Protection Relays for Coal Mining and Mine Power Systems

The Earth Fault Problem Underground

Most mine distribution networks run either isolated or earthed through an arc suppression coil. Both arrangements keep the earth fault current low enough to be safe, and both make the fault hard to find: a single-phase earth fault does not trip the feeder, and the faulted circuit has to be identified and removed before a second fault on another phase turns into a phase-to-phase short.

That is the job of small current grounding line selection. It compares the zero-sequence transients of every feeder on the busbar, identifies the faulted one and signals it to the operator – so the faulted feeder is switched out deliberately instead of the whole section tripping.

Devices We Supply for Mine Networks

Why Line Selection Beats Tripping

Tripping the busbar on a single-phase earth fault stops production for every section fed from it. Line selection lets the operator transfer load first, then isolate the faulted feeder. In a mine where ventilation and dewatering cannot stop, that difference is the whole point of the device.

The 610H uses the transient zero-sequence current at the moment of the fault, which is the part of the signal that is unaffected by the arc suppression coil – that is why it works on compensated networks where steady-state methods fail.

Continuous Production Needs Fast Restoration

Feeder automation with fault passage indication and remote control shortens an outage from hours of driving and patrolling to minutes of switching. The DTU-380H provides the remote control and the IEC 61850 interface to the control centre; the protection relays provide the fault detection.

Tell Us the Earthing Arrangement

Send the network earthing arrangement (isolated, resistance earthed or compensated), the number of feeders on each busbar, the CT ratios and the fault level to our engineering team. Line selection performance depends on those parameters, and we will confirm the configuration before quoting.

Common Specifications

Ambient operating range-25 to +55 °C
Rated frequency50 / 60 Hz
Routine testingIEC 60255 routine tests on every unit before shipment
CommunicationIEC 61850, Modbus RTU / TCP where specified on the datasheet
MountingPanel, rack or switchgear cubicle, per product
CertificationCE; quality system certified to ISO 9001:2015

Ordering and Documentation

Minimum order quantity is 1 unit. Standard lead time is 7 to 15 working days, with EXW, FOB, CIF or DDU terms as agreed on the quotation. Every order ships with the datasheet, manual, connection diagram and factory routine test report matched to the exact model and firmware version. See Technical Downloads for the document set and Quality and Certifications for the CE certificate, ISO 9001:2015 certificate and type test reports.

OEM and ODM supply is available: branding, labelling, document sets and enclosure details are agreed in writing before production. All equipment carries a 12-month warranty against manufacturing defects.

Send the single-line diagram, CT/VT ratios and the protection functions you need to our engineering team and we will return the matching configuration, documents and quotation.

Related: Overload Shedding System ASH-441H

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.