Protection Relays for Petrochemical and Chemical Plants

What Stops a Plant

In a refinery or chemical plant the electrical network is designed around one rule: a process trip costs far more than the electrical equipment that prevented it. Two things dominate. First, motors – pumps, compressors, fans and extruders – fail thermally, lose a phase, or run into a stalled rotor, and a motor protection relay that trips late has already damaged the winding. Second, switchgear arc faults: an arcing fault in a live cubicle releases energy that no overcurrent curve clears fast enough, and the people in front of the panel take the consequence.

The third is stability. When the utility supply dips or a generator trips, the plant either sheds load deliberately in a controlled sequence or loses the whole board.

Devices We Supply for Plant Electrical Networks

Motor Protection in Practice

Thermal replica overload (49), instantaneous and time-delayed overcurrent (50/51), earth fault (50N/51N), negative sequence / unbalance (46), locked rotor and stall (48/51LR), start supervision (66), undercurrent (37) for pump loss of load, and differential (87M) above roughly 1 MW. Starting against a closed valve, a frequent-start duty and a hot restart after a trip are the three cases where a generic overload curve is not enough – which is why the setting work matters as much as the device.

Arc Flash Protection

The ATN-800H detects the light of an arc through optical sensors in the cubicle and trips in a few milliseconds, well ahead of the overcurrent curve. In plants where maintenance staff work on or near energised switchgear, it is the single most effective electrical safety measure on the board.

Send Us the Motor List

Send the motor list with rated kW, full load current, starting method, locked rotor time and duty cycle to our engineering team. We will return the recommended relay model per motor, the setting sheet and the quotation.

Common Specifications

Ambient operating range-25 to +55 °C
Rated frequency50 / 60 Hz
Routine testingIEC 60255 routine tests on every unit before shipment
CommunicationIEC 61850, Modbus RTU / TCP where specified on the datasheet
MountingPanel, rack or switchgear cubicle, per product
CertificationCE; quality system certified to ISO 9001:2015

Ordering and Documentation

Minimum order quantity is 1 unit. Standard lead time is 7 to 15 working days, with EXW, FOB, CIF or DDU terms as agreed on the quotation. Every order ships with the datasheet, manual, connection diagram and factory routine test report matched to the exact model and firmware version. See Technical Downloads for the document set and Quality and Certifications for the CE certificate, ISO 9001:2015 certificate and type test reports.

OEM and ODM supply is available: branding, labelling, document sets and enclosure details are agreed in writing before production. All equipment carries a 12-month warranty against manufacturing defects.

Send the single-line diagram, CT/VT ratios and the protection functions you need to our engineering team and we will return the matching configuration, documents and quotation.

Equipment referenced in this sector note: the ATN-800H arc flash protection relay, the ASD-441H motor protection relay and the 87T transformer differential relay.