Ping-Pong Type Rotor Earth Fault Protection Relay | 64R Relay for Generators
The rotor earth fault protection relay (50N/51N ) is suitable for protecting generators with hydro turbine capacities not exceeding 10 MW and steam turbine generator capacities not exceeding 100 MW.
Protection Configuration
The generator rotor is grounded at one point
Two-point grounding of the generator rotor
Communication Mode
Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)
Description
Rotor Earth Fault Protection
What Is Rotor Earth Fault Protection?
Rotor earth fault protection is a generator protection function designed to detect insulation failure between the rotor winding or excitation circuit and ground. A 64R relay, also called a rotor earth fault protection relay, continuously monitors rotor insulation and provides an alarm or trip signal when a ground fault is detected.
Why is rotor earth fault protection required?
| Reason | Explanation |
|---|---|
| Localized heating | First earth fault causes uneven current distribution and insulation stress |
| Second fault risk | Two earth faults create a shorted winding section → vibration, shaft magnetization, burning |
| Equipment protection | Rotor is costly and critical; early detection prevents major damage |
| Maintenance planning | Alarm-based protection allows scheduled repairs instead of forced outages |
| Code compliance | Required by standards for large generators and critical machines |
What happens when a rotor winding is grounded?
| Grounding Status | Trip Required? | Main Risks |
|---|---|---|
| Single-point grounding | No trip (alarm only) | Early warning of insulation deterioration; maintenance should be scheduled promptly |
| Two-point grounding | Immediate trip required | Winding burnout, vibration damage, rotor shaft magnetization |
| Intermittent / arcing grounding | Depends on severity | Overvoltage damages turn-to-turn insulation and expands the fault |
What is the difference between single-point and two-point rotor ground faults?
| Comparison Item | Single-Point Grounding | Two-Point Grounding |
|---|---|---|
| Number of fault points | 1 | 2 (at different locations) |
| Short-circuit loop formed? | No (no short-circuit current) | Yes (partial winding is shorted, generating massive short-circuit current) |
| Immediate impact on unit | No significant effect; unit can continue operating | Severe vibration, winding burnout, rotor shaft magnetization |
| Protection response | Alarm signal only, no trip | Immediate trip and shutdown |
| Remedial action | Schedule planned maintenance | Emergency shutdown, full inspection and repair |
64R Relay
What Is a 64R Relay?
A 64R relay is a generator protection relay used to detect rotor earth faults and monitor the insulation resistance of the rotor winding or excitation circuit to ground, commonly referred to as a rotor earth fault relay, rotor ground fault relay, generator rotor protection relay, or excitation circuit ground fault relay.
| Term | Meaning |
|---|---|
| 64R | ANSI device number for rotor earth fault protection |
| 64R relay | Relay used to detect rotor earth faults |
| Rotor earth fault protection | Protection function for detecting rotor insulation failure |
| Rotor ground fault protection | Alternative terminology for rotor earth fault protection |
| Rotor earth fault protection relay | Dedicated relay/IED providing 64R protection |
How Does a 64R Rotor Earth Fault Relay Work?
Ping-Pong Method is an online insulation resistance monitoring technique used for rotor earth fault protection. It is an improved variant of the injection-type detection method. Its core principle is to alternately inject positive and negative DC voltages, and measure the leakage current during each injection, thereby eliminating system interference and accurately calculating the insulation resistance of the rotor winding to ground.

64R Relay Protection Functions
| Function | Description |
|---|---|
| Rotor insulation monitoring | Continuously tracks rotor-to-ground insulation condition |
| Single-point rotor earth fault alarm | Alarms on first earth fault; unit remains operational |
| Two-point rotor earth fault protection | Trips immediately on second fault to prevent severe damage |
| Ground fault detection | Detects earth faults in rotor/excitation circuit |
| Insulation resistance measurement | Measures insulation resistance to assess insulation health |
| Fault location | Pinpoints fault position along rotor winding for repair |
| Alarm output | Provides alarm signal (contact/digital) for operator warning |
| Trip output | Sends trip signal to shut down generator on critical faults |
| Event recording | Records faults, timestamps, and relay actions for diagnostics |
| Communication | Supports SCADA integration via standard protocols (Modbus, IEC 61850, DNP3) |
AGZ-441H Product Overview
- The rotor earth fault protection relay 50N/51N is suitable for protecting generators with hydro turbine capacities not exceeding 10 MW and steam turbine generator capacities not exceeding 100 MW.
- Together with generator differential protection and generator backup protection, it forms a comprehensive generator protection system. It can be installed in a centralized panel or distributed across multiple locations.
Device storage capacity
- Trip Reports: The device cyclically stores up to 128 latest trip records.
- Operation Log: It cyclically records up to 128 recent operation events.
- Device Self-Test: Up to 32 groups of latest self-test data are saved in cyclic mode.
- Fault Recording: The device cyclically keeps 32 recent fault recording events.
Environmental Conditions
- Operating temperature range: -10°C to 55°C
- Operating temperature range: -40°C to 70°C
- Storage temperature: -40°C to 80°C
- Relative humidity: 5%–90% (no condensation inside the product)
- Altitude: ≤2000 m; for altitudes above 2000 m, adjustments shall be made using the altitude correction factor.
Protection Setting Sheet
| No. | Setting Name | Setting Range | Unit | Default Value | Remark |
|---|---|---|---|---|---|
| 1 | One-point Ground Fault Setting | 0.1–100 | kΩ | 10 | Unit: kΩ (kiloohm) |
| 2 | One-point Ground Fault Time Delay | 0–100.00 | s | 5 | Adjustable on-site as required |
| 3 | One-point Ground Fault Mode | 0–2 | — | 2 | 0=Disabled, 1=Trip, 2=Alarm |
| 4 | Two-point Ground Fault Setting | 0.050–0.999 | % | 30% | 0.3, position deviation between one-point and two-point grounding |
| 5 | Two-point Ground Fault Time Delay | 0–100 | s | 2 | |
| 6 | Ground Protection Starting Voltage | 10–500 | V | 50 | Default: 50V; set according to actual excitation voltage |
Dimensions and Cutout Sizes

Applications of 64R Rotor Earth Fault Protection
- Hydroelectric generators
- Steam turbine generators
- Gas turbine generators
- Diesel generators
- Industrial synchronous generators
- Large synchronous motors
- Power plants
- Industrial power systems
FAQ
1. What is a 64R relay?
A 64R relay is a generator protection relay dedicated to detecting rotor earth faults and monitoring the insulation resistance of the rotor winding or excitation circuit to ground.
2. What does a 64R relay protect?
It protects the generator rotor winding and the excitation circuit against earth/ground faults.
3. What is rotor earth fault protection?
It is a protection scheme that detects insulation failures between the rotor winding and ground, preventing damage from single-point (alarm) or two-point (trip) earth faults.
4. How does rotor earth fault protection work?
It continuously monitors the insulation resistance of the rotor circuit to ground. When a fault occurs, the leakage current increases; the relay measures this change and issues an alarm or trip signal based on the fault severity.
5. What causes a rotor earth fault?
Common causes include:
-
Aging or deterioration of rotor insulation
-
Mechanical stress, vibration, or thermal overload
-
Moisture ingress or contamination
-
Manufacturing defects or previous repair damage
6. What happens when a generator rotor has an earth fault?
-
Single-point fault: Alarm only; unit can continue running but requires scheduled maintenance.
-
Two-point fault: Immediate trip required; may cause severe vibration, winding burnout, and shaft magnetization.
7. What is the difference between 64R and 64S?
| ANSI Code | Application |
|---|---|
| 64R | Rotor earth fault protection (for generator rotor circuit) |
| 64S | Stator earth fault protection (for generator stator winding) |
8. Does a 64R relay detect single-point and two-point rotor faults?
Yes. A 64R relay typically:
-
Alarms on a single-point earth fault
-
Trips immediately upon detection of a two-point earth fault
9. What is the difference between voltage injection and ping-pong rotor earth fault protection?
| Method | Principle |
|---|---|
| Voltage Injection | Applies a fixed DC/AC voltage to the rotor circuit and measures leakage current to calculate insulation resistance |
| Ping-Pong Method | Alternately injects positive and negative DC voltages; uses differential measurement to cancel interference, providing higher accuracy and noise immunity |
10. How do you test a 64R relay?
Typical testing methods include:
-
Insulation resistance test – using a megger to simulate insulation degradation
-
Injection test – applying a known fault resistance to verify alarm/trip thresholds
-
Secondary injection test – using a relay test set to inject signals and check operating time, pickup values, and logic outputs
-
Communication check – verifying SCADA data exchange and event recording
Other Generator Protection Equipment
64R Rotor Earth Fault Protection Relay | Voltage Injection
441H generator backup protection relay
Additional information
| Rated Voltage | 3.0kV, 3.6kV, 7.2kV, 12kV, 12.7kV, 24kV, 25.2kV, 36kV, 40.5kV, 72.5kV, 126kV, 252kV, 363kV, 550kV, 800kV |
|---|











xiao zhang –
Rotor earth fault relay (ANSI 64R) monitors generator rotor winding insulation damage. High measuring precision, adjustable sensitivity and standard communication, widely used for turbo & hydro generators.