Description
Overview
- The ASD-441H Motor protection relay is primarily designed to protect motors.It is suitable for high-voltage motors in 3 kV to 35 kV systems,
and serves as bay-level equipment, performing protection, measurement, control, and communication functions.
Product Functions (ANSI)
- Instantaneous Overcurrent Protection 50
- Definite Time Overcurrent & Negative Sequence Overcurrent Protection 51 / 46
- Inverse Time Overcurrent & Inverse Time Negative Sequence Current Protection 51 / 46
- Negative Phase Sequence Voltage Protection 47
- Locked Rotor Protection: Start Locked Rotor & Running Locked Rotor Protection 48
- Thermal Overload Protection 49
- Undervoltage Protection 27
- Overload Protection 51 / 49
- Zero-sequence Overcurrent Protection 50N / 51N
- Overvoltage Protection 59
- Long Start Time Protection / Start Supervision 66
- VT & CT Disconnection Supervision 60
- Control Circuit Break Monitoring 74
Communication Mode
- Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)
Main Functional Specifications
- Protection response time (including the response time of the output relay): Average error in response time: not more than 35 ms;
- Precision operating range: Minimum precision current: 0.08 In, Maximum precision current: 20 In
- Current setting error: When the current exceeds 1.00 A, the error shall not exceed ±2.5%; Voltage setting error: shall not exceed ±3%
- Measurement accuracy: Current (I)/Voltage (U): Class 0.2; Power (P)/Reactive power (Q): Class 0.5
- Remote signal resolution: no more than 2 ms
Event Logging, Fault Recording
- The recorded events include protective action events and device malfunctions;
- Record the type of protection trip, the time of the trip, and the operating parameters at the time of the trip;
- The fault recording data includes: the time of the protection operation, the type of protection operation, and the rms values before and after the recording was initiated;
- Data length of the fault recording: 2 cycles before the fault and 4 cycles after the fault;
- The SOE can retain 48 sets of data after a power loss, and the fault report can retain 16 sets of data after a power loss.
Monitoring Features
- The device is capable of measuring analog quantities such as current, voltage, and frequency;
- Collect position signals from circuit breakers, energy storage systems, isolating switches, and remote/local control switches, as well as other digital signals;
- Control functions of the disconnect switch.
Setting Table
| No. | Display Name | Range | Step | Remark |
|---|---|---|---|---|
| 1 | Instantaneous Overcurrent Protection Setting | |||
| 1.1 | Instantaneous Overcurrent Enable | 1/0 | — | Instantaneous overcurrent: Enable(1)/Disable(0) |
| 1.2 | Instantaneous Time Delay | 0.00~120.00s | 0.01s | |
| 1.3 | Startup Setting Current | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 1.4 | Running Setting Current | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 2 | Overcurrent Protection Setting | |||
| 2.1 | Overcurrent Protection Enable | 1/0 | — | Overcurrent protection: Enable(1)/Disable(0) |
| 2.2 | Overcurrent Time Delay | 0.00~120.00s | 0.01s | |
| 2.3 | Overcurrent Setting Value | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 3 | Negative Sequence Overcurrent Setting | |||
| 3.1 | Negative Sequence Overcurrent Enable | 1/0 | — | Negative sequence overcurrent: Enable(1)/Disable(0) |
| 3.2 | Overcurrent Time Delay | 0.00~120.00s | 0.01s | |
| 3.3 | Overcurrent Setting Value | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=5A In=1A |
| 4 | Inverse Time Overcurrent Setting | |||
| 4.1 | Inverse Time Overcurrent Enable | 1/0 | — | Inverse time overcurrent: Enable(1)/Disable(0) |
| 4.2 | Time Constant | 1.00~100.00s | 0.01s | Time constant for inverse time overcurrent |
| 4.3 | Inverse Time Current I | 0.50~10.00A
0.20~2.00A |
0.01A | In=5A
In=1A |
| 5 | Negative Sequence Inverse Time Setting | |||
| 5.1 | Negative Sequence Inverse Time Enable | 1/0 | — | Negative sequence inverse time: Enable(1)/Disable(0) |
| 5.2 | Inverse Time Constant T | 1.00~100.00s | 0.01s | Time constant for negative sequence inverse time |
| 5.3 | Inverse Time Current I | 0.10~10.00A
0.20~2.00A |
0.01A | In=5A
In=1A |
| 6 | Negative Phase Sequence Voltage Setting | |||
| 6.1 | Negative Phase Sequence Voltage Enable | 1/0 | — | Negative phase sequence voltage: Enable(1)/Disable(0) |
| 6.2 | Negative Phase Sequence Time Delay | 0.10~120.00s | 0.01s | Time delay of negative phase sequence voltage protection |
| 7 | Long Startup Time Setting | |||
| 7.1 | Long Startup Time Protection | 1/0 | — | Trip on overtime startup: Enable(1)/Disable(0) |
| 7.2 | Startup Time Delay | 0.00~120.00s | 0.01s | Startup overtime time delay |
| 7.3 | Rated Current | 1.00~10.00A | 0.01A | |
| 7.4 | Current Threshold | 0.20~5.00A | 0.01A | |
| 8 | Start Locked Rotor Setting | |||
| 8.1 | Start Locked Rotor Enable | 1/0 | — | Start locked rotor protection: Enable(1)/Disable(0) |
| 8.2 | Locked Rotor Time Delay | 0.00~120.00s | 0.01s | |
| 8.3 | Locked Rotor Setting Current | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 9 | Running Locked Rotor Setting | |||
| 9.1 | Running Locked Rotor Enable | 1/0 | — | Running locked rotor protection: Enable(1)/Disable(0) |
| 9.2 | Locked Rotor Time Delay | 0.00~120.00s | 0.01s | |
| 9.3 | Locked Rotor Setting Current | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 10 | Thermal Protection Setting | |||
| 10.1 | Thermal Protection Enable | 1/0 | — | Thermal protection: Enable(1)/Disable(0) |
| 10.2 | Thermal Time Constant | 1.00~100.00s | 0.01s | Heating time constant of thermal protection |
| 10.3 | Alarm Coefficient | 0.10~0.80 | 0.01 | |
| 11 | Undervoltage Protection Setting | |||
| 11.1 | Undervoltage Protection Enable | 1/0 | — | Undervoltage protection: Enable(1)/Disable(0) |
| 11.2 | Undervoltage Trip Mode | 1/0 | — | 1=Trip, 0=Alarm |
| 11.3 | VT Disconnection Block Undervoltage | 1/0 | — | 1=Block, 0=Not block |
| 11.4 | Undervoltage Time Delay | 0.10~120.00s | 0.01s | |
| 11.5 | Undervoltage Setting Value | 5.00~100.00V | 0.01V | |
| 12 | Overload Protection Setting | |||
| 12.1 | Overload Protection Enable | 1/0 | — | Overload protection: Enable(1)/Disable(0) |
| 12.2 | Overload Trip Mode | 1/0 | — | 1=Trip, 0=Alarm |
| 12.3 | Overload Time Delay T | 0.00~120.00s | 0.01s | |
| 12.4 | Overload Current Setting | 0.10~99.99A
0.10~20.00A |
0.01A | In=5A
In=1A |
| 13 | Zero Sequence Overcurrent Setting | |||
| 13.1 | Zero Sequence Overcurrent Enable | 1/0 | — | Zero sequence overcurrent: Enable(1)/Disable(0) |
| 13.2 | Zero Sequence Trip Mode | 1/0 | — | 1=Trip, 0=Alarm |
| 13.3 | Zero Sequence Direction Block | 1/0 | — | Direction block function: Enable(1)/Disable(0) |
| 13.4 | Small Current Grounding Line Selection | 1/0 | — | Line selection: Enable(1)/Disable(0) |
| 13.5 | Line Selection Polarity Reverse | 1/0 | — | 1=Reverse polarity, 0=Positive polarity |
| 13.6 | Zero Sequence Time Delay | 0.00~120.00s | 0.01s | |
| 13.7 | Zero Sequence Current Setting | 0.10~5.00A
0.40~99.00A |
0.01A | Small current grounding system
380V 3-phase 4-wire grounding system |
| 14 | Overvoltage Protection Setting | |||
| 14.1 | Overvoltage Protection Enable | 1/0 | — | Overvoltage protection: Enable(1)/Disable(0) |
| 14.2 | Overvoltage Trip Mode | 1/0 | — | 1=Trip, 0=Alarm |
| 14.3 | Overvoltage Time Delay | 0.10~120.00s | 0.01s | |
| 14.4 | Overvoltage Setting Value | 20.00~120.00V | 0.01V | |
| 15 | Auto-restart Setting | |||
| 15.1 | C10 Auto-restart Function | 1/0 | — | C10 as auto-restart: Enable(1)/Disable(0) |
| 15.2 | Auto-restart Time Delay | 0.00~120.00s | 0.01s | |
| 16 | General Setting | |||
| 16.1 | VT Disconnection Alarm | 1/0 | — | VT disconnection alarm: Enable(1)/Disable(0) |
| 16.2 | CT Disconnection Alarm | 1/0 | — | CT disconnection alarm: Enable(1)/Disable(0) |
| 16.3 | CT Disconnection Block Negative Sequence | 1/0 | — | Block negative sequence on CT fault: Enable(1)/Disable(0) |
| 16.4 | Control Circuit Break Alarm | 1/0 | — | Control circuit break alarm: Enable(1)/Disable(0) |
| 16.5 | Current Block Over / Under Voltage | 1/0 | — | 1=Block, 0=Not block |
| 16.6 | Device Test Mode | 1/0 | — | 1=Test mode, 0=Normal mode |
| 16.7 | 3-Phase 4-Wire Voltage Wiring | 1/0 | — | 0=3P3W, 1=3P4W |
| 16.8 | Current Input 1A Rated | 1/0 | — | 1=1A input, 0=5A input |
| 16.9 | Rated Voltage 380V | 1/0 | — | 1=380V, 0=100V |
| 16.10 | B17 Maintenance Plate Function | 1/0 | — | 1=Maintenance plate, 0=Normal remote signal |
| 16.11 | Integral Energy Calculation | 1/0 | — | 1=Calculate, 0=Not calculate |
| 16.12 | Harmonic Component Calculation | 1/0 | — | 1=Calculate, 0=Not calculate |
| 16.13 | Current Block Threshold | 1.00~10.00A | 0.01A | |
| 16.14 | Sudden Change Startup Current | 1.00~10.00A | 0.01A |
Outline and Installation Dimensions

FAQ
Q:Motor protection relay is primarily designed to protect motors, so how should one choose one?
A:There are many types of motor protection relays, and several principles should be considered when selecting one.
First, motors are classified by voltage rating into low-voltage and high-voltage categories; different voltage ratings require different selection methods.
Second, consider the motor’s capacity; generally, motors with higher capacity have more stringent technical requirements.
Third, refer to the project’s technical specifications.










Reviews
There are no reviews yet.