Send an Inquiry
star-star transformer differential protection

Differential Protection for Star-Star Transformer (Y-Y): Zero-Sequence and Tertiary Effects

Table of Contents

How does differential protection work for a star-star transformer?

Differential protection for a star-star transformer compares the compensated currents on the two sides of the transformer to detect faults within the protected zone. Although both windings use star connections, the scheme still requires careful attention to CT ratio, polarity, phase relationship, zero-sequence current and relay compensation. In traditional schemes CT connections supply phase and zero-sequence compensation, while modern numerical 87T relays perform those functions internally. Under normal load and external faults the two primary currents are related by the transformer turns ratio, so after CT ratios scale them to a common base, any significant difference indicates an internal fault. For a Yy0 vector group there is no phase displacement, which removes the need for phase correction; other groups introduce displacement that must be compensated. Function numbers follow ANSI/IEEE C37.2, differential relays IEC 60255-187-1 and transformers IEC 60076-1. Setting review and quotation within 12 hours, MOQ 1, 7-15 working days.

Introduction

Differential protection for a star-star (Y-Y) transformer compares the compensated currents on the two sides of the transformer to detect faults within the protected zone.

Written by Leon Zhang, Protection Application Engineer · Technical review by the relayprotect.com engineering team · Last reviewed September 2026

Although both transformer windings use star connections, the protection scheme still requires careful consideration of CT ratio, polarity, phase relationship, zero-sequence current and relay compensation. In traditional schemes, CT connections may be used for phase and zero-sequence compensation, while modern numerical 87T relays can perform many compensation functions internally.

This guide covers star-star transformer differential protection in practice: operating principle, CT arrangement, zero-sequence paths, tertiary winding effects, compensation methods and fault behavior. Each section states the condition under which a connection or setting holds, because most Y-Y misoperations trace back to an assumption nobody wrote down.

What Is a Star-Star (Y-Y) Transformer?

A star-star (Y-Y) transformer has both the HV and LV windings connected in a star (wye) configuration.

star-star transformer differential protection

Key Characteristics:

  • HV and LV Windings – Both are star-connected, with accessible neutral points on each side
  • Phase Displacement – Depends on the vector group (e.g., Yy0 has 0°; Yy6 has 180°)
  • Grounding – Each neutral can be grounded, impedance-grounded, or left floating based on system requirements
  • Zero-Sequence Behavior – Zero-sequence currents flow when the neutral is grounded. This affects differential protection, as zero-sequence may appear on one side and not the other, requiring compensation

Selecting a relay for a live project?

Send the system voltage, CT ratio and tripping scheme. Our engineers confirm the model and reply within 12 hours.

View relay modelsRequest a quote

This configuration is common in transmission and distribution systems. Understanding Y-Y characteristics is essential for correct CT connections, phase compensation, and zero-sequence treatment in differential protection applications.

How Differential Protection Works for a Star-Star Transformer

For a star-star (Y-Y) transformer, the differential protection principle remains the same as for other transformer types: currents entering and leaving the protected zone are compared. However, the Y-Y configuration presents specific considerations that affect how the protection is applied.

Current Comparison on HV and LV Sides

The relay measures currents from CTs installed on both the HV and LV sides. Under normal load and external fault conditions, the primary currents on both sides are related by the transformer turns ratio. The relay compares these currents after compensation. Any significant difference indicates an internal fault.

CT Ratio Matching

CT ratios on the HV and LV sides must be selected to produce secondary currents that are proportional to the primary currents. Because the HV and LV currents differ according to the transformer voltage ratio, the CT ratios are typically different. The relay must be configured with the correct CT ratios to properly scale the secondary currents before comparison.

Phase Shift Between HV and LV Currents

In a Y-Y transformer, the phase relationship between HV and LV currents depends on the vector group. For a Yy0 vector group, there is no phase displacement between HV and LV voltages. This simplifies the phase compensation, as no phase correction is required for the currents. However, other vector groups may introduce phase displacement that must be compensated.

Differential Current

The differential current is the vector difference between the compensated currents from both sides. Under normal conditions, this value is near zero. Under internal faults, the differential current increases and initiates the tripping logic.

Restraint Current

Restraint current is derived from the through-current and is used to stabilize the relay during external faults. In a Y-Y transformer, the restraint current is calculated from the compensated currents. As the through-current increases, the operating threshold rises, ensuring stability even when CT errors or saturation produce residual differential currents.

Protection Signal Flow

Differential current comparison between the HV and LV sides of a Y-Y transformer (illustrative)

The relay compares the compensated currents rather than simply comparing the raw CT secondary currents. This compensation accounts for differences in CT ratios, transformer turns ratio, and vector group phase displacement, ensuring that the relay sees balanced currents under normal conditions and responds only to actual internal faults.

CT Connections for Star-Star Transformer Differential Protection

CT wiring is where a Y-Y scheme is really decided. Both families below follow the same transformer differential protection working principle, but they put the compensation in different hardware. For schemes outside transformers, see differential relay protection.

Traditional Electromechanical / Static Relay Schemes

In traditional electromechanical or static relay schemes, CTs on both sides of a Y-Y transformer are typically connected in delta on the secondary side. This delta connection provides a path for zero-sequence currents to circulate within the CT secondary loop, preventing them from reaching the relay. It also introduces a phase shift that may require additional compensation. This approach requires careful CT wiring and offers limited flexibility.

Numerical 87T Relay Schemes

Modern numerical relays simplify CT connections . CTs on both sides are typically connected in star (wye) directly to the relay inputs. Phase compensation and zero-sequence removal are performed internally by the relay software through configurable settings. No external delta connections or interposing CTs are required, reducing wiring complexity and improving flexibility.

Traditional vs Numerical

FunctionTraditional Differential SchemeNumerical 87T Relay
Phase compensationOften through CT connectionsOften performed internally
CT secondary connectionScheme-dependentRelay-specific
Ratio compensationCT ratio / auxiliary CTRelay configuration
Vector compensationExternal connectionSoftware / configuration
Zero-sequence compensationCircuit design dependentOften configurable
Setting flexibilityLimitedHigh

Zero-Sequence Current in Star-Star Transformer Differential Protection

Zero-sequence is where star-star transformer differential protection differs most from the Y-Δ case, and where most external-fault misoperations begin.

What Is Zero-Sequence Current?

Zero-sequence current is the current that flows during a ground fault in a system with a grounded neutral. It represents the unbalanced current returning through the neutral path.

Zero-sequence current returning through a grounded transformer neutral (illustrative)

Why Does It Matter in a Y-Y Transformer?

In a Y-Y transformer, zero-sequence behavior depends on multiple factors: neutral grounding, transformer construction, system grounding, and relay compensation. This makes Y-Y transformers more complex to protect than other configurations.

Ground Fault Behavior

  • With a grounded neutral, zero-sequence current can flow and appears in phase currents
  • With an ungrounded neutral, zero-sequence current cannot flow
  • If only one neutral is grounded, zero-sequence appears on that side only, creating an apparent differential current

87T Zero-Sequence Correction

Correction is required when zero-sequence appears on one side but not the other. The relay has to remove it before the comparison, or the differential element reads a ground fault that is outside the zone.

  • Traditional schemes – Delta-connected CT secondaries trap zero-sequence current in the loop so it never reaches the relay
  • Numerical relays – 87T zero-sequence correction happens inside the relay: each winding is declared grounded or not, and the algorithm subtracts the zero-sequence component accordingly

The setting that decides this is not the differential one. On most numerical relays it sits in the transformer data or winding configuration menu. Enter it wrong and the element behaves as if the neutral were floating.

Effect of Transformer Neutral Grounding

Grounding ConditionZero-Sequence Behavior
Both neutrals groundedMay appear on both sides; compensation may be required
One neutral groundedAppears only on grounded side; compensation required
Neither neutral groundedNo zero-sequence flow (unless external system provides path)

Zero-Sequence Is Not Blocked by the Winding Alone

Zero-sequence behavior in a Y-Y transformer is not determined solely by winding connection. It depends on neutral grounding, transformer construction, system grounding, and relay compensation. Do not assume that a Y-Y transformer always blocks zero-sequence current.

Tertiary Winding and the Zero-Sequence Path

A Y-Y transformer with both neutrals grounded and no closed delta path leaves zero-sequence current nowhere to circulate. A buried delta tertiary fixes that, and it changes what the 87T sees while it does.

What a Delta Tertiary Does

The tertiary is a third winding, usually rated at roughly one third of the main winding rating, connected in delta and brought out only when it feeds station load or a compensating device. Read the figure from the nameplate rather than assuming it. In normal operation it carries little load current, so its contribution to the differential calculation is small. Its job is to give zero-sequence and third-harmonic currents a closed path that does not involve the neutral.

Two consequences follow. A ground fault on one side no longer drives the same zero-sequence current through both CT sets, so much of the apparent differential current a floating Y-Y produces simply disappears. And the tertiary itself becomes something that can fault.

Tertiary Winding Differential Protection

Tertiary winding differential protection treats the delta tertiary as a third input to the same 87T relay, or as a separate zone where the tertiary supplies reactive compensation or station service. Adding it means three current sets have to be matched, which raises the burden on ratio and phase compensation but closes the blind spot at the tertiary.

Where the tertiary is left unwired and unmonitored, a fault inside it is seen only indirectly, through the differential current it drives into the main windings. That is often enough for a solid internal fault, and rarely enough for a low-current turn-to-turn fault. Ask the vendor whether the third input is rated for the tertiary CT class before assuming it can be used.

When There Is No Tertiary

Most distribution Y-Y transformers have no tertiary. The zero-sequence problem is then solved outside the transformer:

  • Leave one neutral ungrounded – zero-sequence current cannot flow, so no correction is needed, at the cost of ground-fault sensitivity on that side
  • Filter inside the relay – a numerical relay removes the zero-sequence component from each side before the comparison, the usual choice when both neutrals are grounded
  • Use a separate ground-fault element – restricted earth fault or neutral overcurrent covers what the differential element cannot see

Whichever route is taken, record it. A scheme that balances on the drawing can still misoperate on an external ground fault if the neutral grounding was changed on site.

Star-Star Transformer Fault Behavior

The table is an acceptance view: for each condition, what the relay should do.

Fault ConditionExpected 87T Behavior
Normal loadStable
External phase faultRestrained
External ground faultNormally stable depending on scheme
Internal phase faultOperates
Internal ground faultOperates if within protection zone
Transformer energizationHarmonic restraint may prevent unwanted trip

Why Compensation Is Important in Y-Y Transformer Differential Protection

Compensation is essential to ensure the relay correctly compares currents from both sides. Without it, the relay may see an apparent differential current under normal conditions. Three key factors make compensation necessary:

CT Ratio Difference

HV and LV currents differ due to different voltage levels. CT ratios are selected accordingly, but the secondary currents are not directly comparable. Compensation scales them to a common reference.

Transformer Ratio

The transformer turns ratio must be accounted for to normalize currents. Without compensation, the relay compares currents of different magnitudes, resulting in persistent differential current.

Why Phase Alignment Matters

The phase relationship between HV and LV currents depends on the vector group. Without proper compensation, currents are not aligned and differential calculation becomes incorrect.

Compensation Methods

  • Traditional schemes – Achieved through CT secondary connections (e.g., delta connections)
  • Numerical 87T relays – Performed internally via software settings, reducing wiring complexity

Testing Considerations for Y-Y Transformer Differential Protection

Test procedures for this family sit under transformer differential protection testing. On a Y-Y unit, the checks below carry most of the risk:

  • CT ratio and polarity – Confirm ratios match nameplate ratings and polarity connections are correct
  • Phase relationship – Verify phase alignment between HV and LV currents per transformer vector group
  • Relay compensation settings – Confirm CT ratio, vector group, and zero-sequence compensation are correctly configured
  • Pickup and bias characteristic – Verify relay operates at set pickup and follows defined bias slope
  • Trip logic – Verify trip contacts, alarms, and interlocking functions operate correctly

Testing should include both secondary injection (relay internal functions) and primary injection (complete CT-to-relay path) per site commissioning procedures.

Common Problems in Star-Star Transformer Differential Protection

These are the symptoms that reach the commissioning team, and the measurement that settles each one.

SymptomMost likely causeMeasurement that settles it
Differential current during normal loadCT ratio mismatchCompare each secondary current against the calculated ratio
Trip on energisationSecond-harmonic restraint not enabledRead the inrush blocking setting and the recorded harmonic ratio
Trip on an external faultCT polarity error or CT saturationCheck polarity at the relay terminals; confirm the CT class for the fault level
Instability on an external ground faultZero-sequence not removedConfirm the grounding as built, then the winding configuration setting
Persistent phase current mismatchWrong vector group or phase compensationCompare the relay reading with the nameplate vector group
No operation on an internal faultTrip circuit or relay configurationInject secondary current and confirm pickup and trip contacts
Low-level differential current at all loadsSecondary wiring or CT burdenInsulation and loop resistance test on each CT circuit

Star-Star vs Star-Delta Transformer Differential Protection

The two families differ in where the phase shift comes from and what the delta winding does to zero-sequence. The star-delta transformer differential protection case has its own page; the table is the short version.

FeatureY-Y TransformerY-Delta Transformer
Phase shift between windings0° for Yy0, 180° for Yy630° steps, e.g. 30° at clock 11
CT phase compensationNone for Yy0; 180° reversal for Yy6Required on one side for any Dyn group
Zero-sequence at the relayDepends on which neutrals are groundedBlocked by the delta winding
Zero-sequence correction settingUsually needed on both windingsSet on the star side only
Closed path for zero-sequenceOnly if a delta tertiary is fittedProvided by the LV delta winding
Most common setting errorZero-sequence left in the comparisonWrong vector group entered
First check on siteNeutral grounding as actually builtVector group on the nameplate

Conclusion

Star-star transformer differential protection looks simpler than the Y-Delta case, and in two respects it is. There is no fixed 30° shift, and phase compensation often reduces to nothing. The complication moves to zero-sequence.

Three checks cover most field failures. Confirm CT ratios and polarity against the nameplate. Confirm that zero-sequence is either blocked or removed on both sides. Confirm that the tertiary, if fitted, sits inside a monitored zone. Get those right and the bias characteristic does the rest.

For the relay end of this work, see the transformer differential protection relay range, which accepts configurable vector group and zero-sequence settings for Y-Y and Y-Δ applications.

References

SourceWhat it coversTypeEdition
IEC 60076-1Power transformers – general; vector groups and phase displacementStandard2011
IEC 60255-187-1Measuring relays – functional requirements for differential protectionStandard2021
IEEE C37.91Guide for protective relay applications to power transformersGuide2021
ANSI/IEEE C37.2Electrical power system device function numbers (87T)Standard2022
IEC 60255-1Measuring relays and protection equipment – common requirementsStandard2022

Star-Star (Y-Y) Transformer Differential Protection – Q&A

What is differential protection for a star-star transformer?

It is a protection scheme that compares currents entering and leaving a Y-Y transformer to detect internal winding faults. The relay monitors the current balance between HV and LV sides and trips when an imbalance indicates a fault.

How does differential protection work for a Y-Y transformer?

The relay measures currents on both sides, compensates for CT ratio and transformer ratio differences, and aligns phase relationships according to the vector group. Under normal conditions, compensated currents balance. Internal faults create differential current and trigger tripping.

What CT connection is used for a star-star transformer differential protection?

The required CT connection depends on the protection scheme and relay design. Traditional schemes may use CT secondary connections for phase compensation, while modern numerical relays can perform compensation internally.

Does a Y-Y transformer require phase compensation?

Yes. Phase compensation is required to align HV and LV currents according to the transformer vector group. Without it, the relay may see incorrect differential current even under normal load.

How does zero-sequence current affect Y-Y transformer differential protection?

Zero-sequence current can appear on one side of a Y-Y transformer and not the other, depending on neutral grounding. This creates an apparent differential current that must be compensated to prevent misoperation.

Why is CT polarity important for Y-Y transformer differential protection?

CT polarity ensures that currents from both sides are correctly oriented for differential calculation. Reversed polarity causes a persistent differential current, leading to possible false tripping.

Can a numerical 87T relay be used for a Y-Y transformer?

Yes. Numerical 87T relays are suitable for Y-Y transformers. They perform phase compensation, CT ratio matching, and zero-sequence compensation internally through configurable software settings.

What causes false differential current in a Y-Y transformer?

Common causes include CT ratio mismatch, CT polarity errors, incorrect vector group or compensation settings, CT saturation, and zero-sequence current effects without proper compensation.

What is the difference between Y-Y and Y-Delta transformer differential protection?

The main difference lies in zero-sequence behavior and compensation requirements. Y-Y transformers may have zero-sequence current on one side depending on neutral grounding, requiring specific compensation. Y-Delta transformers have delta winding that traps zero-sequence current, simplifying compensation.

How is star-star transformer differential protection tested?

Testing includes CT ratio and polarity checks, secondary injection tests for pickup and slope, harmonic restraint verification, and primary injection tests to validate the complete protection path from CTs to relay.

Send the nameplate data if you want the settings checked before the panel is built.

About Author
Leon Zhang
Hello, I'm Leon Zhang. I have 15 years of experience in the power relay protection industry with extensive pre-sales and after-sales project experience. Our company specializes in various complete sets of relay protection and automation equipment. I can assist customers in solving all practical on-site project challenges and provide optimal integrated solutions.
Tell Us Your Requirement
Send an Inquiry

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.