Send an Inquiry
Solar Anti-Islanding Protection

Solar Anti-Islanding Protection: Principles, Devices and Applications

Table of Contents

What is solar anti-islanding protection and why is it required?

Solar anti-islanding protection detects an unintended island and opens the interconnection breaker as soon as the utility supply is lost or drifts outside its limits. ANSI functions 27, 59, 81U, 81O and 81R do the measuring, and IEEE 1547-2018 sets the 2 s disconnection deadline that keeps line workers safe. Islanding occurs when a PV array keeps energising a feeder after the breaker opens, because local load still matches generation; voltage and frequency then drift outside their band and damage the inverters. Passive detection watches voltage and frequency for a threshold crossing; active detection injects a small disturbance such as reactive power and watches the reply, since an island cannot absorb it. Running both shrinks the non-detection zone. Three routes are common: inverter firmware, a relay at the point of common coupling, and a coordinated scheme for utility-scale sites. IEEE 1547, UL 1741 and IEC 62116 all require anti-islanding on grid-connected PV. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

Solar Anti-Islanding Protection at a Glance

  • Definition: solar anti-islanding protection detects the instant a grid-connected PV plant loses the utility supply, then opens the interconnection breaker so the plant cannot keep energising an island.
  • Test standard: IEC 62116 sets the islanding test procedure for PV inverters, and IEC 61727 classifies inverters that clear it as non-islanding.
  • Disconnect time: IEEE 1547-2018 requires distributed resources to disconnect within 2 seconds of island formation.
  • Passive method: ANSI functions 27, 59, 81U, 81O and 81R (ROCOF) watch voltage, frequency and rate of change of frequency without injecting anything.
  • Active method: AFD, SFS, SMFS and reactive power disturbance inject a small signal, and that is what shrinks the non-detection zone (NDZ).
  • Usual settings: undervoltage 70-90% of Un, overvoltage 110-120%, underfrequency 47-49.5 Hz, overfrequency 50.5-52 Hz, ROCOF 0.5-1.0 Hz/s.
  • Location: at the point of common coupling (PCC), on the grid side, with current transformers upstream of the PCC.
  • Region codes: UK G98 and G99, Germany VDE-AR-N 4105, Australia and New Zealand AS/NZS IEC 62116, Gulf States GSO IEC 62116.

What Is Solar Anti-Islanding Protection?

Anti-islanding protection relay installed at the PCC of a grid-connected PV plant

Solar anti-islanding protection is the protection function that detects an unintended island and opens the interconnection breaker as soon as the utility supply is lost or drifts outside its limits. ANSI functions 27, 59, 81U, 81O and 81R do the measuring, and IEEE 1547-2018 sets the 2 s disconnection deadline.

Three routes are in common use. Inverter firmware carries the function on small arrays. An anti-islanding relay at the point of common coupling (PCC) covers commercial and industrial plants. A coordinated scheme, where the inverter and the relay exchange status over a communication link, covers utility-scale sites that have to show the DNO a redundant trip path.

What Is Islanding in a PV System?

Islanding occurs when a solar PV system keeps energising part of the electrical grid after the utility grid has been disconnected. For example, if a fault causes the substation breaker to open, a feeder with PV systems could remain energized if local load matches the remaining generation. The inverters, still seeing voltage, continue to supply power, creating an “island” independent of the main grid. This condition is dangerous because voltage and frequency can drift outside acceptable limits, posing risks to utility workers and connected equipment.

Why Is Anti-Islanding Protection Required?

Anti-islanding protection is mandated by international grid standards for two primary reasons:

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

Personnel Safety: the first job is to protect utility workers. When a grid outage occurs, linemen may be dispatched to repair downed lines. If a PV system continues to energize those lines, it creates an electrocution hazard. Anti-islanding protection ensures the PV system shuts down within two seconds of grid loss per IEEE 1547.

Equipment Protection: islanding lets voltage and frequency drift outside their acceptable band, which can damage the array, the inverters and anything else fed from the same bus.

Regulatory Compliance: IEEE 1547, UL 1741 and IEC 62116 all require anti-islanding protection on grid-connected PV, whatever the local grid operator calls it.

How Anti-Islanding Protection Works in Solar PV

Anti-islanding protection in PV systems is typically implemented using passive and active detection methods, often combined in modern inverters to minimize non-detection zones.

Passive Detection: the relay watches grid parameters such as voltage and frequency and trips once the deviation passes a threshold. ANSI functions 27, 59, 81U, 81O and 81R (ROCOF) cover that group.

Active Detection: the relay injects a small disturbance, reactive power for instance, and watches the reply. An island cannot absorb it, so voltage or frequency moves out of limit and protection trips. Slip-mode frequency shift is the most common active technique. Running passive and active detection together is what shrinks the non-detection zone.

How Does Solar Anti-Islanding Protection Work?

Anti-islanding detection in solar PV systems generally uses two approaches: passive detection and active detection. Modern protection schemes may combine both methods to improve detection reliability and reduce the non-detection zone (NDZ).

Passive Anti-Islanding Detection

Passive detection continuously monitors voltage, frequency, and phase without injecting disturbances. Protection trips when parameters deviate from thresholds.

MethodDetection Principle
Over/Under Voltage (27/59)Trips when voltage exceeds or falls below range
Over/Under Frequency (81O/81U)Trips when frequency exceeds or falls below range
ROCOF (81R)Trips when rate of frequency change exceeds threshold

Advantages: Simple, reliable, no impact on power quality.
Limitation: Non-detection zone (NDZ) exists when PV output closely matches local load.

Active Anti-Islanding Detection

Active detection injects small disturbances; in an island condition, disturbances amplify and trigger tripping.

TechniquePrinciple
Active Frequency Drift (AFD)Shifts output frequency; accelerates deviation in island
Sandia Frequency Shift (SFS)Positive feedback accelerates frequency deviation
Slip-Mode Frequency Shift (SMFS)Alters phase angle to destabilize the island
Reactive Power DisturbanceInjects reactive power variation and monitors voltage response

Hybrid Approach: passive monitoring runs continuously, and the active disturbance only fires once the passive logic flags something suspicious. That is the arrangement that holds the NDZ down to almost nothing.

Voltage and Frequency Monitoring

Basic passive detection methods, required by all grid interconnection standards.

  • Undervoltage (27): Trips when voltage drops below 70-90% of rated
  • Overvoltage (59): Trips when voltage rises above 110-120% of rated
  • Underfrequency (81U): Trips when frequency falls below setpoint (e.g., 49.5Hz)
  • Overfrequency (81O): Trips when frequency exceeds setpoint (e.g., 50.5Hz)

Per IEEE 1547-2018, distributed generators must disconnect within 2 seconds after islanding.

ROCOF and Other Detection Methods

Rate of Change of Frequency (ROCOF / 81R)
Detects sudden frequency changes. In an island, frequency drifts rapidly due to power imbalance; trips when ROCOF exceeds threshold (typically 0.5–1.0 Hz/s).

Vector Surge (78)
Detects sudden phase angle changes caused by grid disconnection.

Method Comparison

MethodTypeNDZSpeedPQ Impact
Voltage/FrequencyPassiveModerate<2sNone
ROCOFPassiveSmall100-200msNone
Active DriftActiveVery smallMediumSlight
HybridCombinedNear-zeroFastMinimal

Anti-Islanding Protection in Grid-Connected PV Systems

Anti-islanding protection for grid-connected PV systems prevents a solar installation from continuing to energize the utility network after an unintended loss of grid supply. Depending on the project design, anti-islanding functions may be integrated into the inverter, provided by an external protection relay, or implemented through a coordinated protection scheme.

Typical Protection Architecture

Anti-islanding protection arrangement at the point of common coupling in a PV plant

Site wiring is where these schemes usually fail. Voltage is taken from the grid side of the main AC breaker, current transformers go upstream of the PCC, and the trip contact lands on the shunt trip coil of that same breaker. Everything downstream of those three connections is software.

Where Is Anti-Islanding Protection Implemented?

Anti-islanding protection may sit inside the inverter, in an external relay, or in both. The usual arrangement is secondary equipment at the PCC: the inverter keeps its own firmware protection, and the relay adds the functions the inverter was never asked to do.

OptionDescriptionTypical Application
Inverter-IntegratedFunctions embedded in inverter firmwareSmall to medium residential/commercial PV
External RelayDedicated anti-islanding protection relay (e.g., ASF-441H) installed at the PCCLarge commercial, industrial, utility-scale PV
Coordinated SchemeInverter + external relay with communicationProjects requiring redundancy or specific grid code compliance

Why an External Relay May Be Required

  • Grid code compliance – Some utilities require a separate certified device at PCC
  • Redundancy – Provides independent backup protection for critical installations
  • Flexibility – Configurable settings, multiple stages, and SCADA communication
  • Retrofit – Adds protection without replacing existing inverters
  • Multi-inverter systems – Single relay coordinates protection at PCC
System SizeRecommended Approach
Small residential/commercialInverter-integrated protection
Large commercial / industrialExternal relay recommended
Utility-scale / criticalCoordinated scheme with redundancy

Differences Between Active Anti-Islanding Protection and Passive Anti-Islanding Protection

Comparison DimensionPassive Anti-Islanding DetectionActive Anti-Islanding Detection
Basic PrincipleReal-time monitoring of grid parameters including voltage, frequency and phase. Islanding is identified once parameters deviate from normal thresholds (over/undervoltage, over/underfrequency).The inverter continuously injects minor disturbance signals (frequency drift, reactive power perturbation) into the grid and monitors system feedback. Disturbances are absorbed by the bulk grid under grid-tied status; once islanding occurs, accumulated disturbances push parameters out of limits to detect islanding.
Impact on Power GridZero impact; no active interfering signals injected.Minor adverse impact; intentional injected perturbations may slightly degrade power quality.
Non-Detection Zone (NDZ)Wide NDZ. When distributed generation output precisely matches local load, voltage and frequency remain stable without triggering protection, resulting in detection failure.Narrow or negligible NDZ. Active disturbances inevitably shift operating parameters after island formation, effectively eliminating blind zones under power balance conditions.
ReliabilityRelatively low. Prone to maloperation caused by inherent grid fluctuations and load switching.Higher reliability. However, simultaneous active perturbation from multiple inverters may interfere with each other (dilution effect) and weaken detection performance.

Solar Anti-Islanding Protection Standards

Three separate things are being set here. How islanding performance has to be tested, how fast the plant must disconnect, and which grid support functions stay enabled before the disconnect is allowed. The first is IEC 62116. The second and third come from the interconnection standard or the regional grid code.

IEC 62116

IEC 62116 defines the test procedure for evaluating islanding prevention measures in PV inverters.

Key Requirements:

  • Standardized and repeatable test procedure for anti-islanding performance
  • Inverter must disconnect within 2 seconds after islanding detection
  • Applicable to single-phase and multi-phase PV inverters
  • Inverters that clear the test are classed as non-islanding under IEC 61727

Scope: IEC 62116 is a test procedure standard, not a protection function standard. It defines how to test anti-islanding performance.

IEEE 1547

IEEE 1547 is the U.S. standard for interconnecting distributed energy resources (DER) with electric power systems (2018 revision).

Key Requirements:

  • Distributed resources must detect islanding and disconnect within 2 seconds of formation
  • Voltage and frequency support required (not just disconnect)
  • IEEE 1547.1 defines conformance test procedures

Additional Certifications:

  • UL 1741: product safety certification
  • UL 1741 SA: smart inverter functions such as voltage and frequency ride-through

Regional Grid Codes

Regional grid codes reference IEC 62116 or IEEE 1547 while setting region-specific thresholds and trip times.

CodeRegionScopeKey Requirement
G98UK≤16A per phase (≤3.68kW)Self-certification; BS EN 62116 referenced
G99UK>16A per phaseEngineering assessment; DNO approval; witnessed FAT
VDE-AR-N-4105GermanyDER interconnectionAnti-islanding mandatory
AS/NZS IEC 62116Australia/New ZealandAdopted from IECSame as IEC 62116
GSO IEC 62116Gulf StatesAdopted by endorsementSame as IEC 62116

Note: CE marking and UL listing are product safety certifications, not anti-islanding test standards. They may reference relevant standards but do not define test procedures for islanding prevention.

Standards at a Glance

StandardScopeKey RequirementRegion
IEC 62116Test procedure2s disconnect; standardized testInternational
IEEE 1547Interconnection standard2s disconnect; ride-through (2018)USA
UL 1741/SAProduct safety certificationSafety listing; smart inverterUSA
G98Small generationSelf-certification; BS EN 62116UK
G99Generation >16AEngineering assessment; DNO approvalUK
VDE-AR-N-4105Grid interconnectionAnti-islanding mandatoryGermany

For project-specific anti-islanding compliance, consult applicable grid codes. The ASF-441H is type-tested to IEC 62116 and IEEE 1547, with regional settings configurable for G98/G99 and other grid code requirements.

Solar Anti-Islanding Protection Standards Comparison

Standard / RequirementMain FocusTypical Application
IEC 62116PV anti-islanding test procedurePV inverters
IEEE 1547DER interconnection requirementsNorth America
G98/G99UK distributed generation requirementsUK
Local Grid CodeUtility-specific requirementsProject dependent

Applicable requirements depend on the country, utility and connection level.

Core Functions of Anti-Island Protection Devices

Anti-islanding protection devices put microcomputer protection in a single box. Where an older panel needed five or six single-function relays, one unit now handles the monitoring, the islanding judgement, the breaker control and the talk-back to SCADA.

They run passive and active detection side by side. Neither one alone is enough: passive detection leaves a blind spot when load and generation match, and active detection weakens when several inverters perturb at the same moment. Their core functions are listed below.

Real-Time Grid Parameter Monitoring

The relay samples the electrical parameters at the coupling point continuously: grid voltage, frequency, phase angle, impedance, and the active and reactive balance between generation and load.

That stream is what exposes islanding at all. Under a power imbalance the frequency starts to run away, and a ROCOF setting picks the event up before a plain over/underfrequency threshold would.

Intelligent Islanding Fault Identification

Two detection mechanisms run side by side. Passive detection waits for voltage and frequency to move past a threshold. Active detection adds a disturbance signal, which finds the islanding conditions passive detection misses because load and generation are still balanced.

The other half of the job is telling islanding apart from a normal load step. Comparing the measured swing against the set thresholds and holding the trip output until the pattern matches is what keeps a large motor start from being read as a lost grid.

Millisecond-Level Fault Tripping Protection

Once an islanding state is confirmed, the relay drives its trip output and the PCC breaker opens. Device output is typically 200 ms or less, comfortably inside the 2 s window IEEE 1547-2018 allows, and the breaker adds another 30 to 50 ms on top. The line is dead well before a lineman arrives.

Overvoltage and Undervoltage, Overfrequency and Underfrequency Protection

These are the same ANSI 27, 59, 81U and 81O functions an anti-islanding relay already measures, so they arrive with the device. If voltage or frequency leaves its safe band because of a fault elsewhere on the network, the relay trips on that condition as well, which stops the island from driving an already weak network further out of limit.

Fault Recording & Remote Communication

The relay stores fault time, fault type and the recorded parameter set, which is what you need when a warranty claim six months later has to be answered with evidence. Communication runs over RS485, MODBUS and Ethernet, so an operator can read measurements, change settings and pull records into a SCADA master without going to the site.

Automatic Reset & Grid Reconnection

After the utility supply returns and the measured values settle back inside their normal band, the relay can reset itself or wait for an operator. Automatic reclose suits an unattended plant. A manual reset is the safer choice where closing onto a still-faulty network would cost more than a night of downtime.

How to Install Solar Anti-Islanding Protection

Anti-islanding relay wiring: current transformers on the grid side of the PCC

Most islanding failures traced after handover are installation faults, not setting faults. The steps below cover an external relay such as the ASF-441H. The wider picture of relay protection for PV power systems is written up separately.

Protection Point and PCC

Install the relay at the Point of Common Coupling (PCC)  the interface where the PV system connects to the utility grid, typically in the main AC distribution panel or interconnection switchgear.

Key Points: Locate close to PCC; 144×144mm panel cutout; clear labeling; accessible for inspection; IP rating per site conditions.

Voltage and Current Inputs

Connect grid-side voltage and current signals to the relay.

Voltage: Connect to grid side of main breaker (100V/220V/400V selectable); verify phase sequence and polarity.

Current: CTs on grid side of PCC; CT ratio must match relay (1A or 5A); verify polarity (S1 towards source).

Important: CTs must be on the grid side of PCC, not inverter side.

Trip Output to Circuit Breaker

The relay trips the circuit breaker at the PCC when protection conditions are detected.

  • Connect relay trip output (NO contact) to breaker trip coil
  • Trip circuit must be independently powered
  • Verify trip time <50ms
  • Include trip circuit supervision if required

Auxiliary Power

The relay requires a stable auxiliary supply.

ParameterRequirement
Voltage110V DC / 220V DC / 220V AC (selectable)
Consumption<20W
SourceGrid side of PCC
BackupUPS recommended for critical installations

Protection Parameter Configuration

Configure parameters per project protection study and grid code.

ParameterTypical Range
Undervoltage (27)70-90% Un
Overvoltage (59)110-120% Un
Underfrequency (81U)47-49.5Hz
Overfrequency (81O)50.5-52Hz
ROCOF (81R)0.5-1.0 Hz/s
Reverse Power (32R)1-5% of rated power

Steps: Set CT/PT ratios → Configure each function → Program I/O → Set communication → Save backup.

Commissioning and Functional Testing

ASF-441H anti-islanding protection relay in a protection cabinet

1. Pre-Energization Checks

  • Verify wiring, CT polarity, CT ratio, and auxiliary power

2. Power-Up Verification

  • Confirm relay boots, display reads correctly, communication works

3. Secondary Injection Testing

  • Inject test signals to verify each protection function trips at correct threshold
  • Test trip output to breaker

4. Live Commissioning

  • Verify relay readings match actual system values
  • Simulate grid loss (if permitted) to confirm trip time

Acceptance: All functions within accuracy; trip times meet grid code; communication functional; settings documented.

For installation support, commissioning guidance, and setting calculations, contact Autony.

Anti-Islanding Protection Relays from the Manufacturer

Autony builds anti-islanding protection relays for grid-connected solar PV and distributed generation, together with the 400 V relay family that pairs with them.

The ASF-441H is a microprocessor-based relay that detects islanding and the other abnormal grid conditions around it, then opens the PCC unless IEC 62116 and IEEE 1547 say otherwise.

Two devices cover most PV interconnects. The 400 V anti-islanding protection relay fits a low-voltage distribution board. The ASF-441H takes ANSI 27, 59, 81U, 81O, 81R and 32R in one case, which is what medium-voltage or large low-voltage plants ask for.

FAQ: Anti-Islanding Protection Questions for Solar PV

Q1. What is anti-islanding protection in a solar PV system?

A:It ensures the PV system stops feeding power to the grid when the utility is de-energized, preventing energized islands that pose electrocution risks and equipment hazards.

Q2. Why is anti-islanding protection important for grid-connected PV?

A:It protects utility workers from electrocution, prevents equipment damage from unstable voltage/frequency, and is required by international grid interconnection standards.

Q3. What is the difference between inverter anti-islanding protection and an external anti-islanding protection relay?

A:Inverter protection is built-in and suits small systems. An external relay (e.g., ASF-441H) provides independent, configurable backup protection at the PCC for larger commercial or utility-scale systems.

Q4. What is the difference between active and passive anti-islanding detection?

A:Passive monitors voltage/frequency without injecting disturbances. Active injects small perturbations, in an island, disturbances amplify and trigger protection.

Q5. What is the non-detection zone (NDZ)?

A:A condition where passive methods cannot detect islanding because load and generation are closely matched, keeping voltage/frequency stable. Active methods minimize or eliminate NDZ.

Q6. What standards are used for PV anti-islanding testing?

A:IEC 62116 (test procedure), IEEE 1547 (2s disconnection), and regional codes like UK G98/G99 and VDE-AR-N-4105.

Q7. Where should an external anti-islanding protection device be installed?

A:At the Point of Common Coupling (PCC), between the PV system and the utility grid, typically in the AC distribution panel or interconnection switchgear.

Q8. Can an anti-islanding relay be used as backup protection for a PV inverter?

A:Yes. It provides independent backup if inverter protection fails, often required by utilities for larger installations to ensure redundancy.

Q9. How is anti-islanding protection tested during commissioning?

A:Through pre-energization checks, secondary injection testing to verify protection thresholds, and live functional testing to confirm disconnection within required time.

Q10. How do I select an anti-islanding protection relay for a solar PV project?

A:Small systems: inverter-integrated protection is sufficient. Large commercial/utility-scale: external relay with configurable functions and communication is recommended per grid code requirements.

Conclusion

Solar anti-islanding protection is a grid-code obligation, not an upgrade you can defer to phase two. Small arrays are covered by inverter firmware. Commercial and industrial plants need an anti-islanding relay at the PCC. Utility-scale sites usually run both, with the inverter and the relay watching each other.

Three checks decide whether an installation will hold up under audit. The current transformers sit on the grid side of the PCC, the plant passes the IEC 62116 islanding test at the settings it will actually run, and the disconnect lands inside the 2 s window that IEEE 1547-2018 allows.

Field record

Anti-islanding is a grid-connection requirement, not a relay preference. The PV reference in our record is a 3 MW rooftop plant in Hebei that needed joint commissioning with two dispatch centres before it could export. The same requirement applies to the LV reverse power installation in Sri Lanka, which is described separately on this site. The project record gives the voltage band and plant type for each country.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.