87G/50/51 Micom Generator Protection Relay

Overview of Micom Generator Protection Relay

Micom Generator Protection Relay belongs to generator protective relays, which is suitable for differential and backup protection of small generators, as well as protection for hydro-generators up to 2 MW and turbine generators up to 10 MW.

Generator Protection Relay Numbers(ANSI):

87/87G/50/51/49/46/50N/51N/40/32/81O/81U/59/27/59N/60/63/27

Communication Mode:Optional: RS-485, CAN bus, Ethernet, IEC 60870-5-103 ,IEC 61850

In-house Factory & Technical Team, OEM ODM Custom Electrical Equipment

Description

Overview of Micom Generator Protection Relay

  • Micom Generator Protection Relay belongs to generator protective relays, which is suitable for differential and backup protection of small generators, as well as protection for hydro-generators up to 2 MW and turbine generators up to 10 MW.

Features and Specifications

  • Differential Instantaneous Trip (Trip)
  • Percentage Differential Protection (Trip)
  • Excessive Differential Current (Alarm)
  • Three-stage Overcurrent Protection (Trip)
  • Inverse-time Overcurrent (Trip; Normal / Severe / Extreme mode optional)
  • Overload Protection (Alarm / Trip optional)
  • Two-stage Negative Sequence Overcurrent Protection (Stage I: Trip; Stage II: Alarm / Trip optional)
  • Inverse-time Negative Sequence Overcurrent (Trip)
  • Three-stage Zero-sequence Overcurrent (Stage I/II: Trip; Stage III: Alarm / Trip optional)
  • Loss of Excitation Protection (Trip)
  • Reverse Power Protection (Trip)
  • Overfrequency Protection (Trip)
  • Underfrequency Protection (Trip)
  • Overvoltage Protection (Trip)
  • Undervoltage Protection (Alarm / Trip optional, with current blocking)
  • Zero-sequence Overvoltage Protection (Alarm / Trip optional)
  • PT Circuit Disconnection (Alarm)
  • CT Circuit Disconnection (Alarm)
  • Control Circuit Disconnection (Alarm)
  • Non-electrical Quantity Protection (Alarm / Trip optional)
  • PT Voltage Loss (Alarm)
  • System Power Loss (Alarm / Trip optional)

Generator Protection Relay Numbers(ANSI):

  • 87/87G/50/51/49/46/50N/51N/40/32/81O/81U/59/27/59N/60/63/27

Measurement and Control Functions

  • Busbar voltage: Ua, Ub, Uc, Uab, Ubc, Uca;
  • Measured current: Ia, Ic;
  • Power: P, Q, COSφ;
  • Frequency: f;
  • Electric energy: EP+, EP-, EQ+, EQ-;
  • Supports 21-channel active binary inputs (AC/DC 220V, DC 100V or DC 48V; voltage level shall be specified when ordering);
  • Equipped with 11 protection output channels, 2 signal output channels, 1 closing position signal output channel, and 1 device power-loss output channel.

Communication Functions

  • Communication Interfaces:

    2 Ethernet ports

    2 RS485 ports; the second RS485 port is multiplexed with the time synchronization port, supporting either communication or time synchronization via configuration setting.

  • Communication Protocols: IEC-103/IEC-61850/Modbus

Time Synchronization Functions

  • Supports time synchronization via communication message, SNTP and IRIG-B.

Printing Functions

  • The device supports dot-matrix printers with serial communication capabilities and can print set values, event logs, and waveform recording events. Translation

Generator Protection Relay Settings

No. Setting Name Setting Range Unit Default Value Remarks
1 Differential Starting Current 0.1–100 A 1
2 Differential Instantaneous Setting 0.1–100 A 5
3 Inflection Point Setting 0.1–100 A 1
4 Ratio Restraint Coefficient 0.1–0.9 0.5
5 Generator Rated Current 0.1–100 A 5
6 Overcurrent Stage I Setting 0.1–100 A 8
7 Overcurrent Stage II Setting 0.1–100 A 7
8 Overcurrent Stage II Time Delay 0–100 S 0.5
9 Overcurrent Stage III Setting 0.1–100 A 5
10 Overcurrent Stage III Time Delay 0–100 S 1
11 Undervoltage Blocking Current Setting 1–400 V 70
12 Negative Voltage Blocking Current Setting 1–400 V 10
13 Inverse-time Overcurrent Setting 0.1–100 A 5
14 Inverse-time Overcurrent Time Delay 0–100 S 1
15 Inverse-time Overcurrent Type 0–3 1 1=Normal, 2=Severe, 3=Extreme
16 Overload Setting 0.1–100 A 5
17 Overload Time Delay 0–100 S 2
18 Overload Type 0–2 1 0=Exit, 1=Trip, 2=Alarm
19 Negative Sequence Overcurrent Stage I Setting 0.1–100 A 2
20 Negative Sequence Overcurrent Stage I Time Delay 0–100 S 1
21 Negative Sequence Overcurrent Stage II Setting 0.1–100 A 1
22 Negative Sequence Overcurrent Stage II Time Delay 0–100 S 2
23 Negative Sequence Overcurrent Stage II Type 0–2 1 0=Exit, 1=Trip, 2=Alarm
24 Negative Sequence Inverse-time Overcurrent Setting 0.1–100 A 5
25 Negative Sequence Inverse-time Overcurrent Time Delay 0–100 S 1
26 Negative Sequence Inverse-time Overcurrent Type 0–3 1 1=Normal, 2=Severe, 3=Extreme
27 Zero-sequence Overcurrent Stage I Setting 0.1–100 A 2
28 Zero-sequence Overcurrent Stage I Time Delay 0–100 S 0.2
29 Zero-sequence Overcurrent Stage II Setting 0.1–100 A 2
30 Zero-sequence Overcurrent Stage II Time Delay 0–100 S 1
31 Zero-sequence Overcurrent Stage III Setting 0.1–100 A 2
32 Zero-sequence Overcurrent Stage III Time Delay 0–100 S 2
33 Zero-sequence Overcurrent Stage III Type 0–2 1 0=Exit, 1=Trip, 2=Alarm
34 Zero-voltage Blocking Zero-sequence Setting 1–400 V 5
35 Loss of Excitation Impedance Setting A 0–100 1
36 Loss of Excitation Impedance Setting B 0.2–200 20
37 Loss of Excitation Protection Time Delay 0–100 S 1
38 Undervoltage Blocking Loss of Excitation Setting 1–400 V 10
39 Reverse Power Protection Setting 0–600 W 50
40 Reverse Power Time Delay 0–100 S 1
41 Overvoltage Setting 1–600 V 120
42 Overvoltage Time Delay 0–100 S 0.5
43 Undervoltage Setting 1–400 V 80
44 Undervoltage Time Delay 0–100 S 1
45 Zero-sequence Overvoltage Setting 1–400 V 30
46 Zero-sequence Overvoltage Time Delay 0–100 S 0.5
47 Zero-sequence Overvoltage Type 0–2 1 0=Exit, 1=Trip, 2=Alarm
48 Overfrequency Protection Setting 35–65 Hz 51
49 Overfrequency Protection Time Delay 0–100 S 0.5
50 Underfrequency Protection Setting 35–60 Hz 49
51 Underfrequency Protection Time Delay 0–100 S 0.5
52 Undervoltage Blocking Frequency Setting 1–400 V 20
53 Slip Blocking Frequency Setting 1–30 Hz/S 3
54 PT Disconnection Time Delay 0–100 S 5
55 PT Voltage Loss Time Delay 0–100 S 5
56 Control Circuit Disconnection Time Delay 0–100 S 10
57 System Power Loss Type 0–2 1 0=Exit, 1=Trip, 2=Alarm
58 Thermal/Hydraulic Accident Type 0–2 1
59 Thermal/Hydraulic Accident Time Delay 0–100 S 0.1
60 Excitation Fault Type 0–2 1
61 Excitation Fault Time Delay 0–100 S 0.1
62 Electrical Accident Type 0–2 1
63 Electrical Accident Time Delay 0–100 S 0.1

Note: Refer to the manual for generator protection relay setting calculation instructions.

Outline and Installation Dimensions

   

FAQ

Q:which relay is used for generator protection?

A:Generator out of step protection relays, reverse power relay for generator protection, three-stage generator current protection, generator loss-of-field protection, generator rotor protection relay,generator differential protection, etc.

Q:which relay is used for generator protection?

A:The generator protection relay price is generally around 6,000 RMB, with higher-specification models costing more.

Reviews

There are no reviews yet.

Be the first to review “87G/50/51 Micom Generator Protection Relay”

Your email address will not be published. Required fields are marked *

High Quality

Stable performance, reliable design, ensuring safe operation for power system protection and grid stability.

Fast Delivery

Timely delivery to support your urgent orders and project schedules efficiently and professionally at any time.

Best Warranty

Professional Warranty: Reliable after-sales support for stable relay protection and long-term customer satisfaction.