Motor Protection Relay

Industrial Electronic Motor Protection Relay for Motor Circuit Safety 49/50/51/46/27/59/87M

During operation, motors shall be protected or alarmed against overload, phase loss, locked rotor, short circuit, overvoltage, undervoltage, earth leakage, three-phase unbalance, overheating, bearing wear as well as stator and rotor eccentricity. Therefore, dedicated protection is essential for electric motors.

Motor Protection Relay types

English NameANSI CodeFunction Description
Instantaneous Overcurrent50Trips immediately in case of severe short circuit faults
Time-delay Overcurrent51Acts with time delay against motor overload and minor locked rotor
Ground/Earth Leakage Overcurrent50G / 51GDetects stator and line ground faults and earth leakage
Negative Sequence / Three-phase Unbalance / Phase Loss46Protects against open phase, current unbalance and abnormal phase sequence
Locked Rotor Protection51LR / 66Provides protection when rotor is stuck during startup or operation
Thermal Overload Protection49MPrevents motor burnout caused by long-term overheating via thermal model
Winding Temperature Protection26Monitors motor winding temperature and triggers action at over temperature
Undervoltage Protection27Protects motor when grid voltage drops abnormally
Overvoltage Protection59Activates protection against excessively high grid voltage
Phase Reversal Protection46RPrevents motor reverse rotation for pumps, fans and similar loads
Frequency Deviation Protection81Monitors abnormal grid frequency
Underload Protection37MDetects no-load condition and loss of load
Reverse Power Protection32Avoids reverse power caused by motor driven by external equipment
Motor Differential Protection87MProtects large high-voltage motors against internal inter-turn and inter-phase faults
Bearing Wear Monitoring/Monitors abnormal wear of motor bearings
Stator & Rotor Eccentricity Monitoring/Detects eccentricity faults of stator and rotor

The above is a summary of electric motor relay protection functions. Below is a detailed introduction to the common electric motor relay protection features.

Introduction to Motor Protection Functions of Electric Motor Protection Relays

87M Protection Relay

For motors with a rated power of 2000 kW and above, or motors below 2000 kW where the instantaneous overcurrent protection relay fails to meet the sensitivity requirements, differential protection shall be adopted to protect against phase-to-phase faults inside the motor and on outgoing leads, with the protection operating for tripping.

Motor differential protection calculation

Taking a 2000 kW, 6 kV motor as an example (rated current approx. 220 A, CT ratio selected as 300/1 A, secondary rated current Ie2​≈0.73A), the differential protection calculation is presented as follows:

ItemParameter DescriptionSetting Value
Operating currentSet to 0.4Ie2 to avoid the maximum unbalanced current0.29 A
Inflection point and slopeInflection point current: 1.0Ie2; Ratio restraint slope Kb1=0.40.73 A (inflection point current)
Differential high-speed trippingFor rapid clearance of severe faults, set to 6Ie24.38 A
Auxiliary functionsCT broken circuit blocking threshold: approx. 1.2Ie2; 15% second harmonic restraint enabled to prevent inrush current mal-operation0.88 A (CT broken circuit blocking threshold)

This setting can reliably distinguish internal faults from external abnormalities and guarantee protection selectivity. Specific values shall be verified according to on-site short-circuit current.

Motor protection relay diagram

Motor protection relay

50/51 protection relay

The protection for phase-to-phase faults of motor stator windings is used for motors under 2000 kW and trips on fault. This overcurrent relay protection shares essentially the same principle as transformer and line overcurrent protection.

49 Protection Relay

This overload relay motor protection prevents overcurrent caused by overload of the mechanical equipment driven by the motor. It operates to issue an alarm signal, or trips after a preset time delay

Motor earth fault protection relay

In small earth current systems, single-phase earth fault protection is mandatory for motors with earth current over 5 A. It gives an alarm at 5~10 A and trips above 10 A.

A single-phase earth fault on high-voltage motors does not require immediate shutdown, as it generally does not interfere with normal operation and only disables leakage protection.

For personal safety and to avoid permanent damage, electronic motor protection relays prohibit energizing motors with internal electric leakage.

27 Relay Protection

This 27 undervoltage protection relay prevents motors from auto-restarting when voltage drops or fails, and operates to trip. It can be installed as required.

51LR Protection Relay

The locked rotor protection relay safeguards the motor during operation. When the rotor gets accidentally locked due to overload, it acts rapidly to shut down the motor, so as to prevent or mitigate damage to the drive unit, bearings and other motor components. This function is automatically enabled after motor start-up is completed.

This protection is equipped with two stages of definite-time overcurrent elements, each of which can be set independently. The two elements compare the positive-sequence current after motor start-up with the preset overcurrent threshold. A start signal will be triggered once the positive-sequence current exceeds the setting value. If no locked rotor condition is detected upon expiry of the user-defined time delay, a tripping signal will be issued.

For positive-sequence current greater than 0.2 In, the reset value is approximately 95% of the operating setting.

Motor Differential Protection

37 Undercurrent (or Underpower) Relay

The 37 undercurrent protection relay activates when all three-phase currents of the air-cooled motor drop below the preset current setting, and issues an alarm signal after a set time delay. It will also trigger an undercurrent alarm when the cooling fan stops running.

46 Relay Rrotection

The negative sequence relay is commonly used to protect motors against negative sequence current resulting from asymmetric faults or unbalanced loads in the motor system.

When negative sequence current flows through the stator windings of a three-phase induction motor, a reverse rotating electromagnetic field is generated, which produces double-frequency current in the rotor. This induces eddy currents on the rotor surface and causes overheating at rotor ends and slot edges.

If the negative sequence current exceeds the motor’s withstand capability, the rotor will overheat and endanger the safe operation of the motor.

This protection is configured with two stages of definite-time overcurrent and one stage of inverse-time overcurrent, all of which can be set independently. Analog channel selection is available for the operating quantity of negative sequence overcurrent protection, allowing users to choose either protection CT or measuring CT.

40 Protection Relay

The loss of excitation protection relay is specially designed for synchronous motors. When a synchronous motor loses excitation or operates with insufficient excitation, it will fall out of synchronism, along with changes in current, voltage, power factor and other electrical parameters. By monitoring these variations, the relay can detect and handle loss-of-excitation faults promptly to protect the motor from damage.

The Loss of Field Protection generally consists of out-of-step protection and under-excitation protection. The out-of-step protection detects the out-of-step condition of synchronous motors and trips the circuit once a fault is identified, preventing continuous operation under out-of-step status. The under-excitation protection monitors the excitation level.

It issues an alarm or initiates tripping when excitation is insufficient, so as to protect the motor from damage caused by under-excitation.

Thermal Overload Protection Relay

The thermal overload relay motor protection, one of the motor protective relays, protects the motor by monitoring its temperature.

The motor temperature will rise during prolonged operation or heavy loading, and may burn out without timely intervention.

Equipped with temperature sensors mounted on the motor, this protection tracks temperature in real time. When the temperature exceeds the preset threshold, it trips the circuit or triggers an alarm to prompt operators to lower the motor temperature.

Motor Dry Run Protection Relay

It is widely used for pump and fan motors. This protection functions under dry running and dry grinding conditions when the equipment operates without water or media, preventing component wear and motor overheating damage. It is commonly equipped in pump motor protection relays.

Summary of Motor Protection Functions

Refer to the motor protection relay setting guide for relay setting for motor protection, including the configuration of protection functions and parameters.

Motor Relay Protection Selection Method from China Motor Protection Relay Factory

Select protection relays according to motor capacity.

Power < 200 kW: Thermal relays or magnetic starters are sufficient.

Power range 200 kW to 2000 kW: Adopt smart motor protection relays (with protection functions against overload, locked rotor, phase unbalance, etc.).

Power > 2000 kW or for stringent process requirements: Differential protection shall be equipped, and protection devices shall be configured in dual redundancy.

The products are sorted by voltage level.

Motor protection falls into two categories: 400V low-voltage motor protectors and high-voltage motor protection for voltage levels of 6kV and higher.

Types of Motor Protection Devices Classified by Function and Product Type

Comprehensive Motor Protection Device

Motor Differential Protection Device

Motor Magnetic Balance Protection Device

Motor Protection Device for Variable Frequency Start-up

Conclusion

From accurate motor protection relay setting calculation to favorable motor protection relay price, we stand ready to serve you. Being a professional China motor protection relay supplier, we supply qualified China motor protection relay for sale worldwide.

Leave a Reply

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.