Intelligent 246H Integrated Measurement and Control Device

The ATN-6101 All-in-One Grid-Connection Communication Device is used in county-wide photovoltaic projects, local power plants and distributed PV systeCommunication Featuresms.

Description

Product Usage

  • The integrated measurement and control device is primarily used for general measurement and control in the integrated automation systems of substations and power plants; it can also be used independently as a standard measurement and control unit, primarily performing telemetry, telecommand, and telecontrol functions.

Features

Device self-test function

  • The device automatically detects faults such as RAM, ROM, A/D, and power loss.
  • Automatically detect parameters such as setpoints, configurations, and coefficients

Event Log

  • Event logs include information on event status and device self-test failures.

Communication Features

  • The device supports four communication modes: RS-485, CAN, wired Ethernet, and fiber-optic Ethernet (specify when ordering);
  • The device uploads real-time data, including measurement data, digital I/O data, alarm signals, configuration settings, and parameters;
  • The device receives control commands from the host system, including remote control and system synchronization.

Monitoring Features

  • The device is equipped with telemetry capabilities to measure analog quantities such as current, voltage, active power, reactive power, power factor, and frequency;
  • It is equipped with telecontrol capabilities to acquire position signals (such as circuit breaker, energy storage, isolating switch, and remote/local) and other digital signals;
  • It is equipped with remote control capabilities to close and open circuit breakers.

The standard features are listed in the table below:

Board Type Power Supply Board Remote Signaling Board Command Output Board Analog Board DC Input Board DC Output Board Communication Board
Board Configuration Optional 32-channel remote signaling 14-channel remote control 8U6I 7/14DC (Optional) 8AO 485, CAN, electrical Ethernet and fiber Ethernet communication (Optional)

General Technical Data

Rated DC Specifications

  • Voltage: 220 V or 110 V (please specify when ordering);
  • The ripple factor of the DC voltage shall not exceed 2%, and the voltage fluctuation range shall be 80% to 110% of the rated voltage.

Rated AC Data

  • Rated AC current In: 5 A, 1 A (specify when ordering);
  • Rated AC voltage Un: 57.7 V, 100 V;
  • The AC power supply waveform is a sine wave with a distortion factor not exceeding 2%;
  • Frequency fn: 50 Hz, with a permissible deviation of ±0.5%.

AC input range

  • Current input range: The device can operate continuously when a current of 1.2In is applied;
  • Voltage input range: The device can operate continuously when a voltage of 1.2Un is applied;

Power Consumption

  • Total power consumption shall not exceed 8 W;
  • AC voltage circuits shall not exceed 0.5 VA per phase;
  • AC current circuits shall not exceed 0.5 VA per phase.

Environmental Conditions

Standard atmospheric conditions

Ambient temperature

  • Operating conditions: –20°C to +70°C, relative humidity 5% to 95% (no condensation or freezing inside the unit);
  • Storage: –30°C to +80°C. When no excitation is applied at the extreme temperature limits, the device shall not undergo irreversible changes, and it shall function normally once the temperature returns to normal. Packaged devices shall be stored at an atmospheric pressure of 80–110 kPa (equivalent to an altitude of 2 km or less) and a relative humidity of no more than 85%.
  • Transportation: -25°C to +70°C, relative humidity not exceeding 85%;

Other requirements

  • The air around the equipment must not contain any acidic, alkaline, corrosive, or explosive substances.

Surroundings

  • The installation site must be protected from sunlight, rain, and snow; shielded against lightning strikes and dust; and well-ventilated;
  • Electromagnetic interference exceeding the limits specified in Clause 2.7 is not permitted;
  • The installation site shall comply with the Class B safety requirements specified in GB/T 9361;
  • The operating environment shall not be subject to vibration exceeding Severity Level 1 as defined in GB/T 11287-2000; during transportation and storage, the equipment shall not be subjected to shock or impact exceeding Severity Level 1 as defined in GB/T 14537-1993;
  • The environment must not contain explosive substances, corrosive media capable of damaging metals, insulation, or surface plating and coatings, or conductive media; significant moisture is not permitted, nor is the presence of severe mold;

FAQ

Q:What is the primary function of a common measurement and control device? Where is it installed, and how should one select it?

A:Public monitoring and control units feature a greater number of analog input points, digital input points, and relay output points. These allow for the acquisition of the power system data required at the power station. They are typically installed as panel assemblies in the substation. When selecting a unit, it is necessary to consider the number of analog, digital, and relay output points, as well as other parameters.

Reviews

There are no reviews yet.

Be the first to review “Intelligent 246H Integrated Measurement and Control Device”

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.