Transformer Differential Protection|87T
Transformer-differential-protection|87t and control units are suitable for substations operating at voltage levels of 110 kV and below. Typically, they are installed in a single panel alongside transformer backup protection devices, non-electrical quantity protection devices, and transformer measurement and control units.
Description
Product Overview
- The AST-441H Digital Transformer Differential Protection|87T and Control Unit is suitable for transformer protection in substations with voltage levels of 110kV and below.
What Is an 87T Relay?
An 87T relay is a transformer differential protection relay that compares the currents entering and leaving the protected transformer zone to detect internal electrical faults.
- 87 = Differential Protection
- T = Transformer
- 87T = Transformer Differential Protection
Product Functions (ANSI)
- Transformer High-Speed Differential Protection 87T-HI / 87HS
- Transformer Differential Protection Relay 87T
- CT Open-Circuit Detection and Excessive Differential Current Alarm
- Overcurrent-start fan
Communication Features
- Communication interfaces (optional): RS-485, CAN bus, Ethernet, IEC 60870-5-103.
- This transformer differential protection device uploads real-time data such as measurements, waveforms, fault and alarm messages, together with all protection parameters and configurations. It supports remote online setting modification and protection function switching.
- The device also accepts commands from the master station, including remote control, time synchronization, parameter adjustment and data access.
Event Logging, Fault Recording
- Event logs cover protection trips and device self-diagnostic faults. They record event type, occurrence time and operating parameters for protection trips, as well as fault type and time for self-test anomalies.
- Fault records include protection operation time, type and RMS values pre- and post-triggering.
- Each channel captures 2 pre-fault cycles and 4 post-fault cycles, with 192 sampling points per channel.
- The SOE stores up to 48 records and fault reports store up to 16 records after power loss.
General Technical Data
| No. | Parameter Category | Core Technical Specification |
|---|---|---|
| 1 | Power Supply & Rated Electrical Parameters | 1. Rated control voltage: AC/DC 220 V
2. Power supply ripple coefficient: ≤ 5% 3. Voltage tolerance: -20% to +15% 4. Rated AC current In: 1 A/5 A (specify when ordering) 5. Rated AC voltage: 100 V 6. Rated frequency: 50 Hz (customizable per project requirements) |
| 2 | Power Consumption | 1. DC power circuit: ≤ 25 VA (normal operation), ≤ 30 VA (device activated)
2. AC voltage circuit: ≤ 1 VA/phase (at 100 V rated voltage) 3. AC current circuit: ≤ 0.5 VA/phase (1 A In), ≤ 1 VA/phase (5 A In) |
| 3 | Output Contact Performance | 1. DC circuit: 50 W breaking capacity (voltage ≤ 250 V, current ≤ 0.5 A, time constant 5 ± 0.75 ms); allowable make current ≤ 5 A
2. AC circuit: 50 W breaking capacity (voltage ≤ 250 V); maximum allowable make current 5 A |
| 4 | Insulation Performance | Meets IEC standard requirements for insulation resistance, dielectric strength, and impulse voltage |
How Does an 87T Relay Work?

Normal Operation:I₁ ≈ I₂ → Low differential current → No trip
Internal Fault:I₁ ≠ I₂ → High differential current → 87T operates → Transformer breaker trips
87T Relay Settings
| No. | Display Name | Range | Step | Remark |
|---|---|---|---|---|
| 1 | High-speed Differential Setting | |||
| 1.1 | High-speed Differential Protection | 1/0 | — | Enable(1) / Disable(0) |
| 1.2 | High-speed Differential Setting Value | 0.40~99.99A | 0.01A | |
| 2 | Differential Protection Setting | |||
| 2.1 | Differential Protection Enable | 1/0 | — | Enable(1) / Disable(0) |
| 2.2 | CT Broken Circuit Blocking Differential | 1/0 | — | CT break blocking function: Enable(1) / Disable(0) |
| 2.3 | Differential Current Setting | 0.50~99.99A | 0.01A | |
| 2.4 | Restraint Current Setting | 0.50~99.99A | 0.01A | |
| 2.5 | Differential Bias Current Setting | 0.50~99.99A | 0.01A | |
| 2.6 | CT Broken Circuit Threshold | 0.50~99.99A | 0.01A | |
| 2.7 | Harmonic Restraint Coefficient | 0.10~0.70 | 0.01 | Second harmonic restraint ratio |
| 2.8 | Slope / Ratio Restraint Coefficient | 0.30~0.70 | 0.01 | |
| 2.9 | Balance Coefficient | 0.100~1.999 | 0.001 | |
| 3 | Overcurrent Fan Control | |||
| 3.1 | Overcurrent Fan Start | 1/0 | — | Enable(1) / Disable(0) |
| 3.2 | Ventilation Time Delay | 0.00~999.99s | 0.01s | |
| 3.3 | Fan Start Current Setting | 0.5~99.99A | 0.01A | |
| 4 | General Setting | |||
| 4.1 | Motor Differential Mode Selection | 1/0 | — | |
| 4.2 | HV Side Y/△-11 Connection | 1/0 | — | |
| 4.3 | HV Side Y/△-01 Connection | 1/0 | — | |
| 4.4 | Secondary Wiring Mode | 1/0 | — | Delta/Y(1) / Y/Y(0) |
| 4.5 | Control Circuit Break Alarm | 1/0 | — | Alarm enable(1) / disable(0) |
| 4.6 | Current Angle Display | 1/0 | — | |
| 4.7 | Secondary Current Rated | 1/0 | — | 1A input(1) / 5A input(0) |
| 4.8 | Inter-tripping C6C7 | 1/0 | — | High-speed & differential trip C06C07(1) |
| 4.9 | Rated Secondary Current | 0.50~99.99A | 0.01A | HV side CT secondary rated current |
How Does an 87T Relay Prevent Transformer Inrush False Tripping?

During transformer energization, magnetizing inrush current is generated, creating a large differential current that risks false operation of the transformer differential protection 87T; the relay detects the prominent second harmonic component contained within the inrush current and activates harmonic restraint or blocking logic, which suppresses the differential trip command and prevents unwanted tripping.
87T Transformer Differential Protection Zone

87T vs 50/51 Transformer Protection
| Feature | 87T Relay | 50/51 Relay |
|---|---|---|
| Protection principle | Differential current | Overcurrent |
| Main protection area | Transformer internal zone | Backup / overcurrent |
| ANSI code | 87T | 50/51 |
| CT requirement | CTs on transformer sides | Current measurement CT |
| Internal winding faults | Highly sensitive | Depends on fault current |
| External fault stability | Bias/restraint | Time-current coordination |
| Typical role | Main transformer protection | Backup protection |
87T vs 87G vs 87L vs 87B
| Relay | Protected Equipment | ANSI Function |
|---|---|---|
| 87T | Transformer | Transformer differential |
| 87G | Generator | Generator differential |
| 87L | Transmission line | Line differential |
| 87B | Busbar | Bus differential |
How to Test an 87T Relay?

Before commissioning the transformer differential protection, technicians shall check the relay wiring, verify the CT ratio and CT polarity, and confirm the correctness of transformer vector group compensation; subsequently, perform a comprehensive secondary injection test, including differential pickup test, bias and slope characteristic test, harmonic restraint test, and trip output test, and finally record and verify all test results to ensure protection performance complies with design requirements.
Outline and Installation Dimensions

FAQ
Q:What is the scope of protection provided by a transformer differential protection device?
A:Transformer differential protection primarily protects the internal components of the transformer. When a turn-to-turn short circuit or a phase-to-phase short circuit occurs inside the transformer, the corresponding protection function in the transformer differential protection device will trigger an alarm and trip the circuit.
Q:How to Select a Transformer Differential Protection Device?
A:When selecting a transformer differential protection device for differential protection of transformer and differential protection for transformer applications, three key points should be noted: first, consider the transformer’s capacity, as larger capacity requires more advanced device functions; second, identify whether the transformer is two-winding or three-winding, since the suitable protection device differs by transformer type; third, refer to relevant industry standards and verify compliance with international norms such as IEC and IEEE.