Current Transformer Inside and Out: Core, Turns, Polarity
What is inside a current transformer and what does each part do?
A current transformer inside a switchgear panel is a ring of grain-oriented silicon steel wound with enamelled copper and cast in epoxy, with the primary conductor passing once through the middle. Four parts decide what the relay sees: core, winding, insulation and terminals, each with its own failure mode. The primary is usually the busbar or cable through the window and counts as one turn, so 400 A goes in and 80 turns make 5 A for the relay. Wound-primary suits low ratios like 50:5; bar-primary is the medium-voltage default. Multi-ratio taps X1 to X5 let one frame serve several ratios. Laminations of 0.23 to 0.35 mm keep flux below 1.5 T, so magnetising current stays small. A split core introduces an air gap, and that gap is where accuracy goes. Accuracy classes follow IEC 61869-2:2012 and IEC 61869-1:2023, with function numbers under IEEE C37.2. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.
Current transformer inside a switchgear panel is a ring of grain-oriented silicon steel wound with a few hundred turns of enameled copper, cast in epoxy, with the primary conductor passing once through the middle. Four parts decide what the relay sees: core, winding, insulation and terminals.
Written by Leon Zhang, protection application engineer. Reviewed by the relayprotect.com engineering team. Updated October 27, 2026.
At a Glance
- A wound-type unit holds four parts: magnetic core, secondary winding, insulation, terminal block.
- IEC 61869-2:2012 governs CTs; IEC 61869-1:2023 carries the general rules and test list.
- The ratio is turns, not size: 400:5 needs 80 secondary turns against one primary turn.
- Protection class 5P20 holds 5 % composite error up to 20 times rated current.
- A 15 VA burden at 5 A equals 0.6 ohm of secondary loop resistance, lead wiring included.
- An open secondary can reach kilovolts, so short S1 to S2 before pulling any wire.
- On the relay side the same loop lands on a coil, an armature and a contact set.
- Five numbers to quote: ratio, class, burden, insulation level and accuracy limit factor.
Current Transformer Inside and Out: The Four Parts That Matter
Open a failed unit on the bench and the order never changes. There is a magnetic core, a secondary winding, an insulation system and a terminal block. Each one owns a different failure mode, a different line on the datasheet and a different test at commissioning.
| Part | Job | What fails first | Symptom on site |
|---|---|---|---|
| Magnetic core | Carries flux around the ring | Lamination shorts, rust in a split core | Ratio error grows with primary current |
| Secondary winding | Turns primary amps into 5 A | Turn-to-turn short-circuit | Low ratio, hot winding, burnt smell |
| Insulation system | Holds 12 kV off the terminals | Partial discharge, then puncture | Earth fault or flashover on the secondary |
| Terminal block | Brings S1 and S2 to the wiring | Loose screw, corrosion | Open circuit, burnt terminal |
Table 1. The four internal parts of a wound-type CT, what each does, and how each fails.
Figure 1 shows the physical order of those parts. The bar runs through the window, the core closes around it, the winding sits on the core, and the epoxy covers everything except the terminal face. Nothing else moves. A CT has no armature, no spring and no contact, which is why a passive ring either works or fails quietly.

Selecting a relay for a live project?
Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.
The Primary Turn You Never See
A window CT has no primary winding in the usual sense. The busbar, the cable or the copper bar passing through the hole is the primary, and it counts as one turn. That single turn is the reason the whole design works: 400 A goes in, 80 turns turn it into 5 A, and nothing in the path touches the high voltage directly.
Wound-primary units exist for low ratios such as 50:5, where a single pass would leave a secondary of ten turns and poor performance. Bar-primary units are the medium-voltage default, and slip-over split cores are used where the cable cannot be disconnected. Multi-ratio taps marked X1 to X5 let one frame serve several ratios, and they follow the tap table in IEEE C57.13-2016.
One turn. That is the entire primary circuit.
A current transformer inside a metalclad panel is the same device, only the primary is a busbar instead of a cable.
What the Core Does With 400 A
The core gives the flux somewhere to go. Grain-oriented silicon steel, stacked in laminations of 0.23 mm to 0.35 mm, carries the flux at a working density well under 1.5 T so the magnetising current stays small. Nanocrystalline strip costs more and buys a much higher permeability, which is what revenue metering at class 0.2S needs. The same silicon steel does the heavy lifting in a power transformer, only there the flux is set by the supply voltage rather than by the load current.
A split core introduces a deliberate air gap, and that gap is where the accuracy goes. Two mating faces that do not close cleanly add reluctance, and a rusty joint adds more each year. Clamp-on units are fine for trending and poor for billing, for exactly this reason. The gap is the enemy.
Windings, Turns and Where 80 Comes From
The arithmetic is short. Ampere-turns balance, so primary current times primary turns equals secondary current times secondary turns. With one primary turn, the turns ratio equals the current ratio: 400 divided by 5 is 80, which is why 400:5 needs 80 turns of enameled copper on the ring.
Winding practice matters more than the datasheet suggests. A winding bunched to one side of the toroid leaks flux and the ratio drifts at high current, which shows up as a curve that bends early during a primary injection test. The wire gauge follows the secondary current: roughly 1.0 mm for 5 A, and a finer 0.5 mm for 1 A. A 1 A secondary is the better choice on a long run to a remote panel, because one fifth of the current means one fifth of the voltage drop for the same copper. Even spacing counts.
Insulation, Casting and the Housing
Resin casting is the medium-voltage default. The core and winding go into a mould, epoxy fills the voids, and the result is a solid block that resists moisture and mechanical shock. The quality of that casting decides the partial discharge figure, and partial discharge is what eventually punctures the insulation from the inside. IEC 61869-1:2023 lists the power frequency withstand and the partial discharge measurement as routine tests, and a 12 kV unit typically has to hold 28 kV for a minute with discharge under 10 pC.
Oil-immersed and tape-wrapped designs still appear in older substations, and a gas-insulated CT is a different animal again. All of them answer the same question: keep the secondary terminal at earth potential while the primary sits at tens of kilovolts. The housing also carries the IP rating, and an IP54 casting outdoors is not the same purchase as an indoor one. Casting quality decides the life.
Polarity Marks and the Direction of the Secondary Current
P1 and P2 mark the primary, S1 and S2 mark the secondary, and the dot convention says that current entering P1 leaves from S1 at the same instant. Get it backwards and the magnitude is still right while the direction is inverted. Overcurrent elements forgive that. A differential relay does not: matched CTs with one reversed polarity look like an internal fault the moment load current flows, and the scheme trips a healthy feeder.
The field check takes a battery and a moving-coil voltmeter. Apply a brief DC pulse to the primary, watch which way the needle kicks, and confirm it agrees with the dot. Do it before the panel is energised, not after. Direction is not optional.
Accuracy Classes Read Off the Nameplate
Metering classes describe how close the ratio and phase angle sit to truth at rated current. Protection classes describe how much composite error the CT may have during a fault, and for how many times rated current that promise holds. Mixing the two up is the most common specification error on a switchgear enquiry.
| Class | Typical use | Error limit |
|---|---|---|
| 0.2S | Revenue metering across a wide current range | 0.2 % from 1 % to 120 % of rated |
| 0.5 | Panel metering and sub-metering | 0.5 % at rated current |
| 5P10 | Feeder overcurrent on small loads | 5 % up to 10 times rated |
| 5P20 | Standard feeder and transformer protection | 5 % up to 20 times rated |
| 10P20 | Backup protection where accuracy is secondary | 10 % up to 20 times rated |
| PX or PR | Differential and high impedance schemes | Set by knee point and winding resistance |
Table 2. Accuracy classes a CT nameplate can carry, and where each belongs.
The letter P is the giveaway. Anything without it is a measuring class and should not be asked to carry a fault current.
Current Transformer Inside the Accuracy Limit: Burden and the Knee Point
Burden is the load the CT has to drive. A 15 VA rating at 5 A works out at 0.6 ohm of total loop resistance, and the loop includes the relay coil, the test link, every terminal and both legs of the lead. Copper is not free: 4 mm² cable runs about 0.0044 ohm per metre, so a 100 m loop already eats 0.44 ohm before the relay draws anything.
The knee point is where the core stops behaving. Below it the secondary current tracks the primary almost exactly, and above it the core saturates and the secondary stops growing. Class 5P20 puts that knee at 20 times rated, which for a 400:5 unit means 8,000 A of primary current. Figure 3 plots the shape: a straight line up to the knee, then a bend that flattens while the primary keeps climbing.

Burden is a budget, not a label.
Current Transformer Inside a Live Cubicle: What You Can and Cannot Touch
A CT secondary is a current source, not a voltage source, and that changes every safety rule. Open the circuit while the primary carries load and the ampere-turns have nothing to oppose them, so the core saturates and the collapsing flux drives a sharp voltage spike across the gap. Units have produced kilovolts this way, enough to puncture their own insulation and to injure whoever opened the link.
The working order is fixed. Short S1 to S2 at the test block first, then isolate, then work. Earth the secondary at one point only, normally at the panel end, because a second earth turns the lead into a loop that carries stray current. Treat every CT secondary as live until the shorting link is proved closed with a meter, not with a glance. Short first, work second.
Inside a Relay: Coil, Armature and Contacts
The 5 A leaving S1 arrives at a coil. On an electromechanical element that coil sits on a magnetic yoke, and the flux it produces pulls a hinged armature against a reset spring. The armature carries a moving contact, and when it travels far enough the moving contact meets a fixed contact and closes the trip circuit. Figure 2 shows those parts in order.

Practical numbers on that mechanism: pickup around 80 % of rating, dropout near 60 %, coil burden of 1 VA to 3 VA, contact rating of 5 A at 250 V AC, and an operate time of 10 ms to 20 ms before contact bounce settles. Solid-state relays replace the armature with sampling and logic, but the burden they present to the CT is still a real number in ohms and still counts against the 15 VA. That is the whole mechanism.
Inside of a Relay: Where the CT Secondary Lands
The wiring side is where most CT faults actually live. The secondary arrives on a terminal block, usually through a test link that can short the loop without disturbing the relay. Ring terminals on 2.5 mm² wire, ferrules crimped rather than twisted, and S1 and S2 marked at both ends are the difference between a scheme you can test and one you can only hope about. Mark both ends.
Inside of a relay the CT circuit also passes through an interlock or a test switch on many designs, and each of those adds contact resistance to the loop. A 0.1 ohm of extra resistance sounds trivial until you remember the whole budget was 0.6 ohm.
Two Devices, One Loop: From Primary Amps to Trip Coil
Put the two halves together and the path is plain. A 4,000 A fault on a 400:5 CT drives 50 A in the secondary, the overcurrent element compares that with its setting, the trip output energises a trip coil at 110 V DC, and the breaker opens in about 60 ms. No power electronics sit in that path, which is why the scheme survives a control supply dip that would crash a soft starter. Transformer inrush is the classic false trip on a differential scheme.

Protection that compares two CTs is stricter about matching. A differential scheme needs both units from the same class, the same ratio and the same burden, or the spill current shows up as a false operation. Details of that comparison sit in our guide to the circuit breaker that finally does the switching.
Ratings and Ratios: A Worked 400:5 Example
Take a 400:5 class 5P20 CT with a 15 VA burden on a feeder that carries 200 A. Secondary current is 200 divided by 80, so 2.5 A. Across a 0.5 ohm loop that is 1.25 V, and the CT runs at half its rated secondary current. Nothing is stressed and the ratio error stays inside 0.5 %.
| Parameter | Value | What it constrains |
|---|---|---|
| Rated primary current | 400 A | Ratio numerator, and the continuous rating |
| Rated secondary current | 5 A | Relay input and wiring size |
| Turns ratio | 80 to 1 | Winding count on the ring |
| Accuracy class | 5P20 | Composite error and the knee point |
| Rated burden | 15 VA | Total loop resistance, wiring included |
| Continuous thermal | 1.2 times rated, 480 A | Loading above nameplate for hours |
| Short time thermal | 25 kA for 1 s | Fault withstand before damage |
Table 3. The numbers on one 400:5 nameplate, and what each one constrains.
The last row matters on a feeder with a high fault level. A CT that saturates gracefully still has to survive the thermal duty, and 25 kA for one second is a common site specification.
How Current Transformers Fail
Failures are slow, then sudden. A winding that short-circuits a few turns drifts in ratio over months, and nobody notices until a metering audit or a mis-coordinated trip. Insulation that discharges quietly punctures in a switching surge. A terminal screw that was never torqued burns through a summer of load.
| Symptom | Likely cause | First check |
|---|---|---|
| Ratio error at high current only | Turn-to-turn short-circuit in the winding | Secondary resistance against the nameplate |
| Burnt terminal, sharp smell | Loose screw, high contact resistance | Thermographic scan under load |
| Earth fault on the secondary | Insulation puncture after partial discharge | Insulation resistance at 500 V |
| Nuisance trip on motor start | Reversed polarity or wrong class | Polarity flick test, class review |
| Open circuit alarm, no current | Broken wire or open test link | Continuity with the secondary shorted |
Table 4. Common CT and CT-circuit failures, ranked by how often they reach the panel.
A current transformer inside a sealed cubicle rarely fails from load. It fails from moisture, vibration and a screwdriver that stopped one turn short.
Two failures dominate the statistics in my own call-outs: an open secondary left by a technician who pulled a meter without shorting, and a corroded joint in a split core that had been clamped over a cable for eight years. Both are preventable with a link and a wire brush.
Current Transformer Inside the Spec: What Your Enquiry Must State
A CT is ordered from a short list, and every line on that list changes the price. Leave one out and the supplier will pick a default for you, which is rarely the one your protection study assumed. Every current transformer inside a bid package carries is priced off these eight lines.
- Ratio, written as primary to secondary, and whether multi ratio taps are needed.
- Accuracy class and accuracy limit factor, for example 5P20, not just 5P.
- Rated burden in VA at the secondary current you actually intend to use.
- Insulation level, 12 kV, 24 kV or 36 kV, matched to the switchgear it sits in.
- Mounting: bar primary, slip-over, window, or a wound primary for low ratios.
- Terminal arrangement, because a 4 mm² ring terminal does not fit every block.
- Ingress protection and ambient range for an outdoor or a coastal installation.
- Standard and edition the certificate must quote, such as IEC 61869-2:2012.
Testing Before You Energize
Five checks catch nearly everything. Measure secondary resistance and compare it with the nameplate or a sister unit, since a shorted turn shows up as a low reading. Prove polarity with a DC pulse. Measure insulation resistance at 500 V and expect well over 100 M ohm on a dry casting. Measure the loop resistance to confirm the burden budget. Then inject primary current at 20 % and at 100 % of rated and compare the secondary reading.
The last step is the one people skip. A ratio check at low current passes a CT that saturates early, because the bend only appears near the knee. Inject at 100 % and, where the set allows it, at the accuracy limit factor. Low current hides the bend.
When a CT Teardown Is the Wrong Answer
Not every accuracy complaint is an internal problem, and opening the unit is the most expensive way to find that out. Five situations argue for stopping before the spanners.
- When the ratio error appears only above the knee: that is a burden or class issue, so re-check the loop resistance before blaming the winding.
- When the meter reads low but primary injection is correct: the fault sits in the wiring or the test link, not inside the casting.
- When the unit is oil-filled and the site has no oil handling: open it and you own an environmental incident as well as a failed CT.
- When the panel is still energised and the secondary cannot be shorted: no reading is worth an open circuit at 12 kV.
- When the class was wrong from the start: a 5P10 cannot be repaired into a 5P20, and a purchase decision is cheaper than a teardown.
Standards Behind Both Devices
The CT side now rests on one family. IEC 61869-1:2023 replaced the 2007 edition and absorbed the old low-power part, so the general requirements and the test list live in one document. IEC 61869-2:2012 adds the specific requirements for current transformers, including the 5P and 10P classes and the accuracy limit factor. Low-power passive units follow IEC 61869-10:2017. That merger matters at tendering.
On the relay side, IEC 60255-1:2022 sets the general requirements for measuring relays and protection equipment, and ANSI/IEEE C37.2:2022 fixes the device numbers that name each function on the drawing. IEEE C57.13-2016 remains the reference for instrument transformers in North American practice, with its own C-class relaying accuracy ratings. One family, one document.
| Standard | Edition | Coverage |
|---|---|---|
| IEC 61869-1 | 2023 | General requirements, dielectric and partial discharge tests |
| IEC 61869-2 | 2012 | Current transformers, classes 5P and 10P, accuracy limit factor |
| IEC 61869-10 | 2017 | Low-power passive current transformers |
| IEC 60255-1 | 2022 | Measuring relays and protection equipment, general requirements |
| ANSI/IEEE C37.2 | 2022 | Device function numbers used on protection drawings |
| IEEE C57.13 | 2016 | Instrument transformer requirements, North American practice |
Table 5. Standards cited on a CT enquiry and on the relay drawing.
Conclusion: What the Inside Tells You
Current transformer inside a panel is a passive device with four parts and one job: scale current without touching voltage. The core carries flux, the winding sets the ratio, the insulation keeps the primary away from the terminal, and the block brings 5 A out to the relay. Size the burden before you choose the class, short the secondary before you touch a wire, and ask for the standard edition on the certificate.
Get those four right and the device outlives the panel it was fitted to. Get the burden wrong and a perfectly healthy CT will lie to the relay at exactly the moment the relay matters.
Frequently Asked Questions
What is inside a current transformer?
Four things: a laminated magnetic core, a secondary winding of fine enameled copper, an insulation system such as cast epoxy, and a terminal block carrying S1 and S2. The primary is usually the busbar or cable that passes once through the window, so it is not a wound part at all.
Why is a current transformer secondary never left open?
With the primary energised there is no opposing ampere-turns, so the whole primary current magnetises the core. The core saturates, and the collapsing flux induces a peak of kilovolts across the open terminals. Short S1 to S2 before you remove any meter or relay.
How do I read 5P20 on a nameplate?
The 5 is a composite error limit of 5 percent, and the 20 is the accuracy limit factor: the CT stays inside that limit up to 20 times rated primary current. A 400:5 class 5P20 unit holds its accuracy up to 8,000 A of primary current.
What does burden mean in VA?
Burden is the apparent power the CT can drive through the whole secondary loop, relay coil and lead wiring included. A 15 VA CT at 5 A can carry 0.6 ohm of total loop resistance. Add the relay, the wire and the test link, and the sum must stay under that figure.
How many turns are on the secondary of a 400:5 CT?
Eighty. The turns ratio equals the current ratio when the primary is a single pass, so 400 divided by 5 gives 80 turns. A 200:5 unit needs 40 turns, and a 1000:5 unit needs 200.
Can I use a 1 A secondary instead of 5 A?
Yes, and on long cable runs you probably should. A 1 A secondary produces one fifth of the voltage drop for the same wire, so the same VA burden reaches much further. The trade is a finer winding and a slightly higher cost per unit.
Field record
Wound and bar-primary CTs appear in every voltage class we work in: 6 kV cement grinding in Bolivia, 11 kV distribution rooms in Nepal and the UAE, 34.5 kV in Mexico City, 66 kV in Qatar and 110 kV substations in Myanmar and Saudi Arabia. Above roughly 35 kV the primary is almost always bar or hairpin; below it, wound primaries dominate because the ratio has to be changed on site. The project record lists every country and its voltage band.
Related Reading on This Site
- Our electromechanical relays guide covers the armature and contact side in more detail.
- The differential relay page explains why matched CTs matter on a unit scheme.
- See how a CT mounts among the busbars in our switchgear assemblies guide.
- For the generator end of the same loop, read generator protection.
- Supervisory reporting of CT values is covered in the SCADA monitoring guide.
For a quotation with drawings and a test certificate, send the feeder schedule.
Related product: 51N Zero sequence current protection relay