400V Low Voltage Generator Protection Relay
Low Voltage Generator Protection Relay delivers complete generator fault protection for 400V standby generator units. Equipped with negative sequence, 59N grounding, reverse power and loss-of-excitation protection, compatible with industrial SCADA systems for remote monitoring and fault data logging.
Description
- Our low voltage generator protection relay is a high-performance microcomputer-based protection and monitoring unit specially developed for 400V low-voltage synchronous generators, diesel generators, gas generators and small hydropower generator sets.
- Integrating professional electrical protection, real-time data measurement, signal acquisition and intelligent communication functions in one compact device, it solves common fault risks of low-voltage generators in industrial power stations, commercial backup power systems and distributed power generation projects.
Protection Configuration
| Protection Item | Function Description | Operation Mode |
|---|---|---|
| Instantaneous Overcurrent | – | Trip |
| Time-delayed Instantaneous Overcurrent | With undervoltage blocking | Trip |
| Overcurrent | – | Trip |
| Inverse Time Overcurrent | Normal / Very Inverse / Extremely Inverse characteristic curves optional | Trip |
| Overload | Alarm or trip configurable | Alarm / Trip selectable |
| Zero-sequence Overcurrent | Self-produced zero-sequence current function optional | Alarm / Trip selectable |
| Overvoltage | – | Trip |
| Undervoltage | Current-blocked undervoltage protection optional | Alarm / Trip selectable |
| Overfrequency | – | Trip |
| Underfrequency | – | Trip |
| Reverse Power | – | Trip |
| CT Broken Circuit | – | Alarm |
| PT Broken Circuit | Undervoltage protection blocked upon PT failure | Alarm |
| Control Circuit Breakage | – | Alarm |
Product Advantages
Industrial-Grade Stability
Adopts anti-interference industrial hardware design with a wide operating voltage range. It runs reliably under high temperature, high humidity and strong electromagnetic interference conditions, ideal for long-term unattended operation of generator sets.
High Precision & Low Measurement Error
Features Class 0.2 electrical measurement accuracy, guaranteeing precise monitoring of generator operating parameters and dependable protection tripping actions.
Easy Installation & Commissioning
Diversified Communication Protocols
Cost-Effective Integrated Design
Low Voltage Generator Protection Relay setting
| No. | Menu Item (Setting Name) | Setting Range | Default Value | Remarks |
|---|---|---|---|---|
| 1 | PT Primary Rated Voltage | 0.1~999.99KV | 10KV | – |
| 2 | PT Secondary Rated Voltage | 100~999V | 100V | – |
| 3 | Measuring CT Primary Rated Current | 1~9999A | 600A | – |
| 4 | Measuring CT Secondary Rated Current | 1~5A | 5A | 5A or 1A |
| 5 | Protection CT Primary Rated Current | 1~9999A | 600A | – |
| 6 | Protection CT Secondary Rated Current | 1~5A | 5A | 5A or 1A |
| 7 | Zero Sequence CT Secondary Rated Current | 1~5A | 5A | 5A or 1A |
| 8 | Reserved | – | – | – |
| 9 | Number of PTs | 2~3 | 3 | – |
| 10 | Number of Measuring CTs | 2~3 | 3 | – |
| 11 | Zero Sequence Voltage Self-generation | 0~1 | 0 | 0: External; 1: Self-generated |
| 12 | Zero Sequence Current Self-generation | 0~1 | 0 | 0: External; 1: Self-generated |
| 13 | Protection Ia Polarity Reversal | 0~1 | 0 | Default |
| 14 | Protection Ib Polarity Reversal | 0~1 | 0 | Default |
| 15 | Protection Ic Polarity Reversal | 0~1 | 0 | Default |
| 16 | I0 Polarity Reversal | 0~1 | 0 | Default |
| 17 | Measuring IA Polarity Reversal | 0~1 | 0 | Default |
| 18 | Measuring IB Polarity Reversal | 0~1 | 0 | Default |
| 19 | Measuring IC Polarity Reversal | 0~1 | 0 | Default |
| 20~24 | Reserved | – | – |
Generator protective relay single line diagram
Application Scenarios
- Backup diesel generator sets for industrial factories
- Low voltage power generation equipment of small and medium hydropower stations
- Standby power supply systems for commercial buildings, hospitals and data centers
- Distributed power generation and off-grid power supply projects
- Marine and mobile low voltage generator units