870-5-104/DNP3 communication + remote monitoring platform, achieving optimal performance in automation, safety, maintenance and energy efficiency.

Small-capacity pumping stations generally have simpler requirements and lower budget. Compact controllers and all-in-one protection devices are well-suited here, delivering reliable performance at a reasonable cost.

Large-capacity units call for advanced configurations at a higher cost. The adopted control and protection devices feature complete functions, reliable protection performance and strong communication capability, well suited for complex operating conditions and unattended operation.

Components of a Pump Station SCADA System

Eleven items make up a complete pump station SCADA system. The first two decide local behaviour, the remaining nine carry data and commands outward.

No.ComponentFunction
1PLCLocal control core – executes pump sequencing, start/stop, interlocks, and alarm logic
2SCADA SoftwareCentral monitoring platform – real-time data display, alarm management, trending, and remote control
3HMIHuman-Machine Interface – graphical display of process parameters, operator input and command execution
4RTURemote Terminal Unit – data acquisition and long-distance communication for remote pump stations
5VFDVariable Frequency Drive – motor speed regulation for pressure control, flow control, and energy savings
6Protection RelaysMotor and electrical protection – overcurrent, overload, phase loss, and ground fault protection
7SensorsGeneral sensing devices – monitor equipment operating status and environmental conditions
8Flow MetersMonitor instantaneous and cumulative flow in pipelines for process control and water accounting
9Pressure SensorsMonitor pipeline and system pressure to ensure operation within safe limits
10Level SensorsMonitor tank, reservoir, or well levels for pump start/stop control and alarming
11Communication GatewayProtocol conversion and network interconnection between Modbus, IEC 60870-5-104, DNP3, etc.

Protection and Control Relays for Pump Stations

Summary Table

Relay TypePrimary FunctionKey Benefits
Motor Protection RelayFull motor protectionMulti-function, communication-ready
Overload ProtectionPrevents thermal damageThermal modeling, adjustable trip curves
Phase Failure ProtectionDetects loss of phaseFast response, prevents winding burnout
Phase Sequence ProtectionPrevents reverse rotationEnsures correct motor direction
Overcurrent ProtectionFast short-circuit protectionInstantaneous/time-delayed settings
Earth Fault ProtectionDetects insulation leakageSensitive to small faults, prevents escalation
Pump Protection RelayMotor + pump-specific protectionDry-run, cavitation, temperature monitoring

Integration with PLC and SCADA

All protection relays in a pump station are typically connected to the PLC via digital I/O or communication protocols (Modbus RTU, Modbus TCP, or Profibus). The PLC reads relay trip and status signals, executes interlock logic, and forwards alarm data to the SCADA system for centralized monitoring. SCADA operators receive real-time protection relay status, alarm notifications, and can remotely reset relays after fault clearance.

How Does a Pump Station SCADA System Work?

A pump station SCADA system integrates field devices, communication networks, and central control software to enable real-time monitoring, data acquisition, and remote control of pumping operations.

The system operates through the following layers:

Sensors & Field Devices

Measure parameters such as water level, flow, pressure, motor current, temperature, and valve position. Convert physical signals into electrical signals (4–20mA, digital, pulse) as data sources for the system.

PLC / RTU

Collects data from sensors, executes local logic (e.g., start/stop pumps based on level), and communicates with the SCADA master station. Receives and executes remote control commands.

VFD / Motor Control

Regulates pump motor speed and torque via Variable Frequency Drives (VFDs) for soft-start, energy saving, and precise control. Protection relays provide overcurrent, overload, and ground fault protection.

Communication Network

Links field devices to the SCADA master station using fiber optic, 4G/5G, radio, or Ethernet. Supports protocols such as Modbus, IEC 60870-5-104, DNP3, and IEC 61850.

SCADA Master Station

Central software platform that receives, processes, stores, and displays all field data. Provides data logging, alarm management, trend analysis, and remote control functions.

HMI / Control Center

Graphical dashboard displaying real-time pump status, flow, level, pressure, current, and alarms. Allows operators to view, control, and respond to system conditions.

Monitoring & Remote Control

Operators can start/stop pumps, adjust setpoints, acknowledge alarms, generate reports, and respond to faults, all from a central location. Site visits drop, and response gets faster.

What the Chain Delivers

The SCADA system continuously monitors and controls pump stations through a closed-loop process, enabling efficient, safe, and unattended operation.

Pump Station SCADA Monitoring

SCADA monitoring enables centralized visualization, analysis, and control of pump station operations through a real-time dashboard covering the following key parameters:

Pump Status

ParameterDescription
RunningMotor energized and rotating
StoppedNot operating (manual/auto stop)
FaultRelay trip or system fault
Local/RemoteControl mode (HMI/PLC or SCADA)

Process Data

ParameterDescription
Water LevelTank/reservoir level for start/stop and dry-run prevention
FlowInstantaneous and cumulative flow for control and accounting
PressureDischarge/suction pressure for safe and efficient operation

Electrical Data

ParameterDescription
VoltageSupply voltage monitoring
CurrentMotor load for overload and imbalance detection
PowerActive/reactive/apparent power for energy monitoring
FrequencyIncoming frequency; used for VFD and sync

Alarm Data

ParameterDescription
Pump FaultTrip from protection relay
Motor OverloadThermal overload detected
High TemperatureWinding/bearing overheat
High/Low LevelLevel threshold exceeded
Communication FailureField device to SCADA link lost

Monitoring Data at a Glance

CategoryParametersPurpose
Pump StatusRunning, Stopped, Fault, Local/RemoteOperational visibility
Process DataLevel, Flow, PressureHydraulic performance control
Electrical DataVoltage, Current, Power, FrequencyMotor health & energy management
Alarm DataFault, Overload, Temp, Level, CommsSafety & early warning

In Practice

SCADA continuously polls PLCs/RTUs and displays data on a color-coded dashboard (green = normal, yellow = warning, red = alarm). Operators can view trends, acknowledge alarms, and issue remote commands, which enables proactive maintenance, reduced downtime, and efficient management of large or remote pump stations.

Remote Pump Station Monitoring and Control

Remote monitoring and control enables operators to supervise and manage pump stations from a central SCADA control center, which removes the need for on-site personnel. That matters most for water utilities with geographically distributed assets.

Remote Pump Station Monitoring

  • View real-time pump status, process data, electrical parameters, and alarms
  • Access historical trends and event logs
  • Receive instant alarm notifications (SMS/email/dashboard)
  • Monitor multiple stations on a single screen

Reduces site visits, lowers costs, and enables faster fault detection.

Remote Pump Control

  • Start/stop individual pumps or pump groups
  • Change control modes (manual/auto/remote)
  • Adjust VFD speed setpoints
  • Acknowledge and reset protection relays
  • Open/close motorized valves

All actions are logged with operator ID, time stamp, and parameter values for full traceability.

Pump Station Remote Monitoring – How It Works

  • Field data acquisition: PLCs/RTUs collect data from sensors, relays, and VFDs
  • Data transmission: Sent via fiber, 4G/5G, radio, or satellite
  • Data processing: SCADA displays data on HMI
  • Operator action: Commands issued based on real-time information
  • Command execution: Transmitted back to field devices for action

Real-time closed-loop operation with latency of a few seconds.

SCADA Remote Control

  • Single dashboard for all stations
  • Role-based user authentication (operator/supervisor/engineer)
  • Interlock verification before command execution
  • Two-step confirmation (select-before-operate)
  • Remote setpoint adjustments for pressure, flow, and level

Centralized Pump Station Monitoring

BenefitDescription
EfficiencyOne operator manages multiple sites, reducing staffing
Faster ResponseInstant alarms enable rapid reaction
Data ConsolidationCentralized historical data for analysis
StandardizationConsistent procedures across all stations
ScalabilityEasy addition of new stations

Remote Capabilities Compared

CapabilityKey Benefit
Remote MonitoringReduced site visits, faster fault detection
Remote ControlNo on-site intervention needed
SCADA Remote ControlSafe, secure, auditable operations
Centralized MonitoringCost-effective, scalable, efficient

What Remote Control Changes

Remote pump station monitoring and control centralizes visibility and control of distributed assets. SCADA enables reliable operation, rapid alarm response, energy optimization, and reduced costs, all from a single control room. This is the foundation of modern intelligent water infrastructure.

Pump Station PLC and SCADA Architecture

In a modern station, PLC, RTU, VFD and SCADA are complementary components that work together to form an integrated, reliable control system.

PLC Control – Local Brain

  • Pump sequencing – Determines start/stop order based on demand
  • Start/Stop control – Issues commands based on level, pressure, or setpoints
  • Interlock logic – Prevents unsafe conditions (dry-run, valve interlock)
  • Duty/Standby rotation – Alternates pumps to equalize runtime
  • Lead/Lag control – Adds or removes pumps based on system demand
  • Alarm logic – Generates local alarms for abnormal conditions

SCADA Monitoring – Central Visibility

  • Real-time monitoring – Displays pump status, flow, level, pressure, current, temperature
  • Alarm management – Collects and prioritizes alarms from multiple sites
  • Trend recording – Stores historical data and performance curves
  • Remote operation – Start/stop pumps, adjust setpoints, acknowledge alarms
  • Historical data – Long-term storage for analysis and reporting
  • Remote pump stations – Deployed at distributed or hard-to-reach sites
  • Telemetry – Transmits data and commands over long distances
  • Central control center – Aggregates and processes data from all remote sites
  • Long-distance media – Supports 4G/5G, fiber, radio, satellite; protocols IEC 60870-5-104, DNP3, Modbus

VFD Control – Motor Optimization

  • Speed regulation – Adjusts motor speed by varying frequency and voltage
  • Pressure control – Maintains constant pressure without throttling valves
  • Flow control – Matches pump output to system demand
  • Energy efficiency – Reduces energy consumption in variable-load applications

How the Four Work Together

ComponentPrimary RoleControlled by / Communicates to
PLCLocal logic & sequencingSCADA via RTU/direct link
RTULong-distance telemetrySCADA master station
VFDSpeed & energy optimizationPLC via analog/fieldbus
SCADACentral monitoring & controlReceives data from PLC/RTU

PLC executes local decisions, RTU ensures remote communication, VFD optimizes motor performance, and SCADA provides centralized visibility and control. Together they form a complete, scalable station control system.

Typical Pump Station Automation Architecture

A modern station follows this layered structure:

LayerDevices / Protocols / Platforms
Field DevicesLevel sensors, Pressure transmitters, Flow meters
Control LayerPLC controller, HMI panel
Protection LayerMotor protection relays, Feeder protection relays, Ground fault relays
Communication LayerModbus TCP, IEC 60870-5-104, DNP3
Supervisory LayerSCADA system, Remote monitoring center
Enterprise LayerCloud analytics, Asset management platforms

This architecture provides complete visibility and control from the field level to enterprise management systems.

Layered control architecture from field sensors to a central control room (illustrative)

Where an LCU Cabinet Fits

An LCU cabinet (local control unit) is the physical form pump station automation takes on site: one enclosure holding the PLC or RTU, the motor protection relays, the I/O marshalling, the local HMI and the power and communication terminations. Ordering the control logic and the enclosure from separate suppliers is the fastest way to end up with a PLC that has nowhere to land its wiring.

Three numbers decide whether the cabinet survives its site. The enclosure rating follows IEC 60529, the IP code: IP54 suits a dry indoor pump room, IP65 is the usual ask for a wet well or an outdoor kiosk. The assembly itself is verified against IEC 61439-2:2020, which covers temperature rise, short-circuit withstand and clearances. And the form of internal separation matters wherever the cabinet sits alongside an MCC.

On a hydropower or irrigation project the same cabinet also carries unit control functions: gate and valve interlocks, bearing temperature trips and the governor interface. PLC control panels for hydropower and pumping stations are built to that layout, and the ATN-400 automation system covers the same duty where one supplier is preferred for controller, protection and SCADA.

Two checks before ordering. Confirm the relay cut-outs and CT wiring are inside the cabinet scope rather than left to the site. And confirm the protocol list matches the SCADA master, because adding IEC 60870-5-104 after delivery means a firmware change on site.

Both checks are cheap on paper and expensive on site.

Production Process for Pumping Station Automation Manufacturers

The purchaser provides equipment documents, including drawings and technical specifications.

The manufacturer develops a reasonable solution based on the technical documents and submits it to the purchaser.

The purchaser reviews the proposed configuration and solution and puts forward feedback. The manufacturer revises the documents repeatedly until the purchaser approves them.

Quotation is provided, together with the equipment delivery lead time.

After-sales service includes on-site commissioning and operator training.

Complete project handover and file archiving.

Factory inspection and packing of a control cabinet before shipment (illustrative)

How We Guarantee After-sales Service for Overseas Projects

Five commitments cover what happens after the cabinet ships. Ask for them in writing with the quotation, because most of them are schedule items rather than product features.

Service ItemDescription
Remote Technical SupportRound-the-clock remote technical support resolves most system problems online.
Technical Documents & TrainingFull sets of English technical materials, plus remote training for your staff.
Spare Parts SupplyCore spare parts are available with quick worldwide delivery.
On-site ServiceOn-site engineering service can be arranged when required.
Technical Follow-up & UpgradeContinuous technical consultation and system upgrade support.

FAQ

1. What is a pump station SCADA system?

A centralized platform for monitoring, controlling, and analyzing pump station operations remotely.

2. How does SCADA work in a pump station?

Field devices report to PLCs and RTUs, which pass the data to the SCADA master station for display on the HMI, and operators send remote commands back down the same path. The integrated pump station automation system page shows the hardware behind each step.

3. What equipment is included in a pump station SCADA system?

PLCs, RTUs, VFDs, protection relays, sensors (level, pressure, flow), MCCs, communication gateways, SCADA software, and HMI.

4. What does a pump station SCADA system monitor?

Pump status, process data (level, flow, pressure), electrical data (voltage, current, power, frequency), and alarms (overload, high temp, comms failure).

5. Can a pump station SCADA system control pumps remotely?

Yes. Start/stop pumps, adjust VFD setpoints, change modes, reset relays, and control valves from the control center.

6. What is the role of a PLC in pump station automation?

Local control brain: it handles sequencing, start/stop, interlocks, duty/standby, lead/lag, and alarms, even if SCADA communication is lost.

7. Difference between PLC and SCADA in a pump station?

AspectPLCSCADA
RoleLocal controlCentral monitoring
LocationPump stationControl center
FunctionReal-time logicDisplay, alarms, remote control
DependencyWorks independentlyRelies on PLC/RTU data

8. Can SCADA monitor multiple pump stations?

Yes. One SCADA system can manage dozens or hundreds of stations from a single control room.

9. Can VFDs be integrated with pump station SCADA?

Yes. VFDs connect to PLC via analog or fieldbus; SCADA monitors VFD status and allows remote setpoint adjustments.

10. What protection relays are used in pump stations?

Motor protection, overload, phase failure, phase sequence, overcurrent, earth fault, and pump protection relays (dry-run, cavitation, temperature).

Conclusion

As infrastructure becomes increasingly complex, pump station automation is no longer optional. It is a necessity for reliable, efficient, and cost-effective operation.

By combining PLC control systems, intelligent protection relays, SCADA platforms and industrial communication networks, operators can cut downtime, improve asset protection, lower energy consumption, and gain complete visibility into their operations.

Send the pump list, motor ratings, transmitter types and the SCADA protocol, and the engineering team comes back with a cabinet layout, a relay schedule and an I/O list you can price against. That is the shortest path from a process description to an orderable system.

Technical References

These are the documents pump station automation equipment is checked against on overseas projects. Version years matter: a datasheet quoting IEC 61131-3:2013 or IEC 61439-2:2011 is describing a withdrawn edition.

SourceWhat it coversTypeEdition
IEC 61131-3Programming languages for programmable controllers: ST, LD, FBD, SFCInternational Standard2025
IEC 61439-2Power switchgear and controlgear assemblies: what a controlgear assembly is verified againstInternational Standard2020
IEC 60529Degrees of protection provided by enclosures (IP code)International Standard1989+AMD1:1999+AMD2:2013
IEC 60255-1General requirements for measuring relays and protection equipmentInternational Standard2022
IEEE C37.96Guide for AC motor protectionIEEE Guide2012
ANSI/IEEE C37.2Device numbers used in protection schemes (47, 49, 50/51, 51N)Standard2022
IEC 60870-5-104Telecontrol over TCP/IP: the SCADA link for remote stationsInternational Standard2006+AMD1:2016

Note on older references. Datasheets still in circulation cite IEC 61131-3:2013 and IEC 61439-2:2011. Both have been superseded. IEC 60529 edition 3 is under development, so the 1989 base edition with its two amendments remains the current reference.

Questions on the settings in this guide go to the engineering team, normally answered the same working day.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.