ASD-441H Motor protection relay

The ASD-441H Motor protection relay is primarily designed to protect motors.It is suitable for high-voltage motors in 3 kV to 35 kV systems,
and serves as bay-level equipment, performing protection, measurement, control, and communication functions.

Product Functions (ANSI)

50/51/46/47/48/49/27/50N/51N/59/66/60/74

Communication Mode

Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)

In-house Factory & Technical Team, OEM ODM Custom Electrical Equipment

Description

Overview

  • The  ASD-441H Motor protection relay is primarily designed to protect motors.It is suitable for high-voltage motors in 3 kV to 35 kV systems,
    and serves as bay-level equipment, performing protection, measurement, control, and communication functions.

Product Functions (ANSI)

  • Instantaneous Overcurrent Protection 50
  • Definite Time Overcurrent & Negative Sequence Overcurrent Protection 51 / 46
  • Inverse Time Overcurrent & Inverse Time Negative Sequence Current Protection 51 / 46
  • Negative Phase Sequence Voltage Protection 47
  • Locked Rotor Protection: Start Locked Rotor & Running Locked Rotor Protection 48
  • Thermal Overload Protection 49
  • Undervoltage Protection 27
  • Overload Protection 51 / 49
  • Zero-sequence Overcurrent Protection 50N / 51N
  • Overvoltage Protection 59
  • Long Start Time Protection / Start Supervision 66
  • VT & CT Disconnection Supervision 60
  • Control Circuit Break Monitoring 74

Communication Mode

  • Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)

Main Functional Specifications

  • Protection response time (including the response time of the output relay): Average error in response time: not more than 35 ms;
  • Precision operating range: Minimum precision current: 0.08 In, Maximum precision current: 20 In
  • Current setting error: When the current exceeds 1.00 A, the error shall not exceed ±2.5%; Voltage setting error: shall not exceed ±3%
  • Measurement accuracy: Current (I)/Voltage (U): Class 0.2; Power (P)/Reactive power (Q): Class 0.5
  • Remote signal resolution: no more than 2 ms

Event Logging, Fault Recording

  • The recorded events include protective action events and device malfunctions;
  • Record the type of protection trip, the time of the trip, and the operating parameters at the time of the trip;
  • The fault recording data includes: the time of the protection operation, the type of protection operation, and the rms values before and after the recording was initiated;
  • Data length of the fault recording: 2 cycles before the fault and 4 cycles after the fault;
  • The SOE can retain 48 sets of data after a power loss, and the fault report can retain 16 sets of data after a power loss.

Monitoring Features

  • The device is capable of measuring analog quantities such as current, voltage, and frequency;
  • Collect position signals from circuit breakers, energy storage systems, isolating switches, and remote/local control switches, as well as other digital signals;
  • Control functions of the disconnect switch.

Setting Table

No. Display Name Range Step Remark
1 Instantaneous Overcurrent Protection Setting
1.1 Instantaneous Overcurrent Enable 1/0 Instantaneous overcurrent: Enable(1)/Disable(0)
1.2 Instantaneous Time Delay 0.00~120.00s 0.01s
1.3 Startup Setting Current 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

1.4 Running Setting Current 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

2 Overcurrent Protection Setting
2.1 Overcurrent Protection Enable 1/0 Overcurrent protection: Enable(1)/Disable(0)
2.2 Overcurrent Time Delay 0.00~120.00s 0.01s
2.3 Overcurrent Setting Value 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

3 Negative Sequence Overcurrent Setting
3.1 Negative Sequence Overcurrent Enable 1/0 Negative sequence overcurrent: Enable(1)/Disable(0)
3.2 Overcurrent Time Delay 0.00~120.00s 0.01s
3.3 Overcurrent Setting Value 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=5A

In=1A

4 Inverse Time Overcurrent Setting
4.1 Inverse Time Overcurrent Enable 1/0 Inverse time overcurrent: Enable(1)/Disable(0)
4.2 Time Constant 1.00~100.00s 0.01s Time constant for inverse time overcurrent
4.3 Inverse Time Current I 0.50~10.00A

0.20~2.00A

0.01A In=5A

In=1A

5 Negative Sequence Inverse Time Setting
5.1 Negative Sequence Inverse Time Enable 1/0 Negative sequence inverse time: Enable(1)/Disable(0)
5.2 Inverse Time Constant T 1.00~100.00s 0.01s Time constant for negative sequence inverse time
5.3 Inverse Time Current I 0.10~10.00A

0.20~2.00A

0.01A In=5A

In=1A

6 Negative Phase Sequence Voltage Setting
6.1 Negative Phase Sequence Voltage Enable 1/0 Negative phase sequence voltage: Enable(1)/Disable(0)
6.2 Negative Phase Sequence Time Delay 0.10~120.00s 0.01s Time delay of negative phase sequence voltage protection
7 Long Startup Time Setting
7.1 Long Startup Time Protection 1/0 Trip on overtime startup: Enable(1)/Disable(0)
7.2 Startup Time Delay 0.00~120.00s 0.01s Startup overtime time delay
7.3 Rated Current 1.00~10.00A 0.01A
7.4 Current Threshold 0.20~5.00A 0.01A
8 Start Locked Rotor Setting
8.1 Start Locked Rotor Enable 1/0 Start locked rotor protection: Enable(1)/Disable(0)
8.2 Locked Rotor Time Delay 0.00~120.00s 0.01s
8.3 Locked Rotor Setting Current 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

9 Running Locked Rotor Setting
9.1 Running Locked Rotor Enable 1/0 Running locked rotor protection: Enable(1)/Disable(0)
9.2 Locked Rotor Time Delay 0.00~120.00s 0.01s
9.3 Locked Rotor Setting Current 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

10 Thermal Protection Setting
10.1 Thermal Protection Enable 1/0 Thermal protection: Enable(1)/Disable(0)
10.2 Thermal Time Constant 1.00~100.00s 0.01s Heating time constant of thermal protection
10.3 Alarm Coefficient 0.10~0.80 0.01
11 Undervoltage Protection Setting
11.1 Undervoltage Protection Enable 1/0 Undervoltage protection: Enable(1)/Disable(0)
11.2 Undervoltage Trip Mode 1/0 1=Trip, 0=Alarm
11.3 VT Disconnection Block Undervoltage 1/0 1=Block, 0=Not block
11.4 Undervoltage Time Delay 0.10~120.00s 0.01s
11.5 Undervoltage Setting Value 5.00~100.00V 0.01V
12 Overload Protection Setting
12.1 Overload Protection Enable 1/0 Overload protection: Enable(1)/Disable(0)
12.2 Overload Trip Mode 1/0 1=Trip, 0=Alarm
12.3 Overload Time Delay T 0.00~120.00s 0.01s
12.4 Overload Current Setting 0.10~99.99A

0.10~20.00A

0.01A In=5A

In=1A

13 Zero Sequence Overcurrent Setting
13.1 Zero Sequence Overcurrent Enable 1/0 Zero sequence overcurrent: Enable(1)/Disable(0)
13.2 Zero Sequence Trip Mode 1/0 1=Trip, 0=Alarm
13.3 Zero Sequence Direction Block 1/0 Direction block function: Enable(1)/Disable(0)
13.4 Small Current Grounding Line Selection 1/0 Line selection: Enable(1)/Disable(0)
13.5 Line Selection Polarity Reverse 1/0 1=Reverse polarity, 0=Positive polarity
13.6 Zero Sequence Time Delay 0.00~120.00s 0.01s
13.7 Zero Sequence Current Setting 0.10~5.00A

0.40~99.00A

0.01A Small current grounding system

380V 3-phase 4-wire grounding system

14 Overvoltage Protection Setting
14.1 Overvoltage Protection Enable 1/0 Overvoltage protection: Enable(1)/Disable(0)
14.2 Overvoltage Trip Mode 1/0 1=Trip, 0=Alarm
14.3 Overvoltage Time Delay 0.10~120.00s 0.01s
14.4 Overvoltage Setting Value 20.00~120.00V 0.01V
15 Auto-restart Setting
15.1 C10 Auto-restart Function 1/0 C10 as auto-restart: Enable(1)/Disable(0)
15.2 Auto-restart Time Delay 0.00~120.00s 0.01s
16 General Setting
16.1 VT Disconnection Alarm 1/0 VT disconnection alarm: Enable(1)/Disable(0)
16.2 CT Disconnection Alarm 1/0 CT disconnection alarm: Enable(1)/Disable(0)
16.3 CT Disconnection Block Negative Sequence 1/0 Block negative sequence on CT fault: Enable(1)/Disable(0)
16.4 Control Circuit Break Alarm 1/0 Control circuit break alarm: Enable(1)/Disable(0)
16.5 Current Block Over / Under Voltage 1/0 1=Block, 0=Not block
16.6 Device Test Mode 1/0 1=Test mode, 0=Normal mode
16.7 3-Phase 4-Wire Voltage Wiring 1/0 0=3P3W, 1=3P4W
16.8 Current Input 1A Rated 1/0 1=1A input, 0=5A input
16.9 Rated Voltage 380V 1/0 1=380V, 0=100V
16.10 B17 Maintenance Plate Function 1/0 1=Maintenance plate, 0=Normal remote signal
16.11 Integral Energy Calculation 1/0 1=Calculate, 0=Not calculate
16.12 Harmonic Component Calculation 1/0 1=Calculate, 0=Not calculate
16.13 Current Block Threshold 1.00~10.00A 0.01A
16.14 Sudden Change Startup Current 1.00~10.00A 0.01A

Outline and Installation Dimensions

Front View Dimension Drawing of the Motor protection relay Dimension Drawing of the Rear Side of the Motor protection relay Side Dimension Drawing of the Motor protection relay Dimensions for Cutouts in Motor protection relay

FAQ

Q:Motor protection relay is primarily designed to protect motors, so how should one choose one?

A:There are many types of motor protection relays, and several principles should be considered when selecting one.

First, motors are classified by voltage rating into low-voltage and high-voltage categories; different voltage ratings require different selection methods.

Second, consider the motor’s capacity; generally, motors with higher capacity have more stringent technical requirements.

Third, refer to the project’s technical specifications.

Reviews

There are no reviews yet.

Be the first to review “ASD-441H Motor protection relay”

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.