-
Leon Zhang sales consultant
-
Email: zxl635973785@gmail.com
-
Phone/WhatsApp: +86 13655813266
ASL-7615 line distance protection relay
Overview
Distance protection measures the distance (or impedance) between the fault location and the protection installation point. Distance relay protection of transmission lines, also referred to as line protection with distance relays, adopts distance relays as the core protective devices, which determine the operating time of protection based on the measured fault distance.
Function Configuration
21/51/51N/51G/79/27/49/81
Communication Mode:Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 (IEC-103)
Description
Guide for protective relay applications to transmission lines
- Distance protection measures the distance (or impedance) between the fault location and the protection installation point. Distance relay protection of transmission lines, also referred to as line protection with distance relays, adopts distance relays as the core protective devices, which determine the operating time of protection based on the measured fault distance.
Function Configuration of Line Distance Protection Relay
Main Protection Functions
| No. | Function Name | ANSI Code |
|---|---|---|
| 1 | Three-stage Distance Protection | 21 |
| 2 | Three-stage Phase Overcurrent Protection | 51 |
| 3 | Two-stage Zero-sequence Overcurrent Protection | 51N / 51G |
| 4 | Three-phase Single-shot Auto-reclosing | 79 |
| 5 | Post-closing Phase / Zero-sequence Current Acceleration Protection | 51ACC |
| 6 | Under-frequency Load Shedding Protection | 81U |
| 7 | Under-voltage Load Shedding Protection | 21 / 27 |
| 8 | Overload Alarm | 49 |
| 9 | Zero-sequence Current Alarm | 51N |
| 10 | Ground Fault Alarm | 51G |
| 11 | Frequency Anomaly Alarm | 81 |
| 12 | Spring Uncharged Alarm | — |
| 13 | Control Circuit Break Alarm | — |
| 14 | TWJ Abnormal Alarm | — |
| 15 | PT Broken Line Alarm | 60 |
| 16 | CT Broken Line Alarm | 60 |
| 17 | Fault Waveform Recording | — |
Main Measurement & Control Functions
- 8-channel remote signal binary input acquisition and device remote signal displacement;
- Remote measurement of 14 analog quantities including Ia, Ib, Ic, 3I0, Ua, Ub, Uc, Uab, Ubc, Uca, P, Q, COSφ and F;
- Remote opening and closing control;
- Small current ground fault line selection test trip (auto-reclosing function supported, external zero-sequence current input required);
- Time synchronization.
Principle

- Protection of transmission line with distance relay adopts the working principle of distance protection. Distance protection works by using an impedance relay to measure the impedance between the fault location and the protection installation point, thereby determining the distance to the fault.
- As a core protective relay product for transmission line, it takes the ratio of the busbar voltage at the protection installation point to the line current as the measured impedance, which reflects the impedance between the protection installation point and the fault location.
- For protective relay transmission line application scenarios, the measured impedance is directly proportional to the distance from the fault location to the protection installation point and is largely unaffected by the operating mode; therefore, the range of distance protection remains essentially constant regardless of changes in operating mode.
line diagram protective relay descriptions

Transmission Line Protection Distance Relays — Setting List
| No. | Setting Name | Setting Range (IN=1A or 5A) | Unit | Remarks |
|---|---|---|---|---|
| 1 | Variation Starting Current Setting | (0.05 ~ 3)IN | A | |
| 2 | Line Positive Sequence Impedance Setting | (0.05~655)/In | Ω | |
| 3 | Line Positive Sequence Impedance Angle | 30°~89° | — | |
| 4 | Total Line Length | 0~655 | km | |
| 5 | Phase Distance Zone I Setting | (0.05~125)/In | Ω | |
| 6 | Phase Distance Zone II Setting | (0.05~125)/In | Ω | |
| 7 | Phase Distance Zone II Time Delay | 0.01~10 | s | |
| 8 | Phase Distance Zone III Setting | (0.05~125)/In | Ω | |
| 9 | Phase Distance Zone III Time Delay | 0.01~10.00 | s | |
| 10 | Overcurrent Zone I Setting | (0.05 ~ 20)IN | A | |
| 11 | Overcurrent Zone I Time Delay | 0 ~ 10 | s | |
| 12 | Overcurrent Zone II Setting | (0.05 ~ 20)IN | A | |
| 13 | Overcurrent Zone II Time Delay | 0.1 ~ 10 | s | |
| 14 | Overcurrent Zone III Setting | (0.05 ~ 20)IN | A | |
| 15 | Overcurrent Zone III Time Delay | 0.1 ~ 10 | s | |
| 16 | Overcurrent Undervoltage Setting | 10 ~ 100 | V | Line Voltage |
| 17 | Overcurrent Negative Sequence Voltage Setting | 2 ~ 57 | V | U2 |
| 18 | Zero-sequence Overcurrent Zone I Setting | (0.05 ~ 20) | A | |
| 19 | Zero-sequence Overcurrent Zone I Time Delay | 0 ~ 10 | s | |
| 20 | Zero-sequence Overcurrent Zone II Setting | (0.05 ~ 20) | A | |
| 21 | Zero-sequence Overcurrent Zone II Time Delay | 0.1 ~ 10 | s | |
| 22 | Overcurrent Acceleration Setting | (0.05 ~ 20)IN | A | |
| 23 | Overcurrent Acceleration Time Delay | 0.00~ 3 | s | |
| 24 | Zero-sequence Overcurrent Acceleration Setting | (0.05 ~ 20)IN | A | |
| 25 | Zero-sequence Overcurrent Acceleration Time Delay | 0.00~ 3 | s | |
| 26 | PT Broken Line Phase Overcurrent Setting | (0.05 ~ 20)IN | A | |
| 27 | PT Broken Line Phase Overcurrent Time Delay | 0.1 ~ 10 | s | |
| 28 | Overload Setting | (0.05 ~ 20)IN | A | |
| 29 | Overload Time Delay | 1 ~ 3600 | s | |
| 30 | Synchronization Closing Angle | 10°~ 50° | — | |
| 31 | Auto-reclosing Time Delay | 0.1 ~ 10 | s | |
| 32 | High Current Reclosing Block Setting | (0.05 ~ 20)IN | A | |
| 33 | Under-frequency Load Shedding Frequency | 45 ~ 49.5 | Hz | |
| 34 | Under-frequency Load Shedding Time Delay | 0.1 ~ 40 | s | |
| 35 | Under-frequency Slip Block Setting | 0.5 ~ 20 | Hz/s | |
| 36 | Under-frequency Voltage Block Setting | 30 ~ 100 | V | Line Voltage |
| 37 | Under-voltage Load Shedding Voltage Setting | 30 ~ 100 | V | |
| 38 | Under-voltage Load Shedding Time Delay | 0.1 ~ 40 | s | |
| 39 | Voltage Change Rate Block Setting | 10 ~ 200 | V/s | Line Voltage |
| 40 | Power Swing Block Overcurrent | (0.05~20)In | A | |
| 41 | Distance Protection Resistance Setting | (0.05~125)/In | Ω | |
| 42 | Accelerated Distance Zone III Time Delay | 0.0~10 | s |
Outline and Installation Dimensions

FAQ
Q:What is the difference between line differential protection and transmission line distance protection relay?
A:Fiber-optic differential protection is based on real-time comparison of currents at both ends of the line; it has no setting blind zones and is not affected by system operating modes or transition resistances.
Distance protection relies on distance protection relays on transmission lines to measure fault impedance and determine the fault distance; it is set using local electrical quantities and is susceptible to interference from system operating conditions and transition resistances.
Q:How difficult are the experiments for line differential protection and line distance protection, respectively?
Q: ANSI standard code for distance protection?
A: Standard ANSI code is 21
Q What is distance protection relay?
ANSI 21 distance protection calculates the impedance from the relay installation point to the fault location. Since impedance is proportional to line length, it judges fault position and trips the circuit breaker selectively without relying on communication channels.
Q What are its advantages compared with line differential protection?
It works independently with no need for fiber communication; can provide remote backup protection for adjacent lines via Zone 3; simpler wiring and lower construction cost. Limitation: Susceptible to arc resistance, power swing and heavy load encroachment.
Q Functions of Zone 1 / Zone 2 / Zone 3
- Zone 1: Instant trip, covers 80%~85% of the protected line to avoid overreach.
- Zone 2: Short time delay, covers the full line plus a small section of the next line, serving as main backup for the protected line.
- Zone 3: Long time delay, covers downstream adjacent lines, acting as remote backup protection.
Q Why cannot Zone 1 cover the entire line?
Fault arc resistance will cause the measured impedance to become larger than actual value. If Zone 1 is set for the whole line, it may fail to trip for faults near the remote end.
Q What is power swing blocking (PSB)?
During system instability and generator out-of-step swing, impedance may fall into protection zones and cause false tripping. PSB identifies swing characteristics and locks distance protection temporarily.
Q What is load encroachment blocking?
Under heavy rated load, normal operating impedance may enter Zone 2/3. This function blocks distance elements to prevent maloperation.
Q Why VT failure blocking is required?
Distance protection needs voltage to compute impedance. If PT/VT loses voltage, impedance calculation becomes invalid; the relay automatically blocks distance protection and sends an alarm.
Q When to use directional distance protection?
For ring networks or tie lines with power bidirectional flow, directional logic ensures the relay only trips for faults within the forward protected direction.
Q How to handle single-phase earth faults?
Zero-sequence distance protection is configured for earth faults, paired with zero-sequence overcurrent (51N) to improve sensitivity for high-resistance earth faults.
Q Typical application scenarios
All voltage level overhead transmission & distribution lines; used as primary protection for short/medium lines and backup protection for differential-protected long lines.
Q Key configurable parameters
Zone reach impedance, time delay of each zone, directional enable, power swing blocking switch, load encroachment threshold, VT supervision enable.
Q Relay trips falsely under normal load
Possible reasons: Zone setting is too large, load encroachment blocking disabled, VT circuit abnormal, system power swing without PSB enabled.
Q Protection fails to trip during line fault
Check CT/VT polarity and wiring, verify zone impedance setting value, confirm protection function is enabled, and check trip circuit integrity.
Q Match with auto-reclosing (79)
After distance protection trips for transient overhead line faults, the relay can trigger single-pole or three-pole auto-reclosing to restore power supply.
Q Can distance protection cooperate with SOTF?
Yes. Switch Onto Fault function trips immediately if a fault exists on the line when closing the breaker.
Q Key site test items
Impedance injection test for three zones, directional characteristic test, VT/CT loop inspection, blocking function simulation test, trip loop check.
Q Is CT secondary circuit allowed to be open?
Strictly prohibited. An open CT secondary will generate dangerous overvoltage and damage the relay.











xiao zhang –
This line distance protection relay (ANSI 21) adopts segmental impedance-type distance logic, effectively resisting load swing and fault transition resistance. Equipped with fault location function and optional multi-protocol communication, widely used for overhead transmission and cable line protection in global power grid projects.
Jack –
Communication protocol compatible with mainstream platforms, stable data upload — good product.
Jack –
Solid hardware workmanship, clearly marked terminals, easy installation.